Transcript
Electrical Installation Power bus connection examples 5 5.8.2 Power bus with Han-Modular® plug connector TIP This example applies for the following connection boxes: Power distribution and line protection • • Han-Modular®-ABOX "MTA...-H12.-...-00" Han-Modular®-ABOX "MTA...-H22.-...-00" • SEW-EURODRIVE recommends using HARTING Power S products for power bus project planning. • Two lines of max. 6 mm2 can be routed in the AC 400 V 50/60 Hz and DC 24 V supply cable. • The spur lines leading to MOVIFIT® have a cross section of 4 mm2 and are a maximum of 1.5 m long. • The Han Power S distributor is available from Harting (part number 6104 202 1069). 812456203 • Supply sensor, group IV (24V_S) In the connector of the Han Power S distributor mentioned above (part number 6104 202 1069), the 24V_S supply voltage of sensor supply group IV is jumpered with 24V_C continuous voltage. Accessories: Harting provides the following accessories for the Han Power S distributor. Type Cable diameter Part number at Harting Bushing seal for small entry 7-10 mm 0912 000 9965 10-13 mm 0912 000 9966 13-16 mm Filler plug for small entry Bushing seal for large entry 7-10 mm 0912 000 9969 10-13 mm 0912 000 9970 13-16 mm 0912 000 9971 16-19 mm 0912 000 9972 19-22 mm Filler plug for large entry 78 0912 000 9967 0912 000 9968 0912 000 9973 0912 000 9974 MOVIFIT®-SC Operating Instructions