Transcript
ZONE CIRCUIT, CONNECTION & ADJUSTMENTS DIAGRAM SPARK QUENCHED FOR PUMP C NO NON ACCEPT NC C NO NC Use VR3 to adjust RESET TIME VR3 Clockwise turn increases pump RUN ON delay time Anti-clockwise turn decreases pump RUN ON delay time Use VR2 to adjust ON DELAY TIME VR2 Clockwise turn increases ON delay time Anti-clockwise turn decreases ON delay time VR3 VR2 SPARK QUENCHED FOR PUMP C NO NON ACCEPT NC C NON ACCEPTABLE CONTACTS FOR PUMP (VOLT FREE) +VE -VE DC INPUT +VE NO NC NON ACCEPTABLE CONTACTS (VOLT FREE) -VE ZONE C NC NO ALARM CONTACTS ACCEPTABLE WARNING! Ensure correct voltage before connecting 12VDC and 24VDC models available ACCEPTABLE CONTACTS FOR SOUNDER (VOLT FREE) CONNECT FLOAT SWITCH(ES) WITH E.O.L FLOAT SWITCH AS LAST FLOAT SWITCH ED830 - BILGE LEVEL ALARM CONTROL UNIT +VE -VE DC INPUT +VE -VE ZONE C NC NO ALARM CONTACTS ACCEPTABLE 7