Download type A2USHCPU-S1 User's Manual
Transcript
4. CPU MODULE MELSEC-A 4.1.3 Operation processing upon momentary power failure The PC CPU detects a momentary power failure when input power voltage supplied to the power supply module becomes lower than the specified range. When the PC CPU detects a momentary power failure, following operation processing is performed. (1) When a momentary power failure shorter than allowable period of momentary power failure occurred: (a) When a momentary power failure occurred, operation processing is interrupted while the output state is retained. (b) When the momentary power failure is reset, operation processing will be continued. (c) When a momentary power failure occurred and the operation was interrupted, measurement of the watchdog timer (WDT) continues. For instance, when the scan time is 190ms and a momentary power failure of 15ms occurs, it causes the watchdog timer error (200ms). Momentary power failure occurred END 0 Power supply restoration END END A2USHCPU-S1 interrupts the operation. Operation processing upon momentary power failure (2) When a momentary power failure longer than the allowable period of momentary power failure occurred: The PC CPU performs the initial start. The operation processing is the same as power-on or reset operation with the reset switch. 4-7