Transcript
7 I Startup Parameter setting: Frequency inverters for category 2GD motors 0 Current monitoring The parameters that need to be set for monitoring the current depend on the motor. X I1 1,5 In (Motor) In (Motor) Iü Iü C B A Motor typedependent I2 fA fB fC fE f [Hz] 4077842059 In I1 I2 IO Nominal current in A permitted max. current in A permitted continuous current range in A Overload current in A X f A, B, C, E Current limitation Frequency in Hz limiting points After motor startup, current limitation I1 is active. Current limitation I2 determines the current that is permanently permitted. The current limitation function can be activated during startup or via parameter P560 Current limitation Ex e motor (the Ex e motor current limitation function is activated automatically for SEW-EURODRIVE motors of category 2 during startup). The characteristic curve for MOVIDRIVE® is defined by operating points A, B and C. The parameters of group P560 are preset during startup, see following table. The values are also specified in the EC prototype test certificate. Parameters Maximum speed Automatic adjustment 86 Point A Point B Point C Frequency [Hz] P561 P563 P565 Current limit in % of IN FI P562 P564 P566 The maximum motor speed must be limited in the "System limits" window. Observe the following when you set the parameter maximum speed: • Maximum speed ≤ start of the field weakening • Maximum speed ≤ motor limit speed and • Maximum speed ≤ maximum gear unit input speed nemax (see gear unit nameplate) The parameter automatic adjustment is activated via guided startup. Thus, the frequency inverter sets parameter IxR value with each enable signal. A manual change is not permitted. Operating Instructions – Explosion-Proof AC Motors EDR.71 – 225