Download User Guide - Isotron Systems
Transcript
Chapter 5: Communications CANbus Wiring Specifications Table 2: CANbus Specifications Power Requirements: 24V Power Supply 24VDC (±4%), 40mA max. per unit + Galvanic Isolation between CANbus and controller: - Circuit protection device Yes 121 terminating resistor Max. Network Cable Length: 1 Mbit/s 500 Kbit/s 250 Kbit/s 125 Kbit/s 100 Kbit/s 50 Kbit/s 20 Kbit/s 25 m 100 m 250 m 500 m 500 m 1000 m 1000 m Note: If you require cable lengths over 500 meters, contact technical support. Table 3: Wiring Considerations • Use twisted-pair cable. DeviceNet® thick shielded twisted pair cable is recommended. • Network terminators: These are supplied with the controller. Place terminators at each end of the CANbus network. Resistance must be set to 1%, 121Ω, 1/4W. • Connect ground signal to the earth at only one point, near the power supply. • The network power supply need not be at the end of the network • Maximum number of controllers in a network: 63 -V L PE H +V -V L PE H +V -V L PE H +V 121 terminating resistor Figure 10. CANbus Wiring Diagram 21