Download Installation Manual
Transcript
Specifications for communication wiring Be sure to keep the rule of below tables about size and length of communication wiring. Central control controller ◆ Design of communication wiring Super modular multi system U1 U2 U3 U4 Summary of communication wiring Outdoor unit Header unit Header unit Outdoor unit Follower unit Header Follower unit unit U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 U3 U4 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 L5 Table-1 Table-2 U1 U2 U3 U4 U5 U6 L2 U1 U2 U3 U4 Indoor unit Control wiring between outdoor units (Shield wire) U1 U2 U1 U2 A B Central control wiring (Shield wire) U1 U2 A B A B L3 U1 U2 U1 U2 A B U1 U2 A B Table-3 U1 U2 A B L7 Control wiring between indoor and outdoor units (Shield wire) Remote controller Control wiring between indoor units (Shield wire) Flow selector unit Flow selector unit Flow selector unit Flow selector unit CN02 CN02 CN02 CN02 CN81 CN81 CN81 CN81 U1 U2 A B Indoor unit U1 U2 A B Indoor unit Table-1 Remote controller U1 U2 A B L6 Remote controller U1 U2 A B Indoor unit U1 U2 A B A B Remote controller Remote controller (Group control) 2-core, non-polarity Shield wire Size / Length 1.25 mm2: Up to 1000 m / 2.0 mm2: Up to 2000 m (*1) (*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4) Indoor unit A B Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4) Type Table-2 A B A B Remote controller Wiring Wiring • Communication wiring and central control wiring use 2-core non-polarity wires. Use 2-core shield wires to prevent noise trouble. • Connecting the closed end terminal of shield wire. (Connected to all connecting sections in each unit) • Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals) • Control wire and power line wire between Flow selector unit and indoor unit are the accessory parts of Flow selector unit. (Wire length : 6m) If the length between indoor unit and Flow selector unit exceeds 5m, connect by using the Connection cable kit sold separately (RBC-CBK15FE). 39-EN Follower unit Header unit Follower unit U3 U4 L1 U1 U2 U3 U4 U5 U6 Follower unit U1 U2 U5 U6 Outdoor unit Central remote device (option) Table-1 L4 2-core, non-polarity Type Shield wire Size / Length 1.25 mm2 to 2.0 mm2 / Up to 100 m (L5) Table-3 Wire – 20 – Communication wiring between outdoor units (L5) Remote controller wiring (L6, L7) 2-core, non-polarity Size 0.5 mm2 to 2.0 mm2 Length • Up to 500 m (L6 + L7) • Up 400 m in case of wireless remote controller in group control. • Up to 200 m total length of communication wiring between indoor units (L6) 40-EN