Optidrive ODP-2 User Guide Revision 1.00
Optidrive P2 Easy Start Up Guide
Display
Keypad Operation can be found
on page 14
Control Terminals
Based on factory settings
AC Supply Connection
Safe Torque Off (STO)
Link the terminals as shown above
through the emergency stop
circuit contacts
Supply Voltage
200 – 240 Volts + / - 10%
380 – 380 Volts + / - 10%
L3 L2 L1
PE
Run / Stop 10K Pot
Close the switch to run (enable)
Open the switch to stop
Fuses or MCB
Check drive
Rating info on
Page 33
M
Motor Cable
For correct cable size, see
Technical Data on page 33
Observe the maximum permissible motor
cable length
For Motor cable lengths > 50 metres, an
output filter is recommended
Use a screened (shielded cable). The shield
should be bonded to earth at both ends
Motor Connection
Check for Star or Delta Connection
Enter the Motor Nameplate Data into the
drive Parameters as follows
Motor Rated Voltage : P1-07
Motor Rated Current : P1-08
Motor Rated Frequency : P1-09
Motor Rated Speed (Optional) : P1-10