Download TR4 Direct Cylindrical
Transcript
en Operating Instructions Electrical installation Chapter 5 TR4 5.3.4 Connection of several safety switches in a cascade Several safety switches with cable (TR4-S....P) or an 8-pin M12 connection plug (TR4-S..01C) can be cascaded (connected in series). The number of safety switches in a cascade is almost unlimited. However it will have an effect on the response time of the system (see section 9.1.2 “Response time for multiple cascaded TR4 safety switches” on page 83). It is therefore recommended not to use more than 30 safety switches in a cascade. Use external device monitoring! WARNING The TR4 has no external device monitoring. To achieve SIL3/PL e you must therefore implement external device monitoring with the aid of suitable higher level safety evaluation. The actual performance level or safety integrity level achieved depends on the external circuit, the design of the wiring, the selection of the control switch and its placement on the machine. Evaluate both safety outputs! To ensure safety it is imperative you evaluate both safety outputs (Out A and Out B) (see Fig. 6). Prevent tampering! On the usage of TKplug connectors for cascading you must mount the connecting cables such that simple bypassing of the safety switch is not possible. 8014465/YIJ2/2015-03-02 Subject to change without notice © SICK AG • Industrial Safety Systems • Germany • All rights reserved 69