Download GTR-600 User manual
Transcript
A. Genset Info.: Display generator inforamtion B. Event Record: Display operation history C. Parameter Modify: 1. Crank Settings 1. Detect Frequency Setting:Disable/ Enable Default:Enable Description:Check frequency value before cranking the engine. 2. Detect oil press Setting:Disable/ Enable Default:Enable Description:Check oil pressure before cranking the engine. 3. Crank interval Setting:5~40(seconds) Default:10 Description:Set the duration of each crank. 4. Crank attempts Setting:1~10 Default:3 Description:Set total number of crank attempts. 5. Escape up limit Setting:15~30(Hz) Default:20 Description:When frequency reaches setting, starter motor disconnects from engine. 6. Engage low limit Setting:15~30(Hz) Default:20 Description:If frequency is below setting allows crank procedure 7. OP build up time Setting:0.2~2.0(Seconds) Default:0.6 Description:Time delay before disconnecting starter motor after oil pressure switch activates. (“Detect oil press” must be enabled.) 8. Idle interval Setting:0~600(Seconds) Default:0 [9]