FP0 Precautions During Programming 8.3 Handling Index Registers R0 DF F81 BIN, WX1, IX 1 F81 BIN, WX0, IXSV0 2 1 Convert the BCD timer number data in WX1 to binary and set it in index register IX. 2 Convert the BCD timer set value in WX0 to binary and stored in the timer set value area SV specified by contents of IX. Example 2: External output of the elapsed value in a timer number specified by a digital switch WY0 7-segmenet indicator Timer elapsed value display PLC Timer number setting 1 Digital switches WX1 R1 DF F81 BIN, WX1, IX 1 F80 BCD, IXEV0, WY0 2 1 Convert the BCD timer number data in WX1 to binary, and set it in index register IX. 2 Convert the elapsed value data EV in the timer specified by IX to BCD, and output it to word external output relay WY0. 8−9