Download Part 5 Troubleshooting
Transcript
Troubleshooting MCAC-VTSM-2011-09 3.20 "P9": Fan module protection Outdoor Unit Display P9(V4+) Error Explanation ODU displays P9. Only V4+ series system would display this code. Supposed Causes 1. 2. 3. 4. Control box is too hot. Fan is blocked or is defective or is not powered correctly. Signal line is loose. Fan module is defective. Troubleshooting P9: Fan module protection Control box is too hot or the heat exchange of fan module is inefficient. Check the heatsink's temperature or move the ODU to a cooler place. Power lines and signal lines of the fan module is defective. Check the lines and fasten their terminal. The fan's motor is blocked or defective. Clear away the block or replace the fan's motor. The power module of the fan is abnormal. Fan module is defective. Replace the corresponding power module. Replace the fan module. Remarks: If P9 occurs 3 times in 30 minutes, system will auto shut down and display H9 malfunction, which can recover only by restarting the machine. At this time, malfunction should be promptly treated to avoid further damage. 196 Troubleshooting