User Manual
Lx / Ls Series II
VOLT FREQ MAX
This test will set the voltage and frequency to a level defined by Table 8-9. The test will last for 30
minutes. The test will be repeated using the voltage from Table 8-8and frequency from Table
8-9. The
key (backspace) will terminate the test at any time.
VOLT UNBALANCE
Standard/Group
Voltage offset
Frequency
RTCA
8
400
A(CF)
8
360/440
A(NF)
8
360/650
Standard/Group
Voltage offset
Frequency
Group1
8
400
Group2
8
360/650
Group3
12
360/800
A(WF)
10
360/800
Table 8-10: Emergency Voltage Unbalance
This test will change the output voltage for phase A and B to 122V and phase C to a voltage
lower by a value specified by an offset. Refer to Table 8-10 for the offset value and the
Frequency. The test will repeat with the same frequency and phase A and B volt is set to 100V
and phase C set to a higher voltage specified by the offset. The test will last 30 minutes. The
test will be repeated for a second Frequency if applicable. The test can be terminated at any
time.
The
key (backspace) will terminate the test at any time.
135