Single and Dual Data Highway Configurations 4 SINGLE AND DUAL DATA HIGHWAY CONFIGURATIONS 4.1 Profibus Data Highway The rules governing the installation and connection of a Profibus DP highway should be observed at all times to produce a successful installation. The highway does not allow power to be transferred and the Profibus module is powered from the actuator itself. The module can only report data when the actuator is powered up. PLC +5V +5V T T Terminator 0V Profibus DP highway 0V Screened cable Fig 7: Typical Profibus DP Data Highway The data highway must be terminated with a proper active termination network at each end of a segment. To ensure successful operation the highway itself should not use tapped spur or stub connections. The connection should be made in and out of each actuator in a daisy chain arrangement on separate terminals to eliminate any internal stubs cabling inside the actuator. The length of the highway and number of devices connected will vary from project to project. The standard permits up to 32 devices to be connected on a section, though one of these will be the PLC. If more devices are needed (up to the maximum addressable of 126) then repeaters may be added as required. Up to 9 repeaters can be used on a single highway provided no more than 4 are between any two devices. Data Rate (Baud) 9600 19200 45.45k 93.75k 187.5k 500k 1.5M Maximum Segment Length 1.2 km 1.2 km 1.2 km 1.2 km 1000m 400m 200m Maximum Highway Length 10 km 10 km 10 km 10 km 10 km 4 km 2 km Max number of 311 311 311 311 311 311 311 actuators/segment Note: 1 – The PLC or Repeater module will be one device. Max 32 devices/segment Since the data passes over a single 2 wire cable there are periods between messages when no devices are actively driving the lines. In order to ensure that data continues to flow correctly after these periods it is advisable to ensure the lines are biased to suitable voltage levels during the time the line is idle. The PFU contains active termination circuits that ensure suitable levels are maintained on the line even with no device transmitting. To select these termination components the appropriate internal links must be fitted. A simple termination resistor is also included and can be connected by linking the appropriate terminals (refer to the actuator wiring diagram). 15 of 66 Publication S420E V3.0 Issue 01/05