Download User's Manual
Transcript
Function-Codes Zoom Table ·F720~725 is used to record the latest three malfunction types and the corresponding frequency, current and voltage at last malfunction. Refer to Appendix 1(P55) for causes and countermeasures for any malfunction. 5.8 Analog signal Parameters 5.8.1 Analog signal Input G N E F In mode of analog speed control, it is necessary to set the min and max input analog, and the corresponding output frequency to secure a good speed control effect. F800 Min Analog Input (V) F801 Max Analog Input (V) F807 Setting Range: 0.00~MIN(F801,10.00) Setting Range: MAX(0.00,F800)~ 10.00 Corresponding Frequency for Min Analog (Hz) F808 Corresponding Frequency for Max Analog (Hz) Setting Range: F112~F111 Setting Range: F112~F111 I U Mfr Value: 0.00 Mfr Value: 10.00 Mfr Value: 0.00 Mfr Value: 50.00 ·Set min and max analogs as per actual input range of analog signal. ·The setting values of F807 and F808 decide proportion mode of analog adjustment change, as shown in Fig 5-12: ·MIN (F801, 10.00) refers to the smaller one of the two values between F801 setting value and 10.00. ·MAX (0.00, F800) refers to the bigger one of the two values between F800 setting value and 0.00. H Input Analog F801 F800 F807 Input Analog F808 F801 Corresponding frequency F800 F807 F808 Corresponding frequency Fig 5-12 Proportion Mode of Analog Adjusting 5.8.2 Pulse Frequency Input F809 Max Input Pulse Frequency (Hz) Setting Range:0~9999 43 Mfr Value: 5000