Installation Do’s & Don’ts
Do
Don’t
•
o ensure that the unit’s detection beams are
D
perpendicular to the anticipated movement
•
Don’t direct the unit’s beams into swaying
trees or bushes
•
eep a minimum distance between adjoining
K
NVX80 detectors to prevent MW cross interference,
see the beam pattern diagram (see page 4)
•
Don’t place the detector facing direct sunlight or
near a heat source, as it might interfere with the
Active IR anti-mask feature
•
o place the unit under a roof, or awning or use our
D
all-weather cover, during an outdoor installation
•
Don’t place any objects, such as shelves, ledges or
plants, below the unit
•
Do install the detector within the suggested range:
installing the unit lower than 2.5 m / 8 ft 2 in may
compromise the Pet Immunity capability, installing
over 3.0 m / 9 ft 8 in may require use of our swivel
bracket adjusted downward shifting the Pet
Immunity beam and neutralizing the creep zone.
Installing the unit over 3.0 m / 10 ft does not affect
the creep zone.
•
Don’t place any reflective objects within 2 m /
6 ft 6 in of the unit, as this may interfere with the
MW anti-mask capabilities
Mounting Considerations
The optimal installation height for the NVX80 is
2.5 m to 3.0 m (8 ft 2 in to 10 ft).
If the installation site is near heavy traffic or objects
beyond the required detection range, adjust the MW
sensitivity and/or tilt the detector down.
2.5 m - 3.0 m
(8'2'' - 10')
Avoid installing the detector near moving objects
(e.g., swaying trees, bushes, etc.).
whether
NVX80 Version 1.02
In order to maximize detection efficiency, choose a
location that is most likely to intercept intruders moving
across the coverage area at a 45 degree angle.


7