Download Reference and Installation Manual
Transcript
Installation Do’s & Don’ts Do Don’t • o ensure that the unit’s detection beams are D perpendicular to the anticipated movement • Don’t direct the unit’s beams into swaying trees or bushes • eep a minimum distance between adjoining K NVX80 detectors to prevent MW cross interference, see the beam pattern diagram (see page 4) • Don’t place the detector facing direct sunlight or near a heat source, as it might interfere with the Active IR anti-mask feature • o place the unit under a roof, or awning or use our D all-weather cover, during an outdoor installation • Don’t place any objects, such as shelves, ledges or plants, below the unit • Do install the detector within the suggested range: installing the unit lower than 2.5 m / 8 ft 2 in may compromise the Pet Immunity capability, installing over 3.0 m / 9 ft 8 in may require use of our swivel bracket adjusted downward shifting the Pet Immunity beam and neutralizing the creep zone. Installing the unit over 3.0 m / 10 ft does not affect the creep zone. • Don’t place any reflective objects within 2 m / 6 ft 6 in of the unit, as this may interfere with the MW anti-mask capabilities Mounting Considerations The optimal installation height for the NVX80 is 2.5 m to 3.0 m (8 ft 2 in to 10 ft). If the installation site is near heavy traffic or objects beyond the required detection range, adjust the MW sensitivity and/or tilt the detector down. 2.5 m - 3.0 m (8'2'' - 10') Avoid installing the detector near moving objects (e.g., swaying trees, bushes, etc.). whether NVX80 Version 1.02 In order to maximize detection efficiency, choose a location that is most likely to intercept intruders moving across the coverage area at a 45 degree angle. 7