Transcript
– 21 – ◆ Group control through a remote controller Group control of multiple indoor units (8 units) through a single remote controller switch Indoor unit No.1 No.2 AB Remote controller AB No.3 No.7 No.4 AB AB AB Power supply terminal block No.8 AB Electrical control box Cord clamps (A.B) Connection of power wires and communication wires Communication terminal block Remove knockouts on the piping / wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes. Power supply wires Cord clamp Earth screw Communication wires Piping / wiring panel Knockout for the communication wire Knockout for the power wire NOTE Be sure to separate the power wire and communication wires. Knockout for the power supply wire ◆ Power supply wire connection 1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power supply wire to the power supply terminal block and the earth wire to the earth screw. After that, fix the power supply wire with the 2 cord clamps. 2. Be sure to use round-type crimping terminals for power connection. Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws. L1 L1 L2 L2 L3 L3 N N 10 mm or more Earth wire 41-EN Power supply wire 42-EN