VM2-Series Flow Meter User’s Manual
I. Functions & Features:
Input Signal
Analog Input Type
Pulse Input Type
DC Voltage(1~5V) / DC Current (4~20mA)
NPN Pulse (0.05Hz~5KHz)
28 ~ 56 times/sec.
50~999ms
Sampling
Period
0.1% FS
Accuracy
Display Range 0 ~ 99999(Instant) / 0~99999999 (Sum)
0.03% FS
0.36" (red) / 0.3" (green)
Direct setting or Teaching. Decimal place can be planned at will.
External Function Resets / pause the total flow, processes radicals of input value
Output Mode 3 output modes (Manual, Return, and Continue) for option.
Character Height
Scaling Setting
Optional
Function
Relay contact output: 1~2 levels(a, b)
Analog output: 4~20mA, 1~5V, 0~10V
Communication: RS-232, RS-422, RS485
II. Panel Explanation:
ESC
Total Flow
SET
HOLD
OUT1
OUT2
OUT3
OUT4
COMM
PEAK
ZERO
TEACH
Escape Key
Set Key
Up Key
ZO/TH
Shift Key
Zero / Teach Key
Instantaneous
Value
Status Index Lamp
Output Index Lamp
v Function Explanation:
q Total Flow Display Window: Displays present accumulated value and set value at setting
mode.
q Instantaneous Value Display Window: Displays the instant flow rate of input value.
q Explanation of Index Lamps:
HOLD: When External Input Control pauses the accumulation, the index lamp starts to blink.
ZERO : When Forced Zeroing is enabled, the index lamp will be turned on.
TEACH : When scaling setting inputs, the index lamp will be turned on. As the software starts
teaching function, the lamp starts to blink.
q Key Functions:
ESC
To switch parameter setting pages, cancel settings, or return to man display.
SET
To enter parameter setting or confirm setting.
To change value. Being pressed for 1 second can make the auxiliary display
window switch between set value or peak value.
To change currently set digit or change parameter directly.
ZO/TH
+
+
ZO/TH
Being held for 1 second can force to zero, or to enable teaching function when
setting values.
Hold for 1 second to cancel forced zeroing.
Hold for 1 second to clear record of peak value (works only when the
auxiliary window is displaying peak value.
III. Operation Instruction:
q Comparative Value Setting:
Main Display
SET
SET
Setting 1
1 sec.
SET
ESC
ESC
SET
Setting 2
Confirm Setting
Cancel Setting
Change Value
Change Digit
ESC
SET
Timer
ESC
SET
q Instruction of Selecting Parameter Setting Page:
v The system parameters are divided into 3 categories. To prevent erred settings so as to cause
Malfunctions, users can only change general settings after system starts. To change advanced
settings, users must switch to the corresponding page.
ESC
3 sec.
SET
ESC
Confirm Setting
Cancel Setting
Change Setting Page
The circles go off one by one.
q Instruction of Entering Parameter Setting:
v After selecting correct setting page, select the parameter your want to adjust.
SET
3 sec.
SET
ESC
The circles go off one by one.
Change parameter or
press for 1 sec. to enter
setting.
Cancel and return to
main display.
q Instruction of Setting Parameters:
v When the parameter to set appears in the display window, press
setting mode.
SET
SET
for 1 second to enter
1 sec.
SET
ESC
Blinks
Confirm Setting
Cancel Setting
Change Setting
Blinks
SET
1 sec.
SET
ESC
Confirm Setting
Cancel Setting
Change Value
Change Set Digit
IV. List of Parameters:
Parameters of Analog Input Type:
Item
Display
Filter
Setting Range
Function Description
To filter out the surge of input signals and regular
Null/Fast/Normal/Slow/Slower
pulsation.
General
Moving Average
1 ~ 16
To filter noise, making display more stable.
Simple Average
1 ~ 16
To make display slower and more stable.
Peak Display
Positive / Negative
Time Base
Second / Minute / Hour
Decimal of Total
0.0000000/…/0.
Output Mode
Manual/Return/Continue
Decimal Place
Display selection of peak value.
Time base, please set second, minute, or hour according to
actual requirements.
To set the decimal place of total value.
Setting of output modes.
0.0000/0.000/0.00/0.0 To set the decimal place of displayed value.
Scaling
Communication
Input 1
-19999 ~ 99999
The input value corresponds to Display 1 (can be set through
Teaching function).
Display 1
-19999 ~ 99999
The value corresponds to Input Scaling 1.
Input 2
-19999 ~ 99999
The input value corresponds to Display 2 (can be set through
Teaching function).
Display 2
-19999 ~ 99999
The value corresponds to Input Scaling 2.
Analog Input
RATE/TOTAL
Selection of analog output source (Rate / Total Value).
Analog Output 1
-19999 ~ 99999
Analog Output 2
-19999 ~ 99999
Mode
ASCII/RTU
Address
1 ~ 255
Baud Rate
119200/9600/4800/2400
The displayed value that the lowest point of analog output
corresponds to.
The displayed value that the highest point of analog output
corresponds to.
Setting of communication modes. Set according to actual
requirements
For data identification during communication. Must not be
repeated in the same system.
Setting of Baud rate. Higher speed has inferior noise resisting
ability.
Setting Range
Function Description
Parameters of Pulse Input Type:
Item
Display
Filter
To filter out the surge of input signals and regular
Null/Fast/Normal/Slow/Slower
pulsation.
General
Sampling Time
50~999ms
Peak Display
Positive / Negative
Time Base
Second/Minute/Hour
Decimal of Total
0.0000000/…/0.
Output Mode
Manual/Return/Continue
Decimal Place
Setting of sampling time; the smaller the value, the faster the
speed.
Display selection of peak value.
Time base, please set second, minute, or hour according to
actual requirements.
To set the decimal place of total value.
Setting of output modes.
0.0000/0.000/0.00/0.0 To set the decimal place of displayed value.
Scaling
Communication
Scaling
0.00001 ~ 999.99999
The input value corresponds to Display Scaling.
Analog Input
RATE/TOTAL
Selection of analog output source (Rate / Total Value).
Analog Output 1
-19999 ~ 99999
Analog Output 2
-19999 ~ 99999
Mode
ASCII/RTU
Address
1 ~ 255
Baud Rate
119200/9600/4800/2400
The displayed value that the lowest point of analog output
corresponds to.
The displayed value that the highest point of analog output
corresponds to.
Setting of communication modes. Set according to actual
requirements
For data identification during communication. Must not be
repeated in the same system.
Setting of Baud rate. Higher speed has inferior noise resisting
ability.
q Scaling Setting
q Analog Output Setting
DA-HI
DSP-1
Input
Instantaneous
Value
Display
Value
DSP-2
DA-LO
IN-1
Output
Metered
Value
IN-2
MIN(4mA)
v Allows to be set via Teaching function
(Analog Input type).
4-20mA
1-5V
0-10V
V. Three Output Modes
q Manual
Load Impedance
< 400Ω
> 250Ω
> 500Ω
q Return
OUT1
OUT1
OUT2
OUT2
MAX(20mA)
Resolution Output Accuracy
5uA
0.5% FS
1.25mV
0.2% FS
2.5mV
0.2% FS
q Continue
OUT1
T
OUT2
T
T
T
RESET
VI. Wiring Diagram:
q Analog Input Type
OUT3
q Pulse Input Type
OUT2
OUT1
(Analog Output)
10
11
12
13
14
15
16
9
18
10
19
8
11
22
7
OUT2
6
5
4
3
2
12
13
14
15
16
OUT1
1
8
7
6
5
4
3
Input
19
2
1
AC/DC
100~240V
COM
Reset cumulant
Grounding
18
21
Pause
accumulation
COM
Reset cumulant
Pause
accumulation
Radical
AC/DC
100~240V
9
17
20
(Aux. Power) (Comm. Port)
1 2 3 4 5
21
Input
Grounding
17
20
(Aux. Power) (Comm. Port)
1 2 3 4 5
22
OUT3
(Analog Output)