tion is activated, the controller automatically switches
the pump on every 30 minutes for 30 seconds.
7.5
Anti-freeze function (F2)
If the anti-freeze function is activated, the controller
switches the pump on as soon as the collector temperature T1 falls below +5 °C. The heat transfer fluid
is thus pumped through the collector and tries to prevent refreezing. If the collector reaches a temperature
of +7 °C, the pump is switched off again.
CAUTION
System can freeze despite the activated anti-freeze
function!
During a power outage (the anti-freeze function does
not operate).
During long-term periods of frost (due to restricted
water tank heat storage).
If collectors are mounted in locations exposed to wind.

It is recommended to generally use the heat carrier
fluid with antifreeze for Solar Plants.
Standard antifreeze liquid for solar energy systems also
contain an additional corrosion inhibitor.