Download Corrigo E - User Manual - Xref controls e-shop
Transcript
Chapter 8 Configuration Start by logging on at System level. See section Access rights above. Using DOWN, set the display marker opposite the menu-title Configuration and press RIGHT. The main configuration menu will be shown. Inputs/Outputs HS Supply Return temp Pump stop Twin/Single pump Run ind/Motor prot Actuator type Actuator run time Actuator exercise Leakage monitoring Pulse inputs Alarm config. Other params System 8.1 In- and Outputs Analogue inputs Digital inputs Universal inputs Analogue outputs Digital outputs General Free configuration Any control signal can be bound to any input/output, the only restriction being that digital signals cannot be bound to analogue inputs and vice versa. It is up to the user doing the binding to make sure that activated functions are bound to appropriate signals. Delivery setting On delivery all the physical inputs and outputs have already been bound to a signal. The delivery settings are suggestions only and can easily be changed. 8.1.1 Analogue inputs AI Analogue input 1 Sign: Outdoortemp Raw value: 18.3 Compensation: 0.0°C All analogue inputs are for PT1000 or 0-10 Volts. Input signals can be compensated for example for wiring resistance. The Raw value will show the actual uncompensated input value. If an input has been assigned to pressure control the following submenu will be available: AI2 Pressure at 0V: 0.0 kPa 10V: 10.0 kPa Filter factor: 0.2 Corrigo E Heating manual, revision G Chapter 8 Configuration 26