Electrical Installation 4.7.6 06/05 Removing the Connection Bracket for the InterferenceSuppression Capacitor with Operation from an Ungrounded Supply If the cabinet unit is operated from an ungrounded supply/IT supply, the connection bracket for the interference-suppression capacitor of the converter (-U1) must be removed. Unscrew the screws M4 (Torx T20) and remove the connection bracket. Fig. 4-4 Removing the connection bracket for the interference-suppression capacitor NOTE For the following cabinet units, the connecting jumper must be removed in both sub-cabinets: • for 3-ph. 380 V – 480 V AC: 6SL3710-2GE41-1AA0, 6SL3710-2GE41-4AA0, 6SL3710-2GE41-6AA0 • for 3-ph. 500 V – 600 V AC: 6SL3710-2GF38-6AA0, 6SL3710-2GF41-1AA0, 6SL3710-2GF41-4AA0 • for 3-ph. 660 V – 690 V AC: 6SL3710-2GH41-1AA0, 6SL3710-2GH41-4AA0, 6SL3710-2GH41-5AA0 4-20 SINAMICS G150 Operating Instructions