Download USER'S GUIDE

Transcript
G9SX
USER'S GUIDE
G9SX
G9SX-NS
G9SX-GS
Flexible Safety Unit
Non-Contact Door Switch Controller
Safety Guard Switching Unit
Cat.No. Z255-E1-01
Introduction
This User’s Guide describes the usage of the G9SX Series-Flexible Safety Units mainly through application
examples.
Humans make mistakes and machines fail.
Therefore it is necessary to design machines and equipment based on the assumption that humans will make
mistakes and machines will fail.
Thus, a circuit configuration is required to ensure safety, even when an onsite operator makes a mistake in machine
operation or when a part of the machine fails. Flexible Safety Units, which enable various safety circuit patterns to be
configured only by simple wiring, provide the core components of such safety circuits.
Use the OMRON Flexible Safety Units in your machine and equipment to improve the safety designs and onsite
worker safety measures.
Outline of this User’s Guide
Section
1
Section
2
Section
3
Section
4
Appendix
2
G9SX
USER'S GUIDE
Application Examples
Introduces applications that can be
configured with the G9SX.
Functions of G9SX
Describes the functions of each unit of
G9SX Series.
Wiring and Setup
Describes the wiring and settings
required for use.
Ratings and Specifications
Provides specifications, dimensions and
terminal arrangements.
Describes troubleshooting, accessories,
and related products.
Ordering Information
■ List of Models
Advanced Unit
Safety outputs
(solid state) (See note 3.)
Auxiliary outputs Logical AND connection
Max. OFFNo. of input
(solid state)
delay time
channels
OFF-delayed (See note 4.)
(See note 1.)
Instantaneous
Inputs
Outputs
(See note 2.)
3
(Semiconductor)
15 s
1
1
(Semiconductor) (Semiconductor)
2
2
(Semiconductor) (Semiconductor)
150 s
1 or 2
channels
24 VDC
15 s
2
2
(Semiconductor) (Semiconductor)
2
(Semiconductor)
Rated
voltage
150 s
Terminal block type
Model
Screw terminals
G9SX-AD322-T15-RT
Spring-cage terminals
G9SX-AD322-T15-RC
Screw terminals
G9SX-AD322-T150-RT
Spring-cage terminals
G9SX-AD322-T150-RC
Screw terminals
G9SX-ADA222-T15-RT
Spring-cage terminals
G9SX-ADA222-T15-RC
Screw terminals
G9SX-ADA222-T150-RT
Spring-cage terminals
G9SX-ADA222-T150-RC
Note: 1. The OFF-delay time can be set in 16 steps as follows:
T15: 0/0.2/0.3/0.4/0.5/0.6/0.7/1/1.5/2/3/4/5/7/10/15 s
T150: 0/10/20/30/40/50/60/70/80/90/100/110/120/130/140/150 s
2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s.
3. P channel MOS FET transistor output
4. PNP transistor output
Basic Unit
Safety outputs
(solid state) (See note 1.)
Instantaneous
OFF-delayed
2
(Semiconductor)
---
Logical AND
connection
Auxiliary outputs
(solid state)
(See note 2.)
Inputs
Outputs
0
2
2
(Semiconductor)
No. of input
channels
Rated
voltage
1 or 2
channels
24 VDC
Terminal block type
Model
Screw terminals
G9SX-BC202-RT
Spring-cage terminals
G9SX-BC202-RC
Note: 1. P channel MOS FET transistor output
2. PNP transistor output
Non-Contact Door Switch Controller (Controllers for D40A)
Safety outputs
(See note.1)
Instantaneous
2
(Semiconductor)
Note: 1.
2.
3.
4.
OFF-delayed
(See note 2.)
0
2
(Semiconductor)
Auxiliary outputs
(See note 3.)
Logical AND Logical AND Max. OFFconnection connection delay time
input
output
(See note 4.)
2
(Semiconductor)
Rated
voltage
--1
1
24 VDC
3.0 s
Terminal block type
Model
Screw terminals
G9SX-NS202-RT
Spring-cage terminals
G9SX-NS202-RC
Screw terminals
G9SX-NSA222-T03-RT
Spring-cage terminals
G9SX-NSA222-T03-RC
P channel MOS FET transistor output
The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s.
PNP transistor output
The OFF-delay time can be set in 16 steps as follows:
0/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1.0/1.2/1.4/1.8/2.0/2.5/3.0 s
Safety Guard Switching Unit
Safety outputs (See note 3.)
Instantaneous
OFF-delayed
(See note 2.)
Auxiliary outputs
(See note 4.)
Logical AND connection
Inputs
Max. OFFRated
delay time
voltage
(See note 1.)
Outputs
2 (semiconductor) 2 (semiconductor) 6 (semiconductor) 1 (semiconductor) 1 (semiconductor)
15 s
24
VDC
Terminal block
type
Model
Screw terminals
G9SX-GS226-T15-RT
Spring-cage
terminals
G9SX-GS226-T15-RC
Note: 1. The OFF-delay time can be set in 16 steps as follows:
T15: 0/0.2/0.3/0.4/0.5/0.6/0.7/1/1.5/2/3/4/5/7/10/15 s
2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s.
3. P channel MOS FET transistor output
4. PNP transistor output (except for the external indicator outputs, which are P channel MOS FET transistor outputs)
Expansion Unit
Safety outputs
Instantaneous
OFF-delayed
4 PST-NO (contact)
---
Auxiliary outputs
(See note 1.)
OFF-delay time
4 PST-NO (contact)
24 VDC
(See note 2.)
Terminal block type
Screw terminals
--1 (semiconductor)
---
Rated voltage
Model
G9SX-EX401-RT
Spring-cage terminals
G9SX-EX401-RC
Screw terminals
G9SX-EX041-T-RT
Spring-cage terminals
G9SX-EX041-T-RC
Note: 1. PNP transistor output
2. The OFF-delay time is synchronized to the OFF-delay time setting in the connected Unit (G9SX-AD-@, G9SX-ADA-@, G9SX-NSA@ and G9SX-GS-@).
G9SX
USER'S GUIDE
3
Model Number Structure
■ Model Number Legend
G9SX - @@@@@@ - @@@ - @@
1
2 3 4
5
6
1. Functions
AD/ADA :Advanced Unit
Advanced Unit
BC
:Basic Unit
T15 : 15 s
GS
:Safety Guard Switching Unit
T150 : 150 s
NS/NSA :D40A Controller
EX
:Expansion Unit
2. Output Configuration (Instantaneous Safety
Outputs)
0 : None
2 : 2 outputs
3 : 3 outputs
4 : 4 outputs
3. Output Configuration (OFF-delayed Safety
Outputs)
0 : None
2 : 2 outputs
4 : 4 outputs
4. Output Configuration (Auxiliary Outputs)
1 : 1 output
2 : 2 outputs
6 : 6 outputs
4
5. Max. OFF-delay Time
G9SX
USER'S GUIDE
Basic Unit
No indicator : No OFF delay
Safety Guard Switching Unit
T15 : 15 s
D40A Controller
T03 : 3 s
Expansion Unit
No indicator : No OFF delay
T
: OFF delay
6. Terminal Block Type
RT : Screw terminals
RC : Spring-cage terminals
CONTENTS
Section
1
Application Examples
1. Partial control of machine
1-1 Parts Processing Machine
7
8
Section
2
Functions of G9SX
37
1. Function list of G9SX-series
38
2. Functions of each Unit
39
8
1-2 Machining Center
11
1-3 Semiconductor Manufacturing Equipment
15
2-1 Basic Unit
39
1-4 Machine Tool
17
2-2 Advanced Unit
40
2-3 Non-Contact Door Switch Controller
42
20
2-4 Safety Guard Switching Unit
44
2-1 Pick and Place Machine
20
2-5 Expansion Unit
48
2-2 Small Assembly System
22
2. Using Non-contact Door Switch
3. Coordinated operation of worker and
machine
3-1 Manufacturing Automotive Parts Using
Semi-automatic Processing
4. Safety Measures for limited operations
25
25
28
4-1 Manufacturing Flat-panel Displays
(Maintenance)
28
4-2 Machining Center (Enabling Switch)
31
4-3 LCD Manufacturing (Guard Lock Control)
34
G9SX
USER'S GUIDE
5
CONTENTS
Section
3
Wiring and Setup
1. I/O Terminals
51
52
Section
4
Ratings and Specifications
1. Ratings
72
1-1 Basic Unit
52
1-1 Advanced Unit/Basic Unit
72
1-2 Advanced Unit
53
1-2 Non-contact Door Switch Controller
73
1-3 Non-contact Door Switch Controller
54
1-3 Safety Guard Switching Unit
74
1-4 Safety Guard Switching Unit
55
1-4 Expansion Unit
75
1-5 Expansion Unit
56
2. Characteristics
2. Functions, Wiring and Settings
57
76
2-1 Advanced Unit/Basic Unit
76
2-2 Non-contact Door Switch Controller
77
2-3 Safety Guard Switching Unit
78
2-4 Expansion Unit
79
2-1 Logical AND Connection
57
2-2 Response Time and Operation Time
60
2-3 Reset Mode
62
2-4 Cross Fault Detection
63
2-5 Connecting Safety Sensors and the G9SX
64
2-6 OFF-delay Time
65
3-1 Advanced Unit
80
2-7 Non-contact Door Switch
66
3-2 Basic Unit
80
2-8 Switching Mode
67
3-3 Non-contact Door Switch Controller
81
2-9 External Indicator Fault Diagnosis
68
3-4 Safety Guard Switching Unit
81
2-10 Connecting Expansion Units
69
3-5 Expansion Unit
82
2-11 Confirming Settings
70
3. Dimensions and Terminal arrangements
Appendix
G9SX
USER'S GUIDE
80
83
1. Troubleshooting
84
2. Logical AND Connections
91
3. Accessories and Related Products
93
Precautions
6
71
95
Section
1
1
Section
Application Examples
Application Examples
1. Partial control of machine
8
1-1 Parts Processing Machine
8
1-2 Machining Center
11
1-3 Semiconductor Manufacturing Equipment
15
1-4 Machine Tool
17
2. Using Non-contact Door Switch
20
2-1 Pick and Place Machine
20
2-2 Small Assembly System
22
3. Coordinated operation of worker and
machine
3-1 Manufacturing Automotive Parts Using
Semi-automatic Processing
25
25
4. Safety Measures for limited operations
28
4-1 Manufacturing Flat-panel Displays
(Maintenance)
28
4-2 Machining Center (Enabling Switch)
31
4-3 LCD Manufacturing (Guard Lock Control)
34
G9SX
USER'S GUIDE
7
1. Partial control of machine
1-1 Parts Processing Machine
Section
The entire device stops when the Emergency Stop Switch is pressed.
Only the processing section stops when the Safety Light Curtain is interrupted.
1
(2) Safety Light Curtain
(1) Emergency Stop
Switch
Application Examples
(1) Emergency Stop
Switch
Processing section
(2) Safety Light
Curtain
Basic Unit
G9SX-BC
Logical AND connection
Processing section
Segment A
Advanced Unit
G9SX-AD
Operation Example
(1) The Emergency Stop Switch
is pressed.
(2) Safety Light Curtain is
interrupted.
Stop Stop
Stop Stop
Segment A
Segment A
Segment B
Segment B
Segment B
Required Units
8
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-AD
1
Safety Light Curtains
40
G9SX
USER'S GUIDE
1. Partial control of machine
■ Wiring Example
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-AD: Auto reset, Cross fault detection mode: OFF (Category 4 Wiring (with Safety Light Curtains)),
1
Logical AND connections, OFF-delay time setting
Application Examples
Wiring Example
Feedback Loop
11
21
12
22
Section
Setup (For details, refer to Section 3.)
KM1
KM2
S1
KM 1
S2
+24V
KM2
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
+24V
S1 : Emergency Stop Switch
S2 : Reset switch
KM1 to KM6 : Contactor
M1 to M3 : 3-phase motor
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
PLC etc.
GND
Emitter
F3SJ-A
Receiver
Feedback Loop
Motor controller
S34
KM3
KM3
KM5
KM 4
KM6
Control output 1
GND
NC
Control output 2
KM4
KM5
KM6
+24V
M2
M3
+24V
NC
AND
A1 T11 T12 T21 T22 T31 T32 T33 Y1
T41 T42
OFF
G9SX-AD322-T15
+24V
Control circuit
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM3 KM4
GND
KM5 KM6
PLC etc.
Motor controller
(Operation command)
Note: 1. This example corresponds to category 4. (when using a Type-4 Safety Sensor).
2. For further information on settings and wiring, refer to the datasheet or instruction sheet for the Safety Sensor.
3. Use Safety Sensors with PNP control outputs.
G9SX
USER'S GUIDE
9
1. Partial control of machine
■ Timing chart
Section
(2)
G9SX-BC202 (upper unit)
Emergency Stop Switch S1
1
Reset switch S2
Application Examples
KM1, KM2 NC contact
KM1, KM2 NO contact
Logical AND output L1
G9SX-AD322-T15 (lower unit)
(1)
Logical AND input T41
Safety Light Curtain
KM3, KM4 NC contact
KM5, KM6 NC contact
KM3, KM4 NO contact
KM5, KM6 NO contact
Operation command
Rotation of motor
OFF-delay time
(1) Safety Light Curtain is interrupted: Only the lower Unit stops.
(2) Emergency stop button pressed: Both the upper and lower Unit stop.
10
G9SX
USER'S GUIDE
OFF-delay time
1. Partial control of machine
1-2 Machining Center
1
(1) Emergency Stop
Switch
(2) Main door
Section
When the Emergency Stop Switch is pressed, the entire machine will stop.
When a door is open, the corresponding part will not be activated.
(4) Tool changer door
(2) Main Door
(3) Pallet Changer Door
Guard Lock
Safety Door
Switch
Basic Unit
G9SX-BC
Safety Door
Switch
(4) Tool Changer Door
Application Examples
(1) Emergency Stop
Switch
Safety Door
Switch
Logical AND connection
(3) Pallet changer door
Advanced Unit
G9SX-AD
Advanced Unit
G9SX-AD
Advanced Unit
G9SX-AD
Operation Example
(1) The Emergency Stop
Switch is pressed.
(2) The main door is opened.
Stop Stop Stop
Stop Stop Stop
Segment A
Segment A
Segment B
Segment C
(3) The pallet changer door
is opened.
Segment B
Segment C
Stop Stop Stop
Stop Stop Stop
Segment A
Segment A
Segment B
Segment C
Segment A
Segment B
Segment C
(4) The tool changer door is
opened.
Segment B
Segment C
Required Units
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-AD
3
Guard Lock Safety Door Switch
Safety Door Switches (Set of two)
40
G9SX
USER'S GUIDE
11
1. Partial control of machine
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-AD (main door section): Manual reset, Cross fault detection mode: ON (Category 4 Wiring),
1
Logical AND connections, OFF-delay time setting
Application Examples
G9SX-AD (pallet changer, tool changer): Auto reset, Cross fault detection mode: ON (Category 4 Wiring),
Logical AND connections, OFF-delay time setting
Wiring Example
Feedback Loop
11
21
12
22
KM1
KM2
S1
KM 1
S2
+24V
KM2
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
+24V
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
S1 : Emergency Stop Switch
S2, S6 : Reset switch
S3 : Guard Lock Safety Door Switch
S4 : Safety Limit Switch
S5 : Lock release switch
S7, S8 : Safety Door Switch
KM1 to KM8 : Contactor
M1 to M4 : 3-phase motor
PLC etc.
GND
Feedback Loop
Motor controller
S34
4
S8
KM7
Lock release signal
KM7
Open
KM8
KM8
KM3
KM4
S3
S5
M4
+24V
+24V
NC
41
A1 T11 T12 T21 T22 T31 T32 T33 Y1
42
11
AND
T41 T42
OFF
G9SX-AD322-T15 (Tool changer door)
12
Control circuit
Guard
Feedback Loop
S4
A2
KM3
S14 S24 S34 S44 S54 L1 X1 X2
KM7 KM8
KM4
PLC etc.
Stop signal
S6
+24V
GND
+24V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
AND
T41 T42
Motor controller
(Operation command)
OFF
G9SX-AD322-T15 (Main door)
Feedback Loop
Motor controller
S7
Control circuit
KM5
KM5
Open
KM6
A2
KM6
S14 S24 S34 S44 S54 L1 X1 X2
M3
KM3 KM4
PLC etc.
+24V
+24V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
GND
Motor controller
(Operation command)
Motor controller
S34
4
Control circuit
KM4
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM5 KM6
Note: This example corresponds to category 4.
12
G9SX
USER'S GUIDE
OFF
G9SX-AD322-T15 (Pallet changer door)
KM3
M2
AND
T41 T42
GND
Motor controller
(Operation command)
PLC etc.
S34
4
1. Partial control of machine
■ Timing chart
Section
G9SX-BC202 (upper unit)
(8)
Emergency Stop Switch S1
1
Reset switch S2
Application Examples
KM1, KM2 NC contact
KM1, KM2 NO contact
Logical AND output L1
G9SX-AD322-T15 (lower unit : Main door)
Logical AND input T41
(1)
(2)
(3)
Safety Limit Switch S4
Guard Lock Safety Door Switch S3
Lock release signal
Lock release switch S5
Door can be opened.
Stop signal
Reset switch S6
KM3, KM4 NC contact
KM3, KM4 NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
G9SX-AD322-T15 (lower unit : Pallet changer door)
Logical AND input T41
(4)
(5)
Safety Door Switch S7
KM5, KM6, NC contact
KM5, KM6, NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
G9SX-AD322-T15 (lower unit : Tool changer door)
Logical AND input T41
(6)
(7)
Safety Door Switch S8
KM7, KM8, NC contact
KM7, KM8, NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
(1) Before operation is started.
(2) Main door is unlocked and opened, and then work is performed.
(3) Restart operation after the main door is closed.
(4) The pallet changer door opens and the pallet changer section stops.
(5) The pallet changer door is closed and the pallet changer is reset.
(6) The tool changer door opens and the tool changer section stops.
(7) The tool changer door is closed and the tool changer section is reset.
(8) If the Emergency Stop Switch is pressed, the upper unit and lower units will stop.
G9SX
USER'S GUIDE
13
1. Partial control of machine
■ Timing chart
Section
G9SX-BC202 (Unit A)
(6)
Emergency Stop Switch S1
Reset switch S2
1
KM1, KM2 NC contact
Application Examples
KM1, KM2 NO contact
Logical AND output L1
G9SX-AD322-T15 (Unit B:Processing section cover)
Logical AND input T41
(1)
(2)
(3)
Safety Door Switch S3
KM3, KM4 NC contact
KM3, KM4 NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
Logical AND output L1
G9SX-AD322-T15 (Unit C:Conveyor section cover)
Logical AND input T41
(4)
(5)
Safety Door Switch S4
KM5, KM6, NC contact
KM5, KM6, NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
OFF-delay time
(1) Before operation is started.
(2) The processing section cover is opened, and the processing section and the conveyor section stops.
(3) The processing section cover is closed and the processing section and conveyor section restart.
(4) The conveyor section cover is opened and the conveyor section stops.
(5) The transport section cover is closed and the conveyor section restarts.
(6) If the Emergency Stop Switch is pressed, unit A, unit B, and unit C will stop.
14
G9SX
USER'S GUIDE
1. Partial control of machine
1-3 Semiconductor Manufacturing Equipment
(2) Processing section cover
(1) Emergency Stop
Switch
Basic Unit
G9SX-BC
Safety Door
Switch
Safety Door
Switch
Advanced Unit
G9SX-AD
Advanced Unit
G9SX-AD
Logical AND
connection
Logical AND
connection
(1) Emergency Stop
Switch
Segment A
(3) Conveyor section cover
Application Examples
(2) Processing
section cover
1
(3) Conveyor
section cover
Section
When the Emergency Stop Switch is pressed, all of the equipment stops.
When the processing section cover is opened, the processing section and conveyor section stop.
When the conveyor section cover is opened, only the conveyor section stops.
Segment B
Segment C
Operation Example
(1) The Emergency Stop
Switch is pressed.
(2) The processing section
cover is opened.
Stop Stop
Stop Stop Stop
Segment A
Segment B
Segment C
(3) The conveyor section
cover is opened.
Segment A
Segment B
Segment C
Stop
Segment A
Segment B
Segment C
Required Units
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-AD
2
Safety Door Switches (Set of two)
40
G9SX
USER'S GUIDE
15
1. Partial control of machine
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-AD: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
1
OFF-delay time setting
Application Examples
Wiring Example
Feedback Loop
11
21
12
22
KM1
KM2
S1
KM 1
S2
+24V
KM2
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
S1 : Emergency Stop Switch
S2 : Reset switch
S3, S4 : Safety Door Switch
KM1 to KM6 : Contactor
M1 to M3 : 3-phase motor
M1
G9SX-BC202 (Unit A)
+24V
Control circuit
A2
S14 S24
L1 L2
KM1 KM2
X1 X2
PLC etc.
GND
Motor controller
S34
4
Feedback Loop
KM3
S3
KM3
Open
KM4
KM4
M2
+24V
+24V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
AND
T41 T42
OFF
G9SX-AD322-T15 (Unit B)
Control circuit
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM3 KM4
GND
PLC etc.
Motor controller
(Operation command)
Motor controller
Feedback Loop
KM5
S4
KM5
Open
KM6
KM6
M3
+24V
+24V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
G9SX-AD322-T15 (Unit C)
Control circuit
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM5 KM6
GND
Note: This example corresponds to category 4.
16
G9SX
USER'S GUIDE
Motor controller
(Operation command)
PLC etc.
AND
T41 T42
OFF
S34
4
1. Partial control of machine
1-4 Machine Tool
(2) Left door
(1) Emergency Stop
Switch
Safety Door
Switch
Safety Door
Switch
Advanced Unit
G9SX-AD
Basic Unit
G9SX-BC
Logical AND
connection
(1) Emergency Stop
Switch
(3) Right door
Application Examples
(3) Right door
1
(2) Left door
Section
When the Emergency Stop Switch is pressed, the entire machine will stop.
If the left door is opened, the left drive section and transport section will stop.
If the right door is opened, the right drive section and transport section will stop.
Advanced Unit
G9SX-AD
Segment A
Segment B
Logical AND
connection
Logical AND
connection
Operation Example
(1) The Emergency Stop
Switch is pressed.
(2) The left door is opened. (3) The right door is opened.
Stop Stop
Stop Stop
Stop Stop
Segment A
Segment A
Segment A
Segment B
A
Segment B
Advanced Unit
G9SX-ADA
Segment B
A
Transport section
Stop
Stop
Stop
Segment C
A
Segment C
A
Segment C
A
Segment C
Required Units
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-AD
2
Safety Door Switches (Set of two)
40
G9SX-ADA
1
---
41
G9SX
USER'S GUIDE
17
1. Partial control of machine
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-AD: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
1
No OFF-delay time setting
Application Examples
G9SX-ADA: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
OFF-delay time setting
Wiring Example
Feedback Loop
11
21
12
22
KM1
KM2
S1
KM 1
S2
+24V
KM2
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
S1 : Emergency Stop Switch
S2 : Reset switch
S3, S4, S5 : Safety Door Switch
KM1 to KM8 : Contactor
M1 to M4 : 3-phase motor
M1
G9SX-BC202
+24V
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
PLC etc.
GND
Feedback Loop
Feedback Loop
S3
S4
KM3
KM3
KM5
KM5
Open
Open
KM4
KM4
KM6
KM6
M2
M3
Right drive section
Left drive section
+24V
+24V
+24V
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
+24V
NC
AND
T41 T42
A1 T11 T12 T21 T22 T31 T32 T33 Y1
OFF
G9SX-AD322-T15 (Left door)
G9SX-AD322-T15 (Right door)
Control circuit
A2
Control circuit
S14 S24 S34 S44 S54 L1 X1 X2
KM3 KM4
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM5 KM6
PLC etc.
GND
GND
Feedback Loop
KM1
KM2
+24V
+24V
NC
Motor controller
S34
4
A1 T11 T12 T21 T22 T31 T32 T33 Y1
AND
T41 T42
G9SX-ADA222-T150
KM7
Control circuit
KM8
M4
Transport section
A2
S14 S24 S34 S44 S54 L1 X1 X2
KM7 KM8
Note: This example corresponds to category 4.
18
G9SX
USER'S GUIDE
GND
AND
T41 T42
Motor controller
(Operation command)
PLC etc.
T51 T52
OFF
PLC etc.
OFF
1. Partial control of machine
■ Timing chart
G9SX-BC202 (upper unit)
Section
(6)
Emergency Stop Switch S1
Reset switch S2
1
KM1, KM2 NC contact
Application Examples
KM1, KM2 NO contact
Logical AND output L1
G9SX-AD322-T15 (middle unit: Left door)
Logical AND input T41
(1)
(2)
(3)
Safety Door Switch S3
KM3, KM4 NC contact
KM3, KM4 NO contact
Logical AND output L1
G9SX-AD322-T15 (middle unit: Right door)
Logical AND input T41
(4)
(5)
Safety Door Switch S4
KM5, KM6, NC contact
KM5, KM6, NO contact
Logical AND output L1
G9SX-ADA222-T150 (lower unit)
Logical AND input T41
Logical AND input T51
KM7, KM8, NC contact
KM7, KM8, NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
OFF-delay time
(1) Before operation is started.
(2) The left door is opened and the left drive section and transport section stop.
(3) The left door is closed and the left drive section and transport section restart.
(4) The right door is opened and the right drive section and transport section stop.
(5) The right door is closed and the right drive section and transport section restart.
(6) If the Emergency Stop Switch is pressed, the Upper Unit, Middle Unit, and Lower Unit will stop.
G9SX
USER'S GUIDE
19
2. Using Non-contact Door Switch
2-1 Pick and Place Machine
Section
If the Emergency Stop Switch is pressed, the entire machine will stop.
If the cover is opened, the entire machine will stop.
1
Cover
(2) Non-contact
Door Switch
Cover
Application Examples
(1) Emergency Stop
Switch
(2) Non-contact
Door Switch
D40A
(1) Emergency Stop
Switch
G9SX-NSA
Motor
Operation Example
(1) The Emergency Stop
Switch is pressed.
(2) Cover is opened.
Stop
Stop
Segment
Motor A
Segment
Motor A
Required Units
20
Unit
Qty.
Safety input to be applied
Page
G9SX-NSA
1
Emergency Stop Switch +
Non-contact Door Switch D40A
43
G9SX
USER'S GUIDE
2. Using Non-contact Door Switch
■ Wiring Example
G9SX-NSA: Manual reset, Cross fault detection mode: OFF (Category 2 Wiring), Logical AND connections: OFF,
OFF-delay time setting
Section
Setup (For details, refer to Section 3.)
1
Application Examples
Wiring Example
Actuator
Feedback Loop
Non-contact
Door Switch
S2
+24V
KM1
11
Motor controller
KM2
S3
12
KM1
S1
KM2
blue
Brown
Black
White
+24V
NC
NC
A1
S14
T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4
NC
NC
AND
T41 T42
OFF
M1
G9SX-NSA222-T03
+24V
Control circuit
A2
S14 S24
S44 S54 L1 X1 X2
KM1 KM2
GND
PLC etc.
Motor controller
(Operation command)
S1 : Emergency Stop Switch
S2 : Non-contact Door Switch
S3 : Reset switch
KM1, KM2 : Contactor
M1 : 3-phase motor
Note: This example corresponds to category 2.
■ Timing chart
Emergency Stop
Switch operation
Emergency Stop Switch S1
Non-contact
Door Switch S2
Reset switch S3
KM1, KM2 NC contact
KM1, KM2 NO contact
Operation command
Rotation of motor
OFF-delay time
OFF-delay time
G9SX
USER'S GUIDE
21
2. Using Non-contact Door Switch
2-2 Small Assembly System
Section
1
When the Emergency Stop Switch is pressed, both robots will stop.
When robot door A is opened, robot A will stop.
When robot door B is opened, robot B will stop.
Application Examples
(1) Emergency Stop
Switch
(2) Robot door A
(3) Robot door B
D40A
D40A
G9SX-BC
Logical AND connections
(3) Robot door B
(2) Robot door A
(1) Emergency Stop
Switch
G9SX-NS
G9SX-NS
Operation Example
(1) The Emergency Stop
Switch is pressed.
Stop Stop
Robot A
Robot B
(2) Robot door A
opened.
Stop Stop
Robot A
Robot B
(3) Robot door B
opened.
Stop Stop
Robot A
Robot A
Robot B
Robot B
Required Units
22
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-NS
2
Non-contact Door Switches D40A (Set of two)
42
G9SX
USER'S GUIDE
2. Using Non-contact Door Switch
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-NS: Auto reset, Logical AND connections (Category 3 Wiring)
1
Application Examples
Wiring Example
Feedback Loop
11
21
12
22
KM1
KM2
S1
KM1
S2
+24V
KM2
NC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
S1 : Emergency Stop Switch
S2 : Reset switch
S3, S4 : Non-contact Door Switch
KM1 to KM6 : Contactor
M1 to M3 : 3-phase motor
+24V
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
PLC etc.
GND
+24V
Non-contact
Door Switch
S4
Feedback Loop
Actuator
Non-contact
Door Switch
Actuator
S3
KM3
KM5
KM4
KM6
+24V
+24V
NC
A1 D1 D2 D3 D4 T31 T32 T33 Y1
+24V
NC
AND
T41
T42
OFF
G9SX-NS202 (Robot door A)
A1 D1 D2 D3 D4 T31 T32 T33 Y1
S14 S24
L1 X1 X2
KM3 KM4
PLC etc.
GND
AND
T41
T42
OFF
G9SX-NS202 (Robot door B)
Control circuit
A2
Feedback Loop
Control circuit
A2
KM3
GND
KM4
S14 S24
L1 X1 X2
KM5 KM6
PLC etc.
KM5
KM6
M2
M3
Note: This example corresponds to category 3.
G9SX
USER'S GUIDE
23
2. Using Non-contact Door Switch
■ Timing chart
Section
G9SX-BC202 (upper unit)
(6)
Emergency Stop Switch S1
Reset switch S2
1
KM1, KM2 NC contact
Application Examples
KM1, KM2 NO contact
Logical AND output L1
Rotation of motor M1
G9SX-NS202 (lower unit : Robot A)
Logical AND input T41
Non-contact
Door Switch S3
(1)
(2)
(3)
KM3, KM4 NC contact
KM3, KM4 NO contact
Rotation of motor M2
G9SX-NS202 (lower unit : Robot B)
Logical AND input T41
(4)
(5)
Non-contact
Door Switch S4
KM5, KM6 NC contact
KM5, KM6 NO contact
Rotation of motor M3
(1) Before operation is started.
(2) Robot door A is opened and robot A stops.
(3) Robot door A is closed and robot A restarts.
(4) Robot door B is opened and robot B stops.
(5) Robot door B is closed and robot B restarts.
(6) If the Emergency Stop Switch is pressed, the upper unit, lower unit A, and lower unit B will all stop.
24
G9SX
USER'S GUIDE
3. Coordinated operation of worker and machine
3-1 Manufacturing Automotive Parts Using Semi-automatic Processing
Safety Light
Curtain
F3SJ
Safety Light
Curtain
F3SJ
Basic Unit
G9SX-BC
Application Examples
(1) Emergency
Stop Switch
A22E
(3) Safety Light Curtain B
1
(2) Safety Light Curtain A
(2) Safety Light
Curtain A
(3) Safety Light
Curtain B
Section
Two pairs of Light Curtains are automatically enabled and disabled according to the operations
of the operator and robot.
Safety Guard
Switching Unit
G9SX-GS
Logical AND
connection
Contactor
(1) Emergency
Stop Switch
Robot
Emergency Stop Switch
When pressed, processing will stop.
Safety Light Curtain A
When both are interrupted simultaneously, processing will stop.
Auto switching
Safety Light Curtain B
Required Units
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-GS
1
Light Curtain + Light Curtain
44
G9SX
USER'S GUIDE
25
3. Coordinated operation of worker and machine
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-GS: Auto reset, Cross fault detection mode: OFF (Category 4 Wiring (with Safety Light Curtains)),
1
Logical AND connections,
Application Examples
OFF-delay time setting
Switching mode: Auto
Diagnostic check of Indicator : Enabled (UB only)
Wiring Example
Feedback loop
Emergency
Stop Switch
11
21
12
22
KM1
KM2
S1
S2
KM1
S1 : Emergency Stop Switch
S2 : Reset switch
KM1 to KM4 : Contactor
M1 to M2 : 3-phase motor
+24V
NC
KM2
A1 T11 T12 T21 T22 T31 T32 T33 Y1
G9SX-BC202
M1
+24V
Control circuit
A2
L1 L2
S14 S24
KM1 KM2
X1 X2
PLC etc.
GND
Safety Sensor A
F3SJ-A
Emitter
Safety Sensor B
F3SJ-A
Receiver
Emitter
Receiver
NC
GND
+24V +24V
NC
A1 T11 T12 T21 T22 Y1
Y3
NC
NC
M1
M2
NC
Control output 2
Control output 1
Control output 1
GND
Control output 2
Feedback Loop
KM3
KM4
+24V
+24V
NC
NC
T61 T62 T71 T72 Y2
Y4
AND
T31 T32 T33
T41 T42
OFF
G9SX-GS226-T15
KM3
Manual
+24V
Control circuit
Auto
KM4
M2
A2
S14 S24 S44 S54
KM3 KM4
GND
Note: This example corresponds to category 4.
26
G9SX
USER'S GUIDE
L1
X1 X2 X3 X4
UA
UB
PLC etc.
Indicator
Indicator
(Diagnostic
(Diagnostic
check disabled) check enabled)
3. Coordinated operation of worker and machine
■ Timing chart
Section
G9SX-BC202
(6)
Emergency Stop Switch S1
1
Reset switch S2
KM1, KM2 NC contact
Application Examples
KM1, KM2 NO contact
Logical AND output L1
G9SX-GS226-T15
Logical AND input T41
(3)
(1)
Safety Sensor A control output
(monitoring the robot)
(2)
(4)
(5)
Safety Sensor B control output
(monitoring the operator)
KM3, KM4 NC contact
KM3, KM4 NO contact
Input A monitor output X3
Input B monitor output X4
External indicator output UA
External indicator output UB
Controls not related to safety
Robot movement enabled
Robot movement enabled in
specific area only
Robot movement disabled
(1) Before operation is started.
(2) Operator inserts workpiece
(3) Robot processes workpiece
(4) Both operator and robot enter the coordinated area: Only the G9SX-GS stops.
(5) The G9SX-GS restarts.
(6) Emergency stop button pressed: All units stop.
G9SX
USER'S GUIDE
27
4. Safety Measures for limited operations
4-1 Manufacturing Flat-panel Displays (Maintenance)
Section
1
Switching between Normal Operating Mode and Maintenance Mode is performed manually.
In Normal Operating Mode, the Safety Door Switch is enabled, and in Maintenance Mode
the Safety Limit Switch is enabled.
Application Examples
(2) Cover (Safety Door Switch)
(3) Conveyor cart
(Safety Limit Switch)
(2) Cover
(1) Emergency
Stop Switch
A22E
(3) Conveyor cart
Safety Door
Switch
D4NS
Basic Unit
G9SX-BC
(4) Mode selector
Safety Limit
Switch
D4F
Key-type
Selector Switch
A22K
Safety Guard
Switching Unit
G9SX-GS
(4) Mode selector
Logical AND
connection
Contactor
(1) Emergency
Stop Switch
Conveyor cart
Normal operating mode
Manual
switching
Emergency Stop Switch
When pressed, processing will stop.
Cover
When the cover is opened, processing will stop.
Conveyor cart
Processing will continue regardless of the conveyor cart position.
Maintenance mode
Manual
switching
Emergency Stop Switch
When pressed, processing will stop.
Cover
Processing will continue regardless of whether the cover is opened or closed.
Conveyor cart
When the conveyor cart moves away from its safe position, processing will stop.
Required Units
28
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-GS
1
Door Switch + Limit Switch
44
G9SX
USER'S GUIDE
4. Safety Measures for limited operations
■ Wiring Example
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
1
OFF-delay time setting
Application Examples
Switching mode: Manual
Diagnostic check of Indicator: Enabled (UA only)
Wiring Example
Feedback loop
Emergency
Stop Switch
11
21
12
22
Section
Setup (For details, refer to Section 3.)
KM1
KM2
S1
S2
KM1
S1 : Emergency Stop Switch
S2, S7 : Reset switch
S3, S4 : Safety Limit Switch
S5 : Safety Door Switch
S6 : Selector switch
KM1 to KM4 : Contactor
M1 to M2 : 3-phase motor
+24V
NC
KM2
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
+24V
Control circuit
A2
S14 S24
L1 L2
KM1 KM2
X1 X2
PLC etc.
23
S3
Conveyor cart
24
S5
11
S4
21
11
22
12
Feedback loop
Cover
12
+24V
S6
KM3
Mode selector
KM4
+24V
+24V
NC
NC
A1 T11 T12 T21 T22 Y1
Y3
NC
M1
M2
AND
T61 T62 T71 T72 Y2
Y4
T31 T32 T33
T41 T42
OFF
G9SX-GS226-T15
KM3
Manual
+24V
Control circuit
Auto
KM4
M2
A2
S14 S24 S44 S54
KM3 KM4
GND
L1
X1 X2 X3 X4
UA
UB
PLC etc.
Indicator
Indicator
(Diagnostic
(Diagnostic
check enabled) check disabled)
Note: This example corresponds to category 4.
G9SX
USER'S GUIDE
29
4. Safety Measures for limited operations
■ Timing chart
Section
G9SX-BC202
(10)
Emergency Stop Switch S1
1
Reset switch S2
Application Examples
KM1, KM2 NC contact
KM1, KM2 NO contact
Logical AND output L1
G9SX-GS226-T15
Logical AND input T41
(4)
Safety Limit Switch S3
Limit Switch S4
(3)
(6)
Safety Door Switch
(5)
(1)
(7)
(9)
Reset switch S6
(2)
(8)
Mode selector input M1
Mode selector input M2
KM3, KM4 NC contact
KM3, KM4 NO contact
Input A monitor output X3
Input B monitor output X4
External indicator output UA
External indicator output UB
Controls not related to safety
Conveyor section movement enabled
(with machine in normal operating mode)
Conveyor section movement enabled in
specific area only
(with machine in maintenance mode)
Conveyor section movement disabled
(1) Start the G9SX-GS in normal operating mode.
(2) Switch to maintenance mode.
(3) The operator opens the door and performs maintenance.
(4) When Safety Limit Switch S3 and Limit Switch S4 are turned OFF in maintenance mode, the G9SX-GS stops.
(5) After the door is closed and the operating mode is switched to normal operating mode, restart the G9SX-GS.
(6) When the door is opened during normal operating mode, the G9SX-GS stops.
(7) Close the door and restart the G9SX-GS.
(8) When the operating mode is switched to maintenance mode while Safety Limit Switch S3 and Limit Switch S4 are turned OFF, the G9SX-GS
stops.
(9) Switch to normal operating mode, and when the door is closed, restart the G9SX-GS.
(10) Emergency stop button pressed: All units stop.
30
G9SX
USER'S GUIDE
4. Safety Measures for limited operations
4-2 Machining Center (Enabling Switch)
(1) Emergency
Stop Switch
A22E
Enabling
Switch
Guard Lock
Safety Door
Switches
(4) Mode selector
Key-type
Selector Switch
A22K
Application Examples
(1) Emergency
Stop Switch
(3) Motor
1
(2) Door
(2) Safety Door Switch
Section
Switching between Normal Operating Mode and Maintenance Mode is performed manually.
In Normal Operating Mode, the Safety Door Switch is enabled, and in Maintenance Mode,
the Safety Limit Switch is enabled.
Basic Unit
G9SX-BC
Safety Guard
Switching Unit
G9SX-GS
Logical AND
connection
Contactor
(3) Enabling Switch
Conveyor cart
Normal operating mode
Manual
switching
Emergency Stop Switch
When pressed, processing will stop.
Door
When the door is opened, processing will stop.
Enabling Device
The enabling switch is disabled.
Maintenance mode
Manual
switching
Emergency Stop Switch
When pressed, processing will stop.
Door
Door Switch is disabled.
Enabling Device
Processing will be possible only when the operator is gripping the enabling
switch.
Required Units
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-GS
1
Door Switch + Enabling Switch
44
G9SX
USER'S GUIDE
31
4. Safety Measures for limited operations
■ Wiring Example
Section
Setup (For details, refer to Section 3.)
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
1
OFF-delay time setting
Application Examples
Switching mode: Manual
Diagnostic check of Indicator: Enabled
Wiring Example
Feedback Loop
11
21
12
22
KM1
KM2
S1
KM1
S2
+24V
NC
S1 : Emergency Stop Switch
S2, S7 : Reset switch
S3 : Enabling Switch
S4 : Guard Lock Door Switch
S5 : Lock release switch
S6 : Safety Limit Switch
KM1 to KM4 : Contactor
M1 to M2 : 3-phase motor
KM2
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
+24V
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
PLC etc.
GND
Lock release signal
KM3
KM4
S4
S5
31
32
11
12
Door
S6
Feedback Loop
OPEN
2
4
1
3
KM3
Enabling
Switch
S3
Stop sigmal
+24V
S7
KM4
Mode selector
+24V
NC
NC
A1 T11 T12 T21 T22 Y1
Y3
M1 M2
NC
NC
T61 T62 T71 T72 Y2
Y4
AND
T31 T32 T33
T41 T42
OFF
G9SX-GS226-T15
Manual
+24V
Control circuit
KM3
Auto
KM4
A2
S14 S24 S44 S54
KM3 KM4
GND
32
G9SX
USER'S GUIDE
L1 X1 X2 X3 X4
UA
UB
M2
PLC etc.
Indicator
Indicator
(Diagnostic
(Diagnostic
check enabled) check enabled)
Note: This example corresponds to category 4.
4. Safety Measures for limited operations
■ Timing chart
Section
G9SX-BC202 (upper unit)
(10)
Emergency Stop Switch S1
1
Reset switch S2
Application Examples
KM1, KM2 NC contact
KM1, KM2 NO contact
Logical AND output L1
G9SX-GS226-T15 (lower unit)
Logical AND input T41
(3)
(8)
Guard Lock Door Switch S4
(4)
(6)
Enabling Switch S3
(1)
(5)
(7)
(9)
Reset switch S7
(2)
Mode selector input M1
Mode selector input M2
KM3, KM4 NC contact
KM5, KM6 NC contact
KM3, KM4 NO contact
KM5, KM6 NO contact
OFF-delay time
OFF-delay time
OFF-delay time
OFF-delay time
(1) In Normal operating mode, the lower unit starts.
(2) Maintenance mode is selected.
(3) The operator opens the door and performs maintenance operation.
(4) The Enabling Switch is gripped to the middle position.
(5) In maintenance mode, the lower unit starts.
(6) When the Enabling Switch is released or gripped, the lower unit stops.
(7) After closing the door and then switching to Normal operating mode, the lower unit will restart.
(8) If the door is opened while in Normal operating mode, the lower unit will stop.
(9) The door is closed, and the lower unit restarts.
(10) If the Emergency Stop Switch is pressed, the upper unit and lower unit will stop.
G9SX
USER'S GUIDE
33
4. Safety Measures for limited operations
4-3 LCD Manufacturing (Guard Lock Control)
Section
When the Safety Limit Switch has confirmed that the hazard source is in a safe position,
the Guard Lock Safety Door Switch will be unlocked.
1
(2) Guard Lock Door Switch
(2) Door
(3) Conveyor cart
(3) Safety Limit Switch
Application Examples
(1) Emergency
Stop Switch
A22E
Guard Lock
Safety Door
Switches
Safety Limit
Switch
D4F
Basic Unit
G9SX-BC
Safety Guard
Switching Unit
G9SX-GS
Logical AND
connection
Contactor
(1) Emergency
Stop Switch
Motor
Emergency Stop Switch
When pressed, processing will stop.
Guard Lock Door Switch
Auto
switching
When turned OFF at the same time, the machine will stop.
Limit Switch
Required Units
34
Unit
Qty.
Safety input to be applied
Page
G9SX-BC
1
Emergency Stop Switch
39
G9SX-GS
1
Guard Lock Door Switch + Limit Switch
44
G9SX
USER'S GUIDE
4. Safety Measures for limited operations
■ Wiring Example
G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring)
G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections,
1
No OFF-delay time setting
Application Examples
Switching mode: Auto
Diagnostic check of Indicator: Enabled (UA only)
Wiring Example
Feedback Loop
11
21
12
22
Section
Setup (For details, refer to Section 3.)
KM1
KM2
S1
S2
KM1
S1 : Emergency Stop Switch
S2, S7 : Reset switch
S3 : Lock release switch
S4 : Guard Lock Door Switch
S5, S6 : Limit Switch
KM1 to KM4 : Contactor
M1 to M2 : 3-phase motor
+24V
NC
KM2
A1 T11 T12 T21 T22 T31 T32 T33 Y1
M1
G9SX-BC202
+24V
Control circuit
A2
S14 S24
L1 L2
X1 X2
KM1 KM2
PLC etc.
GND
Lock release
switch
Guard Lock
Door Switch
(Mechanical lock)
S4
GND
E1
E2
42
41
12
22
11
21
Feedback Loop
Door
Conveyor cart
S5
Limit
Switch
Limit Switch
KM3
S7
KM4
OPEN
S6
Limit
Switch
+24V
NC
NC
A1 T11 T12 T21 T22 Y1
Y3
+24V
NC
M1 M2
T61 T62 T71 T72 Y2
AND
Y4
T31 T32 T33
T41 T42
OFF
G9SX-GS226-T15
Manual
+24V
Control circuit
A2
S14 S24 S44 S54
L1 X1 X2 X3 X4
Auto
UA
UB
KM3 KM4
KM3
GND
Note: This example corresponds to category 4.
Indicator
(Diagnostic
check enabled)
KM4
M2
G9SX
USER'S GUIDE
35
4. Safety Measures for limited operations
■ Timing chart
Section
G9SX-BC202 (upper unit)
(11)
Emergency Stop Switch S1
1
Reset switch S2
Application Examples
KM1, KM2 NC contact
KM1, KM2 NO contact
Logical AND output L1
G9SX-GS226-T15 (lower unit)
Logical AND input T41
(1)
(2)
(5)
(6)
(7)
(8)
Safety Limit Switch S5
Safety Limit Switch S6
Lock release signal
(External indicator output UA)
(3)
(4)
(9)
Guard Lock Door Switch S4
Lock release switch S1
Door can be opened.
Door can be opened.
Reset switch S7
KM3, KM4 NC contact
KM3, KM4 NO contact
(1) When the door is closed, operation is initiated with the reset switch.
(2) The Limit Switch detects the conveyor cart and the lock release signal turns ON.
(3) The door can be opened while the lock release switch pressed.
(4) The door is closed again.
(5) The conveyor cart moves.
(6) The Limit Switch detects the conveyor cart, and the lock release signal turns ON.
(7) The door can be opened while the lock release switch is pressed.
(8) The conveyor cart moves while the door is open, and the lower unit stops.
(9) The door is closed again. The lower unit remains stopped.
(10) The reset switch is used to restart operation.
(11) If the Emergency Stop Switch is pressed, the upper unit and lower unit will stop.
36
G9SX
USER'S GUIDE
(10)
Section
2
Section
Functions of G9SX
2
38
2. Functions of each Unit
39
2-1 Basic Unit
39
2-2 Advanced Unit
40
2-3 Non-Contact Door Switch Controller
42
2-4 Safety Guard Switching Unit
44
2-5 Expansion Unit
48
G9SX
USER'S GUIDE
Functions of G9SX
1. Function list of G9SX-series
37
1. Function list of G9SX-series
Function
G9SX-BC
G9SX-AD
G9SX-ADA
G9SX-NS
G9SX-NSA
G9SX-GS
Inputs
---
●
●
(2 inputs)
●
●
●
Outputs
●
●
●
●
●
●
Emergency stop
●
●
●
---
●
---
Door switch
●
●
●
---
●
●
Non-contact
door switch
(D40A)
---
---
---
●
●
---
Light curtain
●
●
●
---
---
●
Number of safety inputs
1
1
1
1
2
2
Instantaneous
outputs
2
3
2
2
2
2
OFF-delayed
outputs
---
2
2
---
2
2
OFF-delay time
---
0 to 15 s,
0 to 150 s
0 to 15 s,
0 to 150 s
---
0 to 3 s
0 to 15 s
Expansion Unit
connection
---
●
●
---
●
●
---
---
---
---
---
●
Logical
AND
connections
Section
2
Safety
inputs
Functions of G9SX
Safety
outputs
Model
Guard switching
38
G9SX
USER'S GUIDE
2. Functions of each Unit
2-1 Basic Unit
It is possible to connect to other Units by using the logical AND connection output.
■ G9SX-BC@
Safety Inputs
Safety Input
1 input (2-channel input)
Safety input devices
Emergency stop switch, door switch,
light curtain
Section
Safety inputs
Instantaneous outputs
T31 T32 T33 Y1
T11 T12 X1 A1
2 outputs
PWR
Logical AND Connections
None
Number of outputs
2 outputs
Functions of G9SX
G9SX-BC202
24VDC
OFF-delayed outputs None
Number of inputs
2
Safety Outputs (Semiconductor Outputs)
FB
T1
T2
EI
ERR
No.
T21 T22 X2
S14 S24 L1
A2
L2
Required Settings and Wiring
Item
G9SX-BC
Page
Logical AND connection
input enable/disable
---
---
Cross fault detection mode
❍
63
Reset mode
❍
62
OFF-delay time
---
---
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
Safety
Instantaneous
Output
Logical AND
Connection
Output
LED Indicators
Marking
Color
Name
PWR
Green
Power supply indicator
T1
Orange
Safety input #1 indicator
T2
Orange
Safety input #2 indicator
FB
Orange
Feedback/reset input indicator
EI
Orange
Safety output indicator
ERR
Red
Error indicator
T31 T32 T33 Y1
T11 T12 X1 A1
G9SX-BC202
24VDC
PWR
FB
T1
T2
EI
ERR
No.
T21 T22 X2
S14 S24 L1
A2
L2
G9SX
USER'S GUIDE
39
2. Functions of each Unit
2-2 Advanced Unit
This Unit has safety OFF-delayed outputs and can be connected to other Units using the logical AND connection
input and output.
■ G9SX-AD@
Safety Inputs
Section
Safety inputs
1 input (2-channel input)
Safety Input
Emergency stop switch, door switch,
Safety input devices
light curtain
Logical AND
Connection
Input
2
Functions of G9SX
Safety Outputs (Semiconductor Outputs)
Instantaneous outputs
3 outputs
OFF-delayed outputs
2 outputs
T31 T32 T33
T11 T12 Y1
X1
X2
Note: The OFF-delayed outputs can be used as instantaneous outputs by
setting the OFF-delay time to 0 s.
PWR
FB
T1
T2
AND
EI
0.7
0.6
0.5
0.4
0.3
0.2
Logical AND Connections
1 1.5 2
0 15
ED
3
4
5
7
10
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S34 S44 S54
Number of inputs
1 input
Number of outputs
1 output
A1
G9SX-AD322-T15
24VDC
A2
L1
OFF-delay Time Setting
G9SX-AD322-T15-@
0 to 15 s
G9SX-AD322-T150-@
0 to 150 s
Safety
Instantaneous
Output
Safety
OFF-delayed
Output
Required Settings and Wiring
Item
G9SX-AD
Page
Logical AND connection
input enable/disable
❍
57
Cross fault detection mode
❍
63
Reset mode
❍
62
OFF-delay time
❍
65
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
LED Indicators
Marking
Color
PWR
Green
Power supply indicator
T1
Orange
Safety input #1 indicator
T2
Orange
Name
T31 T32 T33
T11 T12 Y1
X1
X2
A1
G9SX-AD322-T15
24VDC
Safety input #2 indicator
PWR
FB
T1
T2
AND
FB
AND
40
Orange
Orange
Feedback/reset input indicator
Logical AND input indicator
EI
Orange
Safety output indicator
ED
Orange
OFF-delayed safety output
indicator
ERR
Red
G9SX
USER'S GUIDE
Error indicator
EI
0.7
0.6
0.5
0.4
0.3
0.2
1 1.5 2
0 15
ED
3
4
5
7
10
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S34 S44 S54
A2
L1
Logical AND
Connection
Output
2. Functions of each Unit
■ G9SX-ADA@
Safety Inputs
Safety inputs
1 input (2-channel input)
Safety Input
Emergency stop switch, door switch,
Safety input devices
light curtain
Logical AND
Connection
Input
Safety Outputs (Semiconductor Outputs)
Section
Instantaneous outputs 2 outputs
OFF-delayed outputs
2 outputs
T31 T32 T33 T51 T52
T11 T12 Y1 X1 X2
PWR
FB
T2
T1
AND1 AND2
0.7
0.6
0.5
0.4
0.3
0.2
Logical AND Connections
1 1.5 2
0 15
ED
3
4
5
7
10
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S44 S54 L1
Number of outputs
2 outputs
Functions of G9SX
EI
2 inputs
2
Note: The OFF-delayed outputs can be used as instantaneous outputs by
setting the OFF-delay time to 0 s.
Number of inputs
A1
G9SX-ADA222-T150
24VDC
A2
L2
OFF-delay Time Setting
G9SX-ADA222-T15-@
0 to 15 s
G9SX-ADA222-T150-@
0 to 150 s
Safety
Instantaneous
Output
Safety
OFF-delayed
Output
Logical AND
Connection
Output
Required Settings and Wiring
Item
G9SX-ADA
Page
Logical AND connection
input enable/disable
❍
57
Cross fault detection mode
❍
63
Reset mode
❍
62
OFF-delay time
❍
65
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
LED Indicators
Marking
Color
PWR
Green
Power supply indicator
T1
Orange
Safety input #1 indicator
T2
Orange
Name
T31 T32 T33 T51 T52
T11 T12 Y1 X1 X2
A1
G9SX-ADA222-T150
24VDC
Safety input #2 indicator
PWR
FB
T1
T2
AND1 AND2
FB
AND1
Orange
Orange
Feedback/reset input indicator
Logical AND input indicator
AND2
Orange
Logical AND input indicator
EI
Orange
Safety output indicator
ED
Orange
OFF-delayed safety output
indicator
ERR
Red
EI
0.7
0.6
0.5
0.4
0.3
0.2
1 1.5 2
0 15
ED
3
4
5
7
10
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S44 S54 L1
A2
L2
Error indicator
G9SX
USER'S GUIDE
41
2. Functions of each Unit
2-3 Non-Contact Door Switch Controller
This is a Special Controller for D40A Non-contact Door Switch. It can be connected to other Units using the logical
AND connection input and output.
■ G9SX-NS@
Safety Inputs
Section
Safety inputs
1 input (2-channel input)
Safety input devices Non-contact door switch (D40A)
Logical AND
Connection
Input
D40A Input
2
Safety Outputs (Semiconductor Outputs)
Functions of G9SX
Instantaneous outputs
2 outputs
OFF-delayed outputs
None
T31 T32 T33 D3
D1 D2 X1 A1
G9SX-NS202
24VDC
Logical AND Connections
PWR
AND
Number of inputs
1 input
Number of outputs
1 output
EI
FB
NS
ERR
No.
T41 T42 X2
S14 S24 L1
A2
D4
Required Settings and Wiring
Item
G9SX-NS
Page
Logical AND connection
input enable/disable
❍
57
Cross fault detection mode
---
---
Reset mode
❍
62
OFF-delay time
---
---
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
Safety
Instantaneous
Output
LED Indicators
Marking
Color
Name
PWR
Green
Power supply indicator
NS
Orange
Non-contact Door Switch input
indicator
FB
Orange
Feedback/reset input indicator
AND
Orange
Logical AND input indicator
EI
Orange
Instantaneous safety output
indicator
ERR
Red
T31 T32 T33 D3
D1 D2 X1 A1
G9SX-NS202
24VDC
PWR
FB
AND
NS
EI
42
G9SX
USER'S GUIDE
Error indicator
ERR
No.
T41 T42 X2
S14 S24 L1
A2
D4
Logical AND
Connection
Output
2. Functions of each Unit
■ G9SX-NSA@
Safety Inputs
Safety inputs
2 inputs (each with 2 channels)
Non-contact door switch (D40A),
Safety input devices
emergency stop switch, door switch
Safety Input
D40A Input
Logical AND
Connection
Input
Safety Outputs (Semiconductor Outputs)
2 outputs
OFF-delayed outputs
2 outputs
T31 T32 T33 D1
T11 T12 Y1 X1
D2
X2
FB
T1
T2
AND
NS
EI
ED
0.8 0.91.0
1.2
1.4
1.8
2.0
2.5
0 3.0
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S44 S54 L1
Number of outputs
1 output
Functions of G9SX
0.7
0.6
0.5
0.4
0.3
0.2
2
PWR
Logical AND Connections
1 input
D3
A1
G9SX-NSA222-T30
24VDC
Note: The OFF-delayed outputs can be used as instantaneous outputs by
setting the OFF-delay time to 0 s.
Number of inputs
Section
Instantaneous outputs
A2
D4
OFF-delay Time Setting
G9SX-NSA222-T03-@
0 to 3 s
Safety
Instantaneous
Output
Required Settings and Wiring
Item
G9SX-NSA
Page
Logical AND connection
input enable/disable
❍
57
Cross fault detection mode
❍
63
Reset mode
❍
62
OFF-delay time
❍
65
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
Safety
OFF-delayed
Output
Logical AND
Connection
Output
LED Indicators
Marking
Color
Name
PWR
Green
Power supply indicator
T1
Orange
Safety input #1 indicator
T2
Orange
Safety input #2 indicator
NS
Orange
Non-contact Door Switch input
indicator
FB
Orange
Feedback/reset input indicator
AND
Orange
Logical AND input indicator
EI
Orange
Instantaneous safety output
indicator
ED
Orange
OFF-delayed safety output
indicator
ERR
Red
T31 T32 T33 D1
T11 T12 Y1 X1
D2
X2
D3
A1
G9SX-NSA222-T30
24VDC
PWR
0.7
0.6
0.5
0.4
0.3
0.2
FB
T1
T2
AND
NS
EI
ED
0.8 0.91.0
1.2
1.4
1.8
2.0
2.5
0 3.0
OFF-DELAY
ERR
No.
T21 T22
T41 T42
S14 S24 S44 S54 L1
A2
D4
Error indicator
G9SX
USER'S GUIDE
43
2. Functions of each Unit
2-4 Safety Guard Switching Unit
This Unit can alternately enable two safety inputs. It can be used to construct safety systems for semi-automatic
processing and maintenance work.
■ G9SX-GS@
Safety Inputs
Safety inputs
2 inputs (each with 2 channels)
Safety Input
Section
Safety input devices Door switch, light curtain
Safety Input
Logical AND
Connection
Input
Safety Outputs (Semiconductor Outputs)
2
Functions of G9SX
Instantaneous outputs
2 outputs
OFF-delayed outputs
2 outputs
Note: The OFF-delayed outputs can be used as instantaneous outputs by
setting the OFF-delay time to 0 s.
T31 T32 T33 Y1 M1 M2 UA UB
T11 T12 T61 T62 Y2 Y3 Y4 A1
G9SX-GS226-T15
24VDC
PWR
Number of inputs
Number of outputs
AND
T2
UB
T7
EI
ED
1.5 2
3
0.7 1
4
0.6
5
0.5
7
0.4
10
0.3
0.2 0 15
1 input
FB
UA
T6
T1
Logical AND Connections
OFF-DELAY
ERR
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 S44 S54
1 output
OFF-delay Time Setting
G9SX-GS226-T15-@
0 to 15 s
Required Settings and Wiring
Item
G9SX-GS
Page
Logical AND connection
input enable/disable
❍
57
Cross fault detection mode
❍
63
Reset mode
❍
62
OFF-delay time
❍
65
Switching mode
❍
67
External indicator fault
diagnosis mode
❍
68
Safety
Instantaneous
Output
Safety
OFF-delayed
Output
Note: Carefully read the Precautions on pages 96 to 99 before configuring
a system using the G9SX-GS.
LED Indicators
Marking
Color
Name
T31 T32 T33 Y1 M1 M2 UA UB
T11 T12 T61 T62 Y2 Y3 Y4 A1
PWR
Green
Power supply indicator
T1
Orange
Safety input A, channel 1 indicator
24VDC
PWR
FB
T2
Orange
Safety input A, channel 2 indicator
T1
UA
T2
T6
UB
T7
G9SX-GS226-T15
44
T6
Orange
Safety input B, channel 1 indicator
T7
Orange
Safety input B, channel 2 indicator
FB
Orange
Feedback/reset input indicator
AND
Orange
Logical AND input indicator
EI
Orange
Safety output indicator
ED
Orange
OFF-delayed safety output indicator
UA
Orange
Safety input A disabled state indicator
UB
Orange
Safety input B disabled state indicator
ERR
Red
G9SX
USER'S GUIDE
Error indicator
EI
1.5 2
3
0.7 1
4
0.6
5
0.5
7
0.4
10
0.3
0.2 0 15
OFF-DELAY
AND
ED
ERR
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 S44 S54
Logical AND
Connection
Output
2. Functions of each Unit
Functions
Auto Switching Function
When the operator inserts the workpiece...
Safety Light Curtain A
While the robot processes the workpiece...
Safety Light Curtain B
• Safety Light Curtain A
monitors the robot.
• The robot can continue
monitors the operator.
• The robot can continue
to operate as long as the
operator does not
interrupt Safety Light
Auto
switching
Curtain B.
Section
to operate as long as it
does not interrupt Safety
Light Curtain A.
• Safety Light Curtain B
2
Manual Switching Function
During normal operation...
During maintenance...
• The Door Switch monitors
the opening and closing of
the door during normal
operation.
• The machine is able to
operate while the door is
closed.
Door Switch
Functions of G9SX
Note: If the operator is able to completely enter the zone inside Safety Light Curtain B, a presence detection device, such as a Safety Mat, is
necessary as an additional safety measure.
• The Limit Switch monitors
the conveyor cart position
during maintenance.
• The machine is able to
operate while the
conveyor cart is in a
specified area.
Manual
switching
Normal
operation
Maintenance
Limit Switch
G9SX
USER'S GUIDE
45
2. Functions of each Unit
Auto Switching Function
(2) Safety Light Curtain A
(2) Safety
Light Curtain A
(3) Safety Light
Curtain B
(1) Emergency
Stop Switch
A22E
(3) Safety Light Curtain B
Safety Light
Curtain
F3SJ
Safety Light
Curtain
F3SJ
Section
2
Basic Unit
G9SX-BC
Auxiliary Output
Logical AND
connection
Programmable
Controllers
CS/CJ Series
Safety Output
Functions of G9SX
The auxiliary output
can be used to
notify operators of
the input, output, or
error status.
Safety Guard
Switching Unit
G9SX-GS
(1) Emergency
Stop Switch
External
External
indicator A indicator B
Robot
Working condition
External
indicator
Welding robot Conveying robot
External Indicator
Output
Contactor
The external indicator
output can be used to
notify operators of Safety
Light Curtains that may
safely be interrupted.
Note: External indicator output may be used as necessary.
G9SX-GS
Safety input
Safety output
Monitor output
External indicator
Safety input A
ON
ON
Input A
monitor
ON
Safety Light
Curtain A
Indicator A
Safety input B
Safety output
Normal operation
Safety Light Curtain B
ON
Emergency
Stop Switch
Welding robot Conveying robot
Indicator B
Safety input A
Monitoring
ON
ON
Input A
monitor
ON
Safety Light
Curtain A
Indicator A
Safety input B
Safety output
Safety Light Curtain B
OFF
Emergency
Stop Switch
OFF
Input B
monitor
OK to work
Indicator B
Safety input A
Welding robot Conveying robot
OFF
Safety Light Curtain B
OFF
Input A
monitor
ON
Input B
monitor
ON
Safety Light
Curtain A
Indicator A
Safety input B
Monitoring
Safety output
ON
Emergency
Stop Switch
Indicator B
Not OK
to work
3
Hazardous condition
Input B
monitor
OK to work
1
2
46
ON
Welding robot Conveying robot
Safety input A
OFF
OFF
OFF
Input A
monitor
OFF
Safety Light
Curtain A
Indicator A
Safety input B
Safety output
Safety Light Curtain B
4
G9SX
USER'S GUIDE
OFF
Emergency
Stop Switch
Not OK
to work
OFF
Input B
monitor
Indicator B
2. Functions of each Unit
Manual Switching Function
(2) Cover
(2) Safety Door Switch
(3) Conveyor cart
(3) Safety
Limit Switch
(1) Emergency
Stop Switch
A22E
Safety Door
Switch
D4NS
Safety
Limit Switch
D4F
Normal operation
Working condition
External
indicator
External
External
indicator A indicator B
Safety output
The external indicator
output can be used to
notify operators that the
cover may be opened.
Note: External indicator output may be used as necessary.
G9SX-GS
Safety input
Disabled
Limit
Switch
Mode
selector
Safety output Mode selector
Monitor output
External indicator
Normal
operating mode
Monitoring
Input A
monitor
ON
Indicator A
Safety output
Door Switch
OFF
Safety input B
ON
ON
Emergency
Stop Switch
Input B
monitor
Indicator B
Not OK
to open
1
Safety input A
Limit
Switch
Input A
monitor
Indicator A
Safety input B
Emergency
Stop
Switch
OK
to open
2
ON
ON
Disabled
Door Switch
Maintenance
mode
ON
Mode
selector
Maintenance
Conveyor cart
External Indicator
Output
Safety input A
Disabled
Monitoring
Disabled
Safety output
OFF
Input B
monitor
Indicator B
Safety input A
Monitoring
Limit
Switch
OK
to open
OFF
Input B
monitor
Limit
Switch
Disabled
Safety output
Indicator B
Maintenance
mode
OFF
OFF
Input A
monitor
OFF
Input B
monitor
OFF
Mode
selector
Indicator A
Safety input B
Disabled
Door Switch
Indicator A
Safety input A
OFF
Monitoring
Input A
monitor
Safety input B
Emergency
Stop Switch
3
ON
ON
Mode
selector
Door Switch
Maintenance
mode
ON
Disabled
Hazardous condition
Contactor
Functions of G9SX
(1) Emergency
Stop Switch
Programmable
Controllers
CS/CJ Series
2
Auxiliary Output
The auxiliary output
can be used to
notify operators of
the input, output, or
error status.
Safety Guard
Switching Unit
G9SX-GS
Logical AND
connection
(4) Mode selector
Key-type
Selector Switch
A22K
Section
Basic Unit
G9SX-BC
4
(4) Mode selector
Emergency
Stop Switch
OK
to open
Disabled
Safety output
Indicator B
G9SX
USER'S GUIDE
47
2. Functions of each Unit
2-5 Expansion Unit
By connecting an Expansion Unit to the G9SX-AD/ADA, G9SX-NSA, or G9SX-GS, safety relay contact outputs can
be added that are synchronized with the safety outputs of the Unit to which the Expansion Unit is connected.
■ G9SX-EX-@
Safety Outputs (Safety Relay Outputs)
Section
Instantaneous outputs
4 outputs
OFF-delayed outputs
None
2
Functions of G9SX
G9SX-AD
G9SX-ADA
G9SX-NSA
G9SX-GS
G9SX-EX
Logical AND Connections
Number of inputs
None
Number of outputs
None
Insert the
connector
G9SX-EX
Required Settings and Wiring
Item
G9SX-EX
Page
Logical AND connection
input enable/disable
---
---
Cross fault detection mode
---
---
Reset mode
---
---
OFF-delay time
---
---
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
Safety
Instantaneous
Output
Note: Refer to 2-10 Connecting Expansion Units on page 69.
LED Indicators
Marking
Color
PWR
Green
Power supply indicator
EI
Orange
Safety output indicator
ERR
Red
Name
Error indicator
PWR
EI
ERR
48
G9SX
USER'S GUIDE
Insert the
connector
2. Functions of each Unit
■ G9SX-EX-T@
Safety Outputs (Safety Relay Outputs)
Instantaneous outputs
None
OFF-delayed outputs
4 outputs
Logical AND Connections
Number of inputs
None
Number of outputs
None
Insert the
connector
G9SX-EX041-T
Insert the
connector
G9SX-EX
Section
G9SX-AD
G9SX-ADA
G9SX-NSA
G9SX-GS
G9SX-EX
2
Required Settings and Wiring
G9SX-EX-T
Page
Logical AND connection
input enable/disable
---
---
Cross fault detection mode
---
---
Reset mode
---
---
OFF-delay time
--- (See note)
65
Switching mode
---
---
External indicator fault
diagnosis mode
---
---
Functions of G9SX
Item
Safety
OFF-delayed
Output
Note: 1. The OFF-delay time on G9SX-EX-T is set from the OFF-delay
preset time on the connected unit (G9SX-AD/-ADA/-NSA/-GS).
2. Refer to 2-10 Connecting Expansion Units on page 69.
LED Indicators
Marking
Color
PWR
Green
Power supply indicator
Orange
OFF-delayed safety output
indicator
ED
ERR
Red
Name
Error indicator
G9SX-EX041-T
PWR
ED
ERR
G9SX
USER'S GUIDE
49
MEMO
50
G9SX
USER'S GUIDE
Section
3
Wiring and Setup
52
1-2 Advanced Unit
53
1-3 Non-contact Door Switch Controller
54
1-4 Safety Guard Switching Unit
55
1-5 Expansion Unit
56
2. Functions, Wiring and Settings
Wiring and Setup
1-1 Basic Unit
3
52
Section
1. I/O Terminals
57
2-1 Logical AND Connection
57
2-2 Response Time and Operation Time
60
2-3 Reset Mode
62
2-4 Cross Fault Detection
63
2-5 Connecting Safety Sensors and the G9SX
64
2-6 OFF-delay Time
65
2-7 Non-contact Door Switch
66
2-8 Switching Mode
67
2-9 External Indicator Fault Diagnosis
68
2-10 Connecting Expansion Units
69
2-11 Confirming Settings
70
G9SX
USER'S GUIDE
51
1. I/O Terminals
1-1 Basic Unit
Signal name
Terminal name
Section
Power supply inputs
A1, A2
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
Safety inputs
T11, T12, T21, T22
Refer to 2-4 Cross Fault Detection and 2-5
Connecting Safety Sensors and the G9SX.
Feedback/reset inputs
T31, T32, T33
Refer to 2-3 Reset Mode.
Cross fault detection input
Y1
Refer to 2-4 Cross Fault Detection.
Instantaneous safety outputs
S14, S24
Keep these outputs open when they are not used.
Logical AND connection output
L1, L2
Refer to 2-1 Logical AND Connection.
Auxiliary monitor outputs
X1, X2
Keep these outputs open when they are not used.
3
Wiring and Setup
G9SX-BC
A1 T11 T12 T21 T22 T31 T32 T33 Y1
(See
note 1.)
Power
supply
circuit
A2
Safety
Input 1
Safety
Input 2
Reset/Feedback
Input
Safety outputs control
S14 S24
L1 L2
Cross
fault
detection
input
Auxiliary
outputs control
X1 X2
(See note 2.)
Note: 1. Internal power supply circuit is not isolated.
2. Outputs S14 and S24 are internally redundant.
52
Wiring
G9SX
USER'S GUIDE
1. I/O Terminals
1-2 Advanced Unit
Signal name
Terminal name
Wiring
Safety inputs
T11, T12, T21, T22
Refer to 2-4 Cross Fault Detection and 2-5
Connecting Safety Sensors and the G9SX
Feedback/reset inputs
T31, T32, T33
Refer to 2-3 Reset Mode.
Logical AND connection inputs
T41, T42, T51, T52
Refer to 2-1 Logical AND Connection.
Cross fault detection input
Y1
Refer to 2-4 Cross Fault Detection.
Instantaneous safety outputs
S14, S24, S34
Keep these outputs open when they are not used.
OFF-delayed safety outputs
S44, S54
Keep these outputs open when they are not used.
Logical AND connection output
L1, L2
Refer to 2-1 Logical AND Connection.
Auxiliary monitor outputs
X1, X2
Keep these outputs open when they are not used.
G9SX-ADA
A1 T11 T12 T21 T22 T31 T32 T33 Y1
T41 T42
(See
note 1.)
Power
supply
circuit
A2
(See note 2.)
Safety
Input 1
Safety
Input 2
Logical AND input
Expansion Unit
Auxiliary
output control output control
S14 S24 S34 S44 S54 L1 X1 X2
(See note 3.)
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 are internally redundant.
(See
note
2.)
(See
note 1.)
Cross
Reset/Feedback fault
detection
Input
input
Safety output control
A1 T11 T12 T21 T22 T31 T32 T33 Y1 T41 T42 T51 T52
Power
supply
circuit
A2
Safety
Input 1
Safety
Input 2
Wiring and Setup
G9SX-AD
3
A1, A2
Section
Power supply inputs
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
Cross
Logical
Logical
Reset/Feedback fault
detection AND input AND input 2
Input
input
Safety output control
Auxiliary
Expansion Unit
output control output control
S14 S24 S44 S54 L1 L2 X1 X2
(See note 3.)
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 are internally redundant.
G9SX
USER'S GUIDE
53
1. I/O Terminals
1-3 Non-contact Door Switch Controller
Signal name
Terminal name
Wiring
Section
3
Wiring and Setup
Power supply inputs
A1, A2
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
Safety inputs
T11, T12, T21, T22
Refer to 2-4 Cross Fault Detection and 2-5
Connecting Safety Sensors and the G9SX.
Non-contact Door Switch (D40A) inputs
D1, D2, D3, D4
Refer to 2-7 Non-contact Door Switch.
Feedback/reset inputs
T31, T32, T33
Refer to 2-3 Reset Mode.
Logical AND connection inputs
T41, T42
Refer to 2-1 Logical AND Connection.
Cross fault detection input
Y1
Refer to 2-4 Cross Fault Detection.
Instantaneous safety outputs
S14, S24
Keep these outputs open when they are not used.
OFF-delayed safety outputs
S44, S54
Keep these outputs open when they are not used.
Logical AND connection output
L1
Refer to 2-1 Logical AND Connection.
Auxiliary monitor outputs
X1, X2
Keep these outputs open when they are not used.
G9SX-NS
A1
G9SX-NSA
D1 D2 D3 D4 T31 T32 T33
T41 T42
A1
T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42
(See
note
2.)
(See
note 2.)
Power Non-contact Door Reset/Feedback Logical AND
input
supply
Input
Switch control
circuit
Auxiliary
(See
Safety output control
output control
note 1.)
A2
S14 S24
L1
X1
X2
(See note 3.)
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S24 are internally redundant.
54
G9SX
USER'S GUIDE
Power
supply
circuit
(See
note 1.)
A2
Safety
input 1
Safety
input 2
fault
Reset/Feedback Cross
detection Non-contact Door
Input
Switch control
input
Safety output control
S14 S24 S44 S54 L1
Auxiliary
output control
X1
Logical
AND input
Expansion Unit
output control
X2
(See note 3.)
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 are internally redundant.
1. I/O Terminals
1-4 Safety Guard Switching Unit
Signal name
Terminal name
Wiring
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
T11, T12, T21, T22
Safety inputs B
T61, T62, T71, T72
Refer to 2-4 Cross Fault Detection and 2-5
Connecting Safety Sensors and the G9SX.
Mode switching inputs
M1, M2
Refer to 2-8 Switching Mode.
Feedback/reset inputs
T31, T32, T33
Refer to 2-3 Reset Mode.
Logical AND connection inputs
T41, T42
Refer to 2-1 Logical AND Connection.
Cross fault detection inputs
Y1, Y2
Refer to 2-4 Cross Fault Detection.
Instantaneous safety outputs
S14, S24
Keep these outputs open when they are not used.
OFF-delayed safety outputs
S44, S54
Keep these outputs open when they are not used.
Logical AND connection output
L1
Refer to 2-1 Logical AND Connection.
Auxiliary monitor outputs
X1, X2, X3, X4
Keep these outputs open when they are not used.
External indicator outputs
UA, UB
Refer to 2-9 External Indicator Fault Diagnosis.
External indicator diagnosis switching
inputs
Y3, Y4
Refer to 2-9 External Indicator Fault Diagnosis.
Wiring and Setup
Safety inputs A
3
A1, A2
Section
Power supply inputs
G9SX-GS
A1
T11 T12 T21 T22 Y1
M1 M2
T61 T62 T71 T72 Y2
Y3 Y4 T31 T32 T33
T41 T42
(See
note
2.)
Cross
Power Safety input A Safety input A fault Mode selector Safety input B Safety input B
detection
supply
Ch. 1
Ch. 2
input
Ch. 1
Ch. 2
input A
circuit
(See
Safety output control
Auxiliary output control
note 1.)
A2
S14 S24 S44 S54 L1
X1 X2 X3 X4
Cross
fault
detection
input B
External
indicator
diagnosis
switching input
Reset/
feedback input
External indicator
output control
Logical
AND input
Expansion Unit
output control
UA UB
(See note 3.)
Note: 1. Internal power supply circuit is not isolated.
2. Logical AND input is isolated.
3. Outputs S14 to S54 and L1 are internally redundant.
G9SX
USER'S GUIDE
55
1. I/O Terminals
1-5 Expansion Unit
Signal name
Terminal name
Wiring
Power supply inputs
A1, A2
Connect the power supply plus (24 VDC) to the
A1 terminal.
Connect the power supply minus (GND) to the A2
terminal.
Safety outputs (See note.)
13-14, 23-24, 33-34, 43-44
Keep these outputs open when not used.
Note: The safety outputs are instantaneous safety outputs for the G9SX-EX401, and OFF-delayed safety outputs for the G9SX-EX041-T.
G9SX-EX401/G9SX-EX041-T
A1
Section
3
Wiring and Setup
56
(See
note 1.)
Exp.
sig.
IN
13 23 33 43
Safety
output
Power control
supply
circuit Auxiliary
output
control
A2
X2
(See note 2.)
K1
Exp.
sig.
OUT
K2
14 24 34 44
Note: 1. Internal power supply circuit is not isolated.
2. Relay outputs are isolated.
G9SX
USER'S GUIDE
2. Functions, Wiring and Settings
2-1 Logical AND Connection
When connecting two or more Units using a logical AND connection, the logical AND connection setting is
performed on the Unit on the input side. Set the logical AND connection preset switch on the Unit that is on the input
side (G9SX-AD322 in the below diagram) to AND.
1. When the G9SX-AD/-NS/-NSA/-GS Is on the Input Side
Unit A
AND
L1
A2
T41
T42
OFF
AND
OFF
G9SX-AD322
Wiring and Setup
Unit B
Unit C
AND
L1
OFF
A2
L1
A2
OFF
AND
T41 T42 T51 T52
3
2. When the G9SX-ADA Is on the Input Side
AND
Section
Note: 1. In the above diagram, a setting error will occur and G9SX-AD322 will set a lock out if the logical AND setting switch on G9SX-AD322 is set to OFF.
Set the switch carefully.
2. Set the logical AND setting switch on Unit A to OFF.
3. A logical AND input cannot be input to the G9SX-BC.
AND
OFF
OFF
T51/T52
T41/T42
G9SX-ADA222
Note: 1. When not connecting Unit B, leave terminals T41 and T42 of the G9SX-ADA222 Unit open, and set the logical AND setting switch T41/T42 to OFF.
2. When not connecting Unit C, leave terminals T51 and T52 of the G9SX-ADA222 Unit open, and set the logical AND setting switch to OFF.
When connecting multiple Units to the input side, follow the wiring example in the following diagram.
Unit A
Input a
G9SX-BC202 or
G9SX-AD322-T
Output (a) L1 A2
Unit B
T41 T42
Logical AND connection signal
(1st stage)
Input b
G9SX-AD322-T
Output (a&b) L1 A2
Next unit (4 unit max.)
T41 T42
G9SX-AD322-T
Logical AND connection signal
(2nd stage)
Next unit (4 unit max.)
T41 T42
G9SX-AD322-T
L1 A2
Next unit (5 layers max.)
Note: When a logical AND connection is not used, keep the logical AND connection inputs (terminals T41, T42, T51, and T52) and logical AND connection
outputs (terminals L1 and L2) open, and set the logical AND setting switch to OFF.
G9SX
USER'S GUIDE
57
2. Functions, Wiring and Settings
3. Logical AND Connection Combinations
( 1 ) One logical AND connection output from an Advanced Unit G9SX-AD can be logical AND connected to up to
four Advanced Units.
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
( 2 ) Two logical AND outputs from a Basic Unit G9SX-BC can be logical AND connected to up to eight Advanced
Units.
G9SX-BC
Section
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
3
G9SX-AD
Wiring and Setup
G9SX-AD
( 3 ) Two logical AND outputs from an Advanced Unit G9SX-ADA can be logical AND connected to up to eight
Advanced Units.
G9SX-ADA
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
( 4 ) Any Advanced Unit with logical AND input can be logical AND connected to Advanced Units on up to five tiers.
Advanced Unit
or Basic Unit
G9SX-AD
G9SX-AD
G9SX-AD
G9SX-AD
58
G9SX
USER'S GUIDE
2. Functions, Wiring and Settings
( 5 ) Two logical AND connection outputs, each from different Advanced/Basic Units, can be logical AND connected
to a single G9SX-ADA Unit.
G9SX-BC
G9SX-BC
G9SX-ADA
( 6 ) The largest possible system configuration contains a total of 20 Advanced and Basic Units. In this configuration,
each Advanced Unit can have up to five Expansion Units.
Advanced Unit
or Basic Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Advanced Unit
Number of Units connected
in series by logical AND:
5 Units max.
Advanced Unit
Wiring and Setup
Advanced Unit
3
Advanced Unit
Section
Advanced Unit
Note 1: Basic Unit = G9SX-BC
Advanced Unit = G9SX-AD or G9SX-ADA
Note 2: The G9SX-AD322-T-@ has only one logical AND
output.
Number of Units connected
per logical AND output:
4 Units max.
Advanced Unit
Advanced Unit
Total number of Units
connected by logical AND:
20 Units max.
Note: The section on Advanced Units, above, can also be replaced with G9SX-NS/-NSA/-GS.
G9SX
USER'S GUIDE
59
2. Functions, Wiring and Settings
2-2 Response Time and Operation Time
(1) G9SX-BC
Safety input
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
15 ms
50 ms
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Safety input
15 ms
50 ms
Logical AND connection
input
15 ms
100 ms
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Non-contact Door Switch
input
20 ms
100 ms
Logical AND connection
input
15 ms
100 ms
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Non-contact Door Switch
input
20 ms
100 ms
Safety input
15 ms
50 ms
Logical AND connection
input
15 ms
100 ms
Safety input
(2) G9SX-AD/ADA
Section
Safety input
D4NS
3
Logical AND
connection input
Wiring and Setup
(3) G9SX-NS
Non-contact Door
Switch input
D40A
Logical AND
connection input
(4) G9SX-NSA
Non-contact Door
Switch input
D40A
Logical AND
connection input
Safety Input
D4NS
Note: 1. The maximum response time is the time it takes the output to turn OFF after the input turns OFF.
2. The maximum operating time is the time it takes the output to turn ON after the input turn ON.
60
G9SX
USER'S GUIDE
2. Functions, Wiring and Settings
(5) G9SX-GS
Safety Input A
D4NS
Safety Input B
D4NS
Logical AND
connection input
Max. response time
(excluding Expansion Units)
(See note 1.)
Max. operating time
(excluding Expansion Units)
(See note 2.)
Safety input A
15 ms (See note 3.)
50 ms
Safety input B
15 ms (See note 3.)
50 ms
15 ms
100 ms
Logical AND connection
input
Note: 1. The maximum response time is the time it takes the output to turn OFF after the input turns OFF.
2. The maximum operating time is the time it takes the output to turn ON after the input turn ON.
3. The maximum response time exists when safety input A or safety input B is enabled.
Case 1
Safety Input
A22E
3
Response Time from When A22E Turns OFF until Safety Output 2
Section
(6) When two or more Units are connected using a logical AND connection.
Turns OFF
+
15 ms
(Logical AND
=
Wiring and Setup
15 ms
(A22E)
30 ms
Connection (1))
Safety Output (1)
Case 2
D40A
Safety Input
D4NS (1)
Logical AND
Connection
(1)
Response Time from When D40A Turns OFF until Safety Output 3
Turns OFF
20 ms
(D40A)
+
15 ms
(Logical AND
=
35 ms
Connection (2))
Case 3
Safety Output (2)
Logical AND
Connection
(2)
Safety Input
D4NS (2)
Response Time from When A22E Turns OFF until Safety Output 3
Turns OFF
15 ms
(A22E)
+
15 ms
(Logical AND
Connection (1))
+
15 ms
(Logical AND
= 45 ms
Connection (2))
Note: The operation time is calculated in a similar fashion.
Safety Output (3)
G9SX
USER'S GUIDE
61
2. Functions, Wiring and Settings
2-3 Reset Mode
Set the reset mode using feedback/reset input terminals T31, T32, and T33.
Reset mode
Wiring
Function summary
Feedback Loop
KM1
KM2
The signal to terminal T33 must be ON for the
safety output to turn ON.
If terminal T33 is not ON, the safety output will
not turn ON.
KM3
Auto reset mode
KM4
+24 V KM5
Section
T31
T32
T33
3
Feedback Loop
Wiring and Setup
KM1
Reset
switch
KM2
KM3
Manual reset mode
KM4
KM5
T31
62
The signal to terminal T32 must turn ON and then
OFF for the safety output to turn ON.
If terminal T32 does not turn ON and then OFF,
the safety output will not turn ON.
G9SX
USER'S GUIDE
T32
+24 V
T33
2. Functions, Wiring and Settings
2-4 Cross Fault Detection
The cross fault detection setting for the safety input is made using the cross fault detection input (terminals Y1 and
Y2).
Cross fault detection mode
Cross fault detection input
ON
Open
OFF
Connect to +24 V
Cross fault detection input
Safety input to be monitored
Function summary
Terminal Y1
Terminals T11-T12 and T21-T22
Detects cross faults across T11-T12 and T21-T22
Terminal Y2
Terminals T61-T62 and T71-T72
Detect cross faults in T61-T62 and T71-T72
If a fault is detected, the following will occur.
Section
1. The safety outputs and logical AND outputs will be locked out.
2. The LED error indicator will be lit.
3
3. The error output (auxiliary output) will turn ON.
Wiring and Setup
For wiring, refer to the following description.
( 1 ) Cross Fault between T11-T12 and T21-T22
Cross fault
detection
Wiring
+24 V
S1
Corresponds to
Safety Category 2
+24 V
T11
T12
T21
T22
Y1
OFF
+24 V
+24 V
S1
Corresponds to
Safety Category 3
+24 V
T11
T12
T21
T22
Y1
T11
T12
T21
T22
NC
Y1
S1
ON
Corresponds to
Safety Category 4
G9SX
USER'S GUIDE
63
2. Functions, Wiring and Settings
2-5 Connecting Safety Sensors and the G9SX
( 1 ) When connecting safety sensors to the G9SX, the Y1 terminal must be connected to 24 VDC.
The G9SX will detect a connection error, if the Y1 terminal is open.
( 2 ) In many cases, safety sensor outputs include an OFF-shot pulse for self diagnosis.
The following condition of test pulse is applicable as safety inputs for the G9SX.
• OFF-shot pulse width of the sensor, during the ON-state: 340 μs max.
340 µs max.
Section
3
Wiring and Setup
64
G9SX
USER'S GUIDE
2. Functions, Wiring and Settings
2-6 OFF-delay Time
The safety output preset time is set using the OFF-delay time preset switch (1 each on the front and back of the
Unit).
Note: 1. Normal operation will occur only if both switches are set to the same setting.
An error will occur if both switches are not identically set.
2. If the preset time is set to 0 seconds, the output function as an instantaneous safety output.
Front
Back
Switch
Section
Switch
3
Wiring and Setup
Refer to the following illustration for details on setting switch positions.
1. G9SX-AD322-T15
0.7
0.6
0.5
0.4
0.3
0.2
1 1.5 2
0 15
3
0.7
0.6
0.5
0.4
0.3
0.2
4
5
7
10
OFF-DELAY
Notch
Example 1: 0-second
OFF-delay
setting
1 1.5 2
0 15
3
4
5
7
10
OFF-DELAY
Example 2: 1-second
OFF-delay
setting
2. G9SX-AD322-T150
60
50
40
30
20
10
70 80 90
100
110
120
130
140
0 150
OFF-DELAY
Example 1: 0-second
OFF-delay
setting
60
50
40
30
20
10
Notch
70 80 90
100
110
120
130
140
0 150
OFF-DELAY
Example 2: 70-second
OFF-delay
setting
G9SX
USER'S GUIDE
65
2. Functions, Wiring and Settings
2-7 Non-contact Door Switch
Example: Wiring a Single Switch
Yellow
Blue
Brown
Black
White
D40A-1C@
D1 D2 D3 D4
Auxiliary output load
(See note.)
A2
Blue
Brown
Black
Brown
Black
White
Blue
Brown
Black
Wiring and Setup
Connect Up to 30 Non-contact Door Switches.
White
3
Example: Wiring Multiple Switches
White
Note: The auxiliary output load current must be 10 mA max.
Blue
Section
G9SX-NS202-@
G9SX-NSA222-T03-@
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
Wiring of Inputs and Outputs
Signal name
66
Wire color
Description of operation
Non-contact Door Switch
power supply input
Brown
Non-contact Door Switch input
White
Inputs signals from the G9SX-NS@.
The Non-contact Door Switch input must be ON as a required condition for the
Non-contact Door Switch output to be ON.
Non-contact Door Switch
output
Black
Turns ON and OFF according to actuator detection and the status of the Noncontact Door Switch input.
Auxiliary output
Yellow
Turns ON when actuator is detected.
G9SX
USER'S GUIDE
Blue
Supplies power to the D40A.
Connect to the D3 and D4 terminals of the G9SX-NS@.
2. Functions, Wiring and Settings
2-8 Switching Mode
The switching mode is set by using the Switching Function setting switch on the bottom of the G9SX Unit. Set the
switch to Auto for auto switching and Manual for manual switching.
For manual switching, connect the mode selector as shown in the following table.
Switching Mode
Auto switching
Switching Function setting switch
Mode selector connection
Manual
NC
NC
M1
M2
Auto
+24V
Manual
Auto
Maintenance
mode
M1
M2
Section
Manual switching
Normal
operating
mode
3
Wiring and Setup
M1 ON, M2 OFF: Normal operating mode
M1 OFF, M2 ON: Maintenance mode
G9SX
USER'S GUIDE
67
2. Functions, Wiring and Settings
2-9 External Indicator Fault Diagnosis
Diagnostic checks of external indicators connected to the G9SX-GS's external indicator outputs UA and UB can be
switched with Y3 and Y4, respectively.
Note: 1. If there is no indicator connected to external indicator output UA, connect Y3 to 24 V. If there is no indicator connected to external indicator output
UB, connect Y4 to 24 V. If they are not connected to 24 V, the G9SX-GS will detect an error.
2. Diagnostic checks cannot be made for LED indicators. Disable the diagnostic check if using LED indicators.
External indicator
output
Diagnostic check enabled
Diagnostic check disabled
+24V
NC
Y3
Y3
UA
UA
Indicator
Indicator
UA
Section
3
Wiring and Setup
68
+24V
NC
Y4
Y4
UB
UB
Indicator
Indicator
UB
G9SX
USER'S GUIDE
2. Functions, Wiring and Settings
2-10 Connecting Expansion Units
• G9SX-EX/G9SX-EX-T Expansion Units can be connected to the G9SX-AD/-ADA Advanced Unit, G9SX-NSA
Non-contact Door Switch Controller, or G9SX-GS Safety Guard Switching Unit to increase the number of safety
outputs. (Expansion Units cannot be connected to the G9SX-BC or to the G9SX-NS Non-contact Door Switch
Controller.)
• A maximum of five Expansion Units can be connected to one Advanced Unit. This may be a combination of
G9SX-EX Instantaneous types and G9SX-EX-T OFF-delayed types.
• Remove the end connector from the Unit (G9SX-AD, G9SX-ADA, G9SX-NSA, or G9SX-GS) and insert the
connector on the Connecting Cable from the first Expansion Unit. Place the end connector that was removed from
the Unit on the last Expansion Unit (i.e., the rightmost Expansion Unit).
• When Expansion Units are connected to an Advanced Unit, make sure that power is supplied to every Expansion
Unit. (Refer to the following diagram for actual Expansion Unit connection.)
Section
3
Advanced Unit
G9SX-AD/-ADA/-NSA/-GS
Wiring and Setup
Terminating
connector
Expansion Unit
G9SX
USER'S GUIDE
69
2-11 Confirming Settings
Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON.
During this settings indication period, the ERR indicator will light, however the auxiliary error output will remain OFF.
G9SX-AD/-ADA/-BC/-NS/-NSA
Indicator
Setting position
T1
Cross fault detection
mode
Y1 terminal
FB
Reset mode
T33 or T32
terminal
Logical AND connection
input mode (See note.)
Logical AND
connection preset
switch
AND
(AND1,
AND2)
Indicator
status
Lit
Setting mode
Setting status
Detection mode
Y1 = open
Not lit
Non-detection mode
Y1 = 24 VDC
Lit
Manual reset mode
T33 = 24 VDC
Auto reset mode
T32 = 24 VDC
Not lit
Lit
Enable logical AND input
"AND"
Not lit
Disable logical AND input
"OFF"
Section
Note: Except for the G9SX-BC and G9SX-NS.
G9SX-GS
3
Wiring and Setup
Indicator
Item
T1
Cross fault detection
mode for safety input A
Y1 terminal
T6
Cross fault detection
mode for safety input B
Y2 terminal
FB
Reset mode
T33 or T32
terminal
Logical AND connection
input mode
Logical AND
connection preset
switch
Switching Function
Switching Function
setting switch
AND
UA, UB
70
Item
G9SX
USER'S GUIDE
Setting position
Indicator
status
Setting mode
Setting status
Lit
Enabled
Y1 = open
Not lit
Disabled
Y1 = 24 VDC
Lit
Enabled
Y2 = open
Not lit
Disabled
Y2 = 24 VDC
Manual reset mode
T33 = 24 VDC
Auto reset mode
T32 = 24 VDC
Lit
Not lit
Lit
Enabled
"AND"
Not lit
Disabled
"OFF"
Lit
Not lit
Manual switching
Auto switching
"Manual"
"Auto"
Section
4
Ratings and
Specifications
1. Ratings
72
1-2 Non-contact Door Switch Controller
73
1-3 Safety Guard Switching Unit
74
1-4 Expansion Unit
75
76
2-1 Advanced Unit/Basic Unit
76
2-2 Non-contact Door Switch Controller
77
2-3 Safety Guard Switching Unit
78
2-4 Expansion Unit
79
3. Dimensions and Terminal arrangements
Ratings and Specifications
2. Characteristics
4
72
Section
1-1 Advanced Unit/Basic Unit
80
3-1 Advanced Unit
80
3-2 Basic Unit
80
3-3 Non-contact Door Switch Controller
81
3-4 Safety Guard Switching Unit
81
3-5 Expansion Unit
82
G9SX
USER'S GUIDE
71
1. Ratings
1-1 Advanced Unit/Basic Unit
Power input
Item
Model
G9SX-AD322-@/ADA222-@
Rated supply voltage
24 VDC
Operating voltage range
−15% to 10% of rated supply voltage
Rated power consumption (See note.) 4 W max.
G9SX-BC202-@
3 W max.
Note: Power consumption of loads not included.
Inputs
Item
Model
G9SX-AD322-@/ADA222-@
G9SX-BC202-@
Safety input
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kΩ (See note.)
Feedback/reset input
Note: Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item
Section
4
Ratings and Specifications
72
Model
G9SX-AD322-@/ADA222-@
G9SX-BC202-@
Instantaneous safety output
(See note 1.)
OFF-delayed safety output
(See note 1.)
P channel MOS FET transistor output
P channel MOS FET transistor output
Load current:
Load current:
Using 2 outputs or less: 1 A DC max. (See note 2.)
Using 1 output: 1 A DC max. (See note 2.)
Using 3 outputs or more: 0.8 A DC max.
Using 2 outputs: 0.8 A DC max.
Auxiliary output
PNP transistor output
Load current: 100 mA max.
Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis. When using the safety outputs as input
signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
Approx. 100 ms
ON
OFF
360 µs max.
2. The following derating is required when Units are mounted side-by-side.
G9SX-AD322-@/G9SX-ADA222-@/G9SX-BC202-@: 0.4 A DC max. load current
G9SX
USER'S GUIDE
1. Ratings
1-2 Non-contact Door Switch Controller
Power input
Item
Model
G9SX-NS202-@
Rated supply voltage
24 VDC
Operating voltage range
−15% to 10% of rated supply voltage
Rated power consumption (See note.) 3 W max.
G9SX-NSA222-T03-@
4 W max.
Note: Power consumption of loads not included.
Inputs
Item
Model
G9SX-NS202-@/G9SX-NSA222-T03-@
Safety input (See note 1.)
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8kΩ (See note 2.)
Feedback/reset input
Note: 1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Door Switch.
2. Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item
Model
G9SX-NS202-@/G9SX-NSA222-T03-@
Auxiliary output
PNP transistor output
Load current: 100 mA max.
4
P channel MOS FET transistor output
Load current: 0.8 A DC max. (See note 2 and 3.)
Section
Instantaneous safety output
(See note 1.)
OFF-delayed safety output
(See note 1.)
Approx.100 ms
ON
OFF
360 µs max.
2. The following derating is required when Units are mounted side-by-side.
G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A DC max. load current
3. Apply the following rated load conditions for inductive loads.
IEC/EN 60947-5-1 DC13: 0.8 A
UL508 Pilot Duty: 0.5 A
G9SX
USER'S GUIDE
Ratings and Specifications
Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
73
1. Ratings
1-3 Safety Guard Switching Unit
Power Input
Item
Model
G9SX-GS226-T15-@
Rated supply voltage
24 VDC
Operating voltage range
−15% to 10% of rated supply voltage
Rated power consumption (See note.) 5 W max.
Note: Power consumption of loads not included.
Inputs
Item
Model
G9SX-GS226-T15-@
Safety inputs
Mode selector input
Operating voltage: 20.4 VDC to 26.4 VDC, Internal impedance: Approx. 2.8 kΩ (See note.)
Feedback/reset input
Note: Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
Item
Model
Section
Instantaneous safety outputs
(See note 1.)
OFF-delayed safety outputs
(See note 1.)
P channel MOS FET transistor outputs
Load current: 0.8 A DC max. (See note 2 and 3.)
Auxiliary outputs
PNP transistor outputs
(for input, output, and error monitoring) Load current: 100 mA max.
4
External indicator outputs
Ratings and Specifications
74
G9SX-GS226-T15-@
P channel MOS FET transistor outputs
Connectable indicators
• Incandescent lamp: 24 VDC, 3 to 7 W
• LED lamp: 10 to 300 mA DC
Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
Approx.100 ms
ON
OFF
360 µs max.
2. The following derating is required when Units are mounted side-by-side.
G9SX-GS226-T15-@: 0.4 A DC max. load current
3. Apply the following rated load conditions for inductive loads.
IEC/EN 60947-5-1 DC13: 0.8 A
UL508 Pilot Duty: 0.5 A
G9SX
USER'S GUIDE
1. Ratings
1-4 Expansion Unit
Power Input
Item
Model
G9SX-EX-@
Rated supply voltage
24 VDC
Operating voltage range
−15% to 10% of rated supply voltage
Rated power consumption (See note.) 2 W max.
Note: Power consumption of loads not included.
Outputs
Item
Model
G9SX-EX-@
Rated load
250 VAC, 3 A / 30 VDC, 3 A (resistive load)
Rated carry current
3A
Maximum switching voltage
250 VAC, 125 VDC
Section
4
Ratings and Specifications
G9SX
USER'S GUIDE
75
2. Characteristics
2-1 Advanced Unit/Basic Unit
Item
Model
G9SX-AD322-@/ADA222-@
G9SX-BC202-@
Over-voltage category (IEC/EN 60664-1)
II
Operating time (OFF to ON state)
(See note 1.)
50 ms max. (Safety input: ON) (See note 2.)
100 ms max. (Logical AND connection input:
ON) (See note 3.)
Response time (ON to OFF state)
(See note 1.)
15 ms max.
ON-state residual voltage
3.0 V max. (safety output, auxiliary output)
OFF-state leakage current
0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time (Reset button pressing
time)
100 ms min.
Accuracy of OFF-delay time
Within ± 5% of the set value
Insulation
resistance
4
Ratings and Specifications
Section
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
500 VAC for 1 min
together
Vibration resistance
---
20 MΩ min. (at 100 VDC)
Between all terminals
connected together and DIN
rail
Shock
resistance
---
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
20 MΩ min. (at 100 VDC)
together
Between all terminals
connected together and DIN
rail
Dielectric
strength
50 ms max. (Safety input: ON)
---
500 VAC for 1 min
Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Destruction
300 m/s2
Malfunction
100 m/s2
Ambient temperature
−10 to 55°C (no icing or condensation)
Ambient humidity
25% to 85%
Terminal tightening torque (See note 4.)
0.5 N·m
Weight
Approx. 200 g
Approx. 125 g
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. Represents the operating time when the safety input turns ON with all other conditions set.
3. Represents the operating time when the logical AND input turns ON with all other conditions set.
4. For the G9SX-@-RT (with screw terminals) only.
76
G9SX
USER'S GUIDE
2. Characteristics
2-2 Non-contact Door Switch Controller
Item
Model
Over-voltage category
(IEC/EN 60664-1)
Operating time (OFF to ON state)
(See note 1.)
Response time (ON to OFF state)
(See note 1.)
G9SX-NS202-@
G9SX-NSA222-T03-@
100 ms max. (Logical AND connection input ON
and Non-contact Door Switch input ON)
50 ms max. (Safety input: ON)
(See note 2.)
100 ms max. (Logical AND connection input ON
and Non-contact Door Switch input ON) (See
note 3.)
15 ms max. (Logical AND connection input:
OFF)
15 ms max. (Safety input OFF and logical AND
connection input OFF)
20 ms max. (Non-contact Door Switch input OFF)
20 ms max. (Non-contact Door Switch input: OFF)
(See note 4.)
(See note 4.)
II
ON-state residual voltage
3.0 V max. (safety output, auxiliary output)
OFF-state leakage current
0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety input,
logical AND connection input, and Noncontact Door Switch input
100 m max. (External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time
Within ±5% of the set value
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
20 MΩ min. (at 100 VDC)
together
Section
4
Insulation
resistance
---
Ratings and Specifications
Between all terminals
connected
together and DIN rail
Dielectric
strength
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected
500 VAC for 1 min.
together
Between all terminals
connected together and DIN
rail
Vibration resistance
Shock
resistance
10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Destruction
300 m/s2
Malfunction
100 m/s2
Ambient operating temperature
−10 to 55°C (no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque (See note 5.)
0.5 N·m
Weight
Approx. 125 g
Approx. 200 g
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. Represents the operating time when the safety input turns ON with all other conditions set.
3. Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set.
4. The fault detection time for 24-V short-circuit faults on the non-contact door switch input is 35 ms max.
When calculating the safe distance for applications other than as door switches, use a fault detection time of 35 ms.
5. For the G9SX-@-RT (with screw terminals) only.
G9SX
USER'S GUIDE
77
2. Characteristics
2-3 Safety Guard Switching Unit
Item
Model
G9SX-GS226-T15-@
Overvoltage category (IEC/EN 60664-1)
II
Operating time (OFF to ON state)
(See note 1.)
50 ms max. (Safety input: ON) (See note 2.)
100 ms max. (Logical AND connection input: ON) (See note 3.)
Response time (ON to OFF state)
(See note 1.)
15 ms max.
Allowable switching time for mode
selector input (See notes 4 and 6.)
450 ms max.
Response time for switching operating
modes (See notes 5 and 6.)
50 ms max.
ON-state residual voltage
3.0 V max. for safety outputs, auxiliary outputs, and external indicator outputs
OFF-state leakage current
0.1 mA max. for safety outputs and auxiliary outputs, 1 mA max. for external indicator outputs
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time
Within ± 5% of the set value
Section
Insulation
resistance
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected together 20 MΩ min. (at 100 VDC)
4
Between all terminals
connected together and DIN
rail
Ratings and Specifications
Dielectric
strength
Between logical AND
connection terminals, and
power supply input terminals
and other input and output
terminals connected together 500 VAC for 1 min
Between all terminals
connected together and DIN
rail
Vibration resistance
Shock
resistance
Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Destruction
300 m/s2
Malfunction
100 m/s2
Ambient operating temperature
−10 to 55°C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque (See note 7.)
0.5 N·m
Weight
Approx. 240 g
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. Represents the operating time when the safety input turns ON with all other conditions set.
3. Represents the operating time when the logical AND input turns ON with all other conditions set.
4. This is the allowable switching time for the operating mode selector. If switching takes more than 450 ms, the G9SX-GS@ will detect an error.
5. This is the time required for the safety input to actually switch to an activated condition after the mode selector input is switched.
<When M2 Is Turned ON after M1 Is Turned OFF> <When M1 Is Turned OFF after M2 Is Turned ON>
450 ms max.
M1
450 ms max.
M1
M2
M2
50 ms max.
UA
UA
Safety input B is activated
UB
Safety input A is activated
6. Only when the G9SX-GS@ is used with manual switching.
7. For the G9SX-@-RT (with screw terminals) only.
78
G9SX
USER'S GUIDE
50 ms max.
UB
Safety input B is activated
Safety input A is activated
2. Characteristics
2-4 Expansion Unit
Item
Model
G9SX-EX-@
Overvoltage category (IEC/EN 60664-1)
II (Safety relay outputs 13 to 43 and 14 to 44: III)
Operating time (OFF to ON state)
(See note 1.)
30 ms max. (See note 2.)
Response time (ON to OFF state)
(See note 1.)
10 ms max. (See note 2.)
ON-state residual voltage
3.0 V max. for safety outputs and auxiliary outputs
OFF-state leakage current
0.1 mA max. for safety outputs and auxiliary outputs
Maximum wiring length of safety input
and logical AND input
100 m max.
(External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time (Reset button pressing
time)
100 ms min.
Accuracy of OFF-delay time (See note 3.) Within ± 5% of the set value
Insulation
resistance
Between all terminals
connected together and DIN
rail
Between all terminals
connected together and DIN
rail
1,200 VAC for 1 min
Between different poles of
outputs
Section
Dielectric
strength
100 MΩ min. (at 500 VDC)
Shock
resistance
Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Destruction
300 m/s2
Malfunction
100 m/s2
Electrical
100,000 cycles min.
(rated load, switching frequency: 1,800 cycles/hour)
Mechanical
5,000,000 cycles min. (switching frequency: 7,200 cycles/hour)
Durability
Ambient operating temperature
−10 to 55°C (with no icing or condensation)
Ambient operating humidity
25% to 85%
Terminal tightening torque (See note 4.)
0.5 N·m
Weight
Approx. 165 g
Ratings and Specifications
Vibration resistance
4
Between safety relay outputs
connected together and
2,200 VAC for 1 min
other terminals connected
together
Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response
times, respectively, of all the Units connected by logical AND.
2. This does not include the operating time or response time of Safety Guard Switching Units (G9SX-AD/-ADA/-NSA/-GS) that are connected.
3. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
4. For the G9SX-@-RT (with screw terminals) only.
G9SX
USER'S GUIDE
79
3. Dimensions and Terminal arrangements
Note: All units are in millimeters unless otherwise indicated.
3-1 Advanced Unit
G9SX-AD322-@
(6) (See note 2.)
Terminal arrangement
T31 T32 T33
T11 T12 Y1 X1 X2 A1
T31 T32 T33
T11 T12 Y1
X1
X2
A1
G9SX-AD322-T15
24VDC
PWR
FB
T1
T2
100 max.
AND
EI
0.7
0.6
0.5
0.4
0.3
0.2
PWR
FB
T1
T2
AND
ED
1 1.5 2
0 15
3
4
5
7
10
EI
ERR
ED
ERR
No.
OFF-DELAY
T21 T22
T41 T42
S14 S24 S34 S44 S54
A2
L1
T21 T22
T41 T42 A2
S14 S24 S34 S44 S54 L1
35.5 max.
(35)*
(10)
* Typical dimension
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
G9SX-ADA222-@
Section
(6) (See note 2.)
Terminal arrangement
T31 T32 T33 T51 T52
T11 T12 Y1 X1 X2 A1
4
Ratings and Specifications
AND1 AND2
G9SX-ADA222-T150
T31 T32 T33 T51 T52
T11 T12 Y1 X1 X2
A1
G9SX-ADA222-T150
24VDC
PWR
FB
T1
FB
T1
T2
T2
100 max.
AND1 AND2
EI
0.7
0.6
0.5
0.4
0.3
0.2
PWR
ED
1 1.5 2
0 15
AND2
EI
3
4
5
7
10
AND1
ED
ERR
ERR
No.
OFF-DELAY
T21 T22
T41 T42
S14 S24 S44 S54 L1
A2
L2
T21 T22
T41 T42 A2
S14 S24 S44 S54 L1 L2
35.5 max.
(35)*
* Typical dimension
(10)
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
3-2 Basic Unit
G9SX-BC202-@
(6) (See note 2.)
Terminal arrangement
T31 T32 T33 Y1
T11 T12 X1 A1
T31 T32 T33 Y1
T11 T12 X1 A1
G9SX-BC202
24VDC
PWR
FB
T1
T2
EI
ERR
100 max.
PWR
FB
T1
T2
EI
ERR
No.
T21 T22 X2
S14 S24 L1
A2
L2
T21 T22 X2 A2
S14 S24 L1 L2
23 max.
(22.5)*
* Typical dimension
80
G9SX
USER'S GUIDE
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
3. Dimensions and Terminal arrangements
3-3 Non-contact Door Switch Controller
G9SX-NS202-@
(6) (See note 2.)
Terminal arrangement
T31 T32 T33 D3
D1 D2 X1 A1
T31 T32 T33 D3
D1 D2 X1 A1
G9SX-NS202
24VDC
PWR
FB
AND
NS
EI
100 max.
PWR
FB
AND
NS
ERR
EI
ERR
No.
T41 T42 X2
S14 S24 L1
A2
D4
T41 T42 X2 A2
S14 S24 L1 D4
23 max.
(22.5)*
115 max.
* Typical dimension
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
G9SX-NSA222-T03-@
Terminal arrangement
(6) (See note 2.)
T11 T12 Y1 X1 X2 A1
D2
X2
D3
A1
FB
T1
T2
AND
NS
EI
ED
0.8 0.91.0
1.2
1.4
1.8
2.0
2.5
0 3.0
100 max.
PWR
FB
T1
T2
AND
NS
EI
ED
ERR
ERR
No.
OFF-DELAY
T21 T22
T41 T42
S14 S24 S44 S54 L1
A2
D4
T21 T22
T41 T42 A2
S14 S24 S44 S54 L1 D4
35.5 max.
(35)*
* Typical dimension
(10)
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
Ratings and Specifications
0.7
0.6
0.5
0.4
0.3
0.2
PWR
4
T31 T32 T33 D1
T11 T12 Y1 X1
G9SX-NSA222-T30
24VDC
Section
T31 T32 T33 D1 D2 D3
3-4 Safety Guard Switching Unit
G9SX-GS226-T15-@
(6) (See note 2.)
Terminal arrangement
T31 T32 T33 Y1 M1 M2 UA UB
T11 T12 T61 T62 Y2 Y3 Y4 A1
T31 T32 T33 Y1 M1 M2 UA UB
T11 T12 T61 T62 Y2 Y3 Y4 A1
G9SX-GS226-T15
PWR
FB
AND
T1
UA
T2
T6
UB
T7
EI
ED
24VDC
PWR
FB
AND
T1
UA
T2
T6
UB
T7
EI
ED
1.5 2
3
0.7 1
4
0.6
5
0.5
7
0.4
10
0.3
0.2 0 15
100 max.
ERR
OFF-DELAY
ERR
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 S44 S54
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 S44 S54
45.5 max.
(45)*
* Typical dimension
(10)
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
G9SX
USER'S GUIDE
81
3. Dimensions and Terminal arrangements
3-5 Expansion Unit
Expansion Unit
G9SX-EX401-@
Expansion Unit (OFF-delayed Model)
G9SX-EX041-T-@
Terminal arrangement
G9SX-EX401-@
(Expansion Unit)
G9SX-EX041-T-@
(Expansion Unit
with OFF Delay)
13 23 33 43
13 23 33 43
PWR
PWR
EI
ED
ERR
ERR
(6) (See note 2.)
G9SX-EX041-T
100 max.
Section
23 max.
(22.5)*
* Typical dimension
4
Ratings and Specifications
82
G9SX
USER'S GUIDE
115 max.
(6) (See note 2.)
Note: 1. Above outline drawing is for -RC terminal type.
2. For -RC terminal type only.
A1 X2 A2
A1 X2 A2
14 24 34 44
14 24 34 44
Appendix
1. Troubleshooting
84
2. Logical AND Connections
91
3. Accessories and Related Products
93
Appendix
G9SX
USER'S GUIDE
83
1. Troubleshooting
■ Fault Detection
When the G9SX detects a fault, the ERR indicator and/or other indicators light up or blink to inform the user about
the fault.
Check and take necessary measures referring to the following table, and then re-supply power to the G9SX.
■ Error Indications
G9SX-BC202-@/G9SX-AD322-@/G9SX-ADA222-@
ERR
indicator
Other
indicator
---
Blinks
T1 blinks
T2 blinks
Fault
Check points and measures to take
Page
(1) Check the disturbance level around the
G9SX and the related system.
---
(2) Replace the G9SX.
---
(1) Incorrect wiring of safety input 1.
(For example, cross fault detection
mode settings and safety input wiring
do not match).
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input 1 and 24 V or
another I/O terminal short circuited.
(2) Check the wiring to T11 and T12.
---
Fault due to electro- (1) Affected by excessive electromagnetic
disturbance.
magnetic disturbance
or of internal circuits (2) Failure of the G9SX internal circuit.
Fault involved with
safety input 1
Fault involved with
safety input 2
(3) Check the wiring to T11, T12, T21 and
(3) Short circuit between safety inputs
(when cross fault detection mode is ON).
T22.
63
(4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX.
---
(1) Incorrect wiring of safety input 2.
(For example, cross fault detection
mode settings and safety input wiring
do not match).
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input 2 and 24 V or
another I/O terminal short circuited.
(2) Check the wiring to T21 and T22.
---
(3) Short circuit between safety inputs
(3) Check the wiring to T11, T12, T21 and
(when cross fault detection mode is ON).
T22.
63
Appendix
(4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX.
---
Fault involved with
feedback/reset
inputs
(1) Incorrect feedback/reset input wiring.
(1) Check the wiring to T31, T32 and T33.
62
Fault in Expansion
Unit
(2) Connecting cable to Expansion Unit or
terminating connector disconnected.
(2) Check the connecting cable to the
Expansion Unit and the connection of
the terminating connector.
69
(3) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(3) Change to a power supply with a
greater current capacity.
---
(4) Supply voltage outside the rated value.
(4) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(5) Failure in internal circuit for T31, T32
and T33.
(5) Replace the G9SX.
---
(6) Expansion Unit relay contact or internal
circuit failed.
(6) Replace the Expansion Unit.
---
(1) Check the wiring to S14, S24 and S34.
---
(2) Check the wiring to S14, S24 and S34.
---
Lights
FB blinks
Expected causes of the fault
Abnormal supply
voltage to
Expansion Unit
Failure in internal
circuit
(1) Instantaneous safety outputs short
circuited.
Fault involved with
instantaneous safety (2) Instantaneous safety outputs and 24 V,
outputs
0 V, or another I/O terminal short
circuited.
EI blinks
Fault involved with
logical AND
connection outputs
(3) Logical AND connection outputs and
24 V, 0 V, or another I/O terminal short
circuited.
(3) Check the wiring to L1 and L2.
---
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
76
(5) Failure in internal circuit for S14, S24
and S34.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for L1 and L2.
(6) Replace the G9SX.
---
Failure in internal
circuit
84
G9SX
USER'S GUIDE
1. Troubleshooting
ERR
indicator
Other
indicator
Fault
Expected causes of the fault
Check points and measures to take
(1) Safety OFF-delayed outputs short
circuited.
(1) Check the wiring to S44 and S54.
---
(2) Wiring to the OFF-delayed safety
contact outputs and 24 V, 0 V, or
another I/O terminal short circuited.
(2) Check the wiring to S44 and S54.
---
Incorrect set values
for OFF-delay time
(3) Settings of two OFF-delay time preset
switches are not the same.
(3) Confirm the set values of the OFFdelay time preset switches on the front
and back of the Unit.
65
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
76
(5) Failure in internal circuit for S44 and
S54.
(5) Replace the G9SX.
---
(6) OFF-delay time preset switch failed.
(6) Replace the G9SX.
---
Fault involved with
OFF-delayed safety
outputs
ED blinks
Failure in internal
circuit
(1) Logical AND connection input and 24 V,
0 V, or another I/O terminal short
(1) Check the wiring to T41 and T51.
circuited.
Fault involved with
logical AND
connection input
Lights
Page
AND blinks
Incorrect setting for
(AND1,
logical AND
AND2)
connection setting
switch
Fault in internal
circuit
Supply voltage
All indicators outside the rated
except PWR value
blink
---
(2) Maximum cable length exceeded.
(2) Make sure that the wiring length for the
T41, T42, T51 and T52 terminals is less
than 100 m.
---
(3) Maximum number of connected Units
exceeded.
(3) Check the logical AND connection for
the G9SX.
59
(4) The logical AND connection preset
switch is set to OFF.
(4) When using a logical AND connection,
set the logical AND connection preset
switch to AND.
57
(5) Failure in internal circuit for T41, T42,
T51 and T52.
(5) Replace the G9SX.
---
(6) The logical AND connection preset
switch failed.
(6) Replace the G9SX.
---
(1) Supply voltage outside the rated value.
(1) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(2) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(2) Change to a power supply with a
greater current capacity.
---
ERR
indicator
Other
indicator
Fault
T1
Off
T2
Blinks
Mismatch between
input 1 and input 2
Expected causes of the fault
The input status between safety input 1
and safety input 2 is different due to a
contact failure or short circuit of a safety
input device or a wiring fault.
Check points and measures to take
Page
Check the wiring from safety input devices
to the G9SX. Or check the input sequence
of safety input devices.
After removing the fault, turn both safety
input 1 and 2 to the OFF state.
---
G9SX
USER'S GUIDE
Appendix
When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table.
85
1. Troubleshooting
G9SX-NS202-@/G9SX-NSA222-@
ERR
indicator
Other
indicator
---
Blinks
T1 blinks
T2 blinks
Fault
Fault involved with
safety input 1
Fault involved with
safety input 2
NS blinks
Failure in internal
circuit
Appendix
FB blinks
Check points and measures to take
Page
(1) Check the disturbance level around the
G9SX and the related system.
---
(2) Replace the G9SX.
---
(1) Incorrect wiring of safety input 1.
(For example, cross fault detection
mode settings and safety input wiring
do not match).
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input 1 and 24 V or
another I/O terminal short circuited.
(2) Check the wiring to T11 and T12.
---
(3) Short circuit between safety inputs
(when cross fault detection mode is
ON).
(3) Check the wiring to T11, T12, T21 and
T22.
63
Fault due to electro- (1) Affected by excessive electromagnetic
disturbance.
magnetic disturbance
or of internal circuits (2) Failure of the G9SX internal circuit.
Fault in Non-contact
Door Switch input
Lights
Expected causes of the fault
(4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX.
---
(1) Incorrect wiring of safety input 2.
(For example, cross fault detection
mode settings and safety input wiring
do not match).
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input 2 and 24 V or
another I/O terminal short circuited.
(2) Check the wiring to T21 and T22.
---
(3) Short circuit between safety inputs
(when cross fault detection mode is
ON).
(3) Check the wiring to T11, T12, T21 and
T22.
63
(4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX.
---
(1) Wiring to the Non-contact Door Switch
input and 24 V or another I/O terminal
short circuited.
(1) Check the wiring to D1 and D2.
66
(2) Incorrect wiring of Non-contact Door
Switch inputs in series connection.
(2) Check the wiring to the D40A.
66
(3) Non-contact Door Switch failed.
(3) Replace the D40A.
---
(4) Failure in internal circuit for D1 and D2.
(4) Replace the G9SX.
---
Fault involved with
feedback/reset
inputs
(1) Incorrect feedback/reset input wiring.
(1) Check the wiring to T31, T32, and T33.
62
Fault in Expansion
Unit
(2) Connecting cable to Expansion Unit or
terminating connector disconnected.
(2) Check the connecting cable to the
Expansion Unit and the connection of
the terminating connector.
69
(3) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(3) Change to a power supply with a
greater current capacity.
---
(4) Supply voltage outside the rated value.
(4) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(5) Failure in internal circuit for T31, T32
and T33.
(5) Replace the G9SX.
---
(6) Expansion Unit relay contact or internal
circuit failed.
(6) Replace the Expansion Unit.
---
(1) Check the wiring to S14 and S24.
---
(2) Check the wiring to S14 and S24.
---
Abnormal supply
voltage to
Expansion Unit
Failure in internal
circuit
(1) Instantaneous safety outputs short
circuited.
Fault involved with
instantaneous safety (2) Instantaneous safety outputs and 24 V,
outputs
0 V, or another I/O terminal short
circuited.
EI blinks
Fault involved with
logical AND
connection outputs
(3) Logical AND connection outputs and
24 V, 0 V, or another I/O terminal short
circuited.
(3) Check the wiring to L1.
---
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
77
(5) Failure in internal circuit for S14 and
S24.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for L1.
(6) Replace the G9SX.
---
Failure in internal
circuit
86
G9SX
USER'S GUIDE
1. Troubleshooting
ERR
indicator
Other
indicator
Fault
Check points and measures to take
Page
(1) Safety OFF-delayed outputs short
circuited.
(1) Check the wiring to S44 and S54.
---
(2) Wiring to the OFF-delayed safety
contact outputs and 24 V, 0 V, or
another I/O terminal short circuited.
(2) Check the wiring to S44 and S54.
---
Incorrect set values
for OFF-delay time
(3) Settings of two OFF-delay time preset
switches are not the same.
(3) Confirm the set values of the OFFdelay time preset switches on the front
and back of the Unit.
65
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
77
(5) Failure in internal circuit for S44 and
S54.
(5) Replace the G9SX.
---
(6) OFF-delay time preset switch failed.
(6) Replace the G9SX.
---
Fault involved with
OFF-delayed safety
outputs
ED blinks
Failure in internal
circuit
Fault involved with
logical AND
connection input
Lights
Expected causes of the fault
Incorrect setting for
AND blinks logical AND
connection setting
switch
Fault in internal
circuit
Supply voltage
All indicators outside the rated
except PWR value
blink
(1) Logical AND connection input and 24 V,
0 V, or another I/O terminal short
(1) Check the wiring to T41.
circuited.
---
(2) Maximum cable length exceeded.
(2) Make sure that the wiring length for the
T41 and T42 terminals is less than 100 m.
---
(3) Maximum number of connected Units
exceeded.
(3) Check the logical AND connection for
the G9SX.
59
(4) The logical AND connection preset
switch is set to OFF.
(4) When using a logical AND connection,
set the logical AND connection preset
switch to AND.
57
(5) Failure in internal circuit for T41 and
T42.
(5) Replace the G9SX.
---
(6) The logical AND connection preset
switch failed.
(6) Replace the G9SX.
---
(1) Supply voltage outside the rated value.
(1) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(2) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(2) Change to a power supply with a
greater current capacity.
---
When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table.
Other
indicator
Fault
T1
Off
T2
Blinks
Mismatch between
input 1 and input 2
Expected causes of the fault
The input status between safety input 1
and safety input 2 is different due to a
contact failure or short circuit of a safety
input device or a wiring fault.
Check points and measures to take
Page
Check the wiring from safety input devices
to the G9SX. Or check the input sequence
of safety input devices.
After removing the fault, turn both safety
input 1 and 2 to the OFF state.
---
G9SX
USER'S GUIDE
Appendix
ERR
indicator
87
1. Troubleshooting
G9SX-GS226-@
ERR
indicator
Other
indicator
---
Blinks
T1 blinks
T2 blinks
T6 blinks
Fault
Fault due to electro- (1) Affected by excessive electromagnetic
disturbance.
magnetic disturbance
or of internal circuits (2) Failure of the G9SX internal circuit.
Fault involved with
safety input A,
channel 1
Fault involved with
safety input A,
channel 2
Fault involved with
safety input B,
channel 1
Lights
Appendix
T7 blinks
FB blinks
Fault involved with
safety input B,
channel 1
G9SX
USER'S GUIDE
Check points and measures to take
Page
(1) Check the disturbance level around the
G9SX and the related system.
---
(2) Replace the G9SX.
---
(1) Incorrect wiring of safety input A
channel 1. (For example, cross fault
detection mode settings and safety
input wiring do not match.)
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input A channel 1 and
24 V or another I/O terminal short
circuited.
(2) Check the wiring to T11 and T12.
---
(3) Short circuit between safety inputs
(when cross fault detection mode is
ON).
(3) Check the wiring to T11, T12, T21 and
T22.
63
(4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX.
---
(1) Incorrect wiring of safety input A
channel 2. (For example, cross fault
detection mode settings and safety
input wiring do not match.)
(1) Check the wiring to T11, T12, T21, T22
and Y1.
63
(2) Wiring to safety input A channel 2 and
24 V or another I/O terminal short
circuited.
(2) Check the wiring to T21 and T22.
---
(3) Check the wiring to T11, T12, T21 and
(3) Short circuit between safety inputs
(when cross fault detection mode is ON).
T22.
63
(4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX.
---
(1) Incorrect wiring of safety input B
channel 1. (For example, cross fault
detection mode settings and safety
input wiring do not match.)
(1) Check the wiring to T61, T62, T71, T72
and Y2.
63
(2) Wiring to safety input B channel 1 and
24 V or another I/O terminal short
circuited.
(2) Check the wiring to T61 and T62.
---
(3) Check the wiring to T61, T62, T71 and
(3) Short circuit between safety inputs
(when cross fault detection mode is ON).
T72.
63
(4) Failure in internal circuit for T61 and T62. (4) Replace the G9SX.
---
(1) Incorrect wiring of safety input B
channel 2. (For example, cross fault
detection mode settings and safety
input wiring do not match.)
(1) Check the wiring to T61, T62, T71, T72
and Y2.
63
(2) Wiring to safety input B channel 2 and
24 V or another I/O terminal short
circuited.
(2) Check the wiring to T71 and T72.
---
(3) Short circuit between safety inputs
(3) Check the wiring to T61, T16, T71 and
(when cross fault detection mode is ON).
T72.
63
(4) Failure in internal circuit for T71 and T72. (4) Replace the G9SX.
---
Fault involved with
feedback/reset
inputs
(1) Incorrect feedback/reset input wiring.
(1) Check the wiring to T31, T32, and T33.
62
Fault in Expansion
Unit
(2) Connecting cable to Expansion Unit or
terminating connector disconnected.
(2) Check the connecting cable to the
Expansion Unit and the connection of
the terminating connector.
69
(3) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(3) Change to a power supply with a
greater current capacity.
---
(4) Supply voltage outside the rated value.
(4) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(5) Failure in internal circuit for T31, T32
and T33.
(5) Replace the G9SX.
---
(6) Expansion Unit relay contact or internal
circuit failed.
(6) Replace the Expansion Unit.
---
Abnormal supply
voltage to
Expansion Unit
Failure in internal
circuit
88
Expected causes of the fault
1. Troubleshooting
ERR
indicator
Other
indicator
Fault
Expected causes of the fault
(1) Instantaneous safety outputs short
circuited.
Fault involved with
instantaneous safety (2) Instantaneous safety outputs and 24 V,
outputs
0 V, or another I/O terminal short
circuited.
EI blinks
Page
(1) Check the wiring to S14 and S24.
---
(2) Check the wiring to S14 and S24.
---
Fault involved with
logical AND
connection outputs
(3) Logical AND connection outputs and
24 V, 0 V, or another I/O terminal short
circuited.
(3) Check the wiring to L1.
---
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
78
(5) Failure in internal circuit for S14 and
S24.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for L1.
(6) Replace the G9SX.
---
(1) Safety OFF-delayed outputs short
circuited.
(1) Check the wiring to S44 and S54.
---
(2) Wiring to the OFF-delayed safety
contact outputs and 24 V, 0 V, or
another I/O terminal short circuited.
(2) Check the wiring to S44 and S54.
---
Incorrect set values
for OFF-delay time
(3) Settings of two OFF-delay time preset
switches are not the same.
(3) Confirm the set values of the OFFdelay time preset switches on the front
and back of the Unit.
65
Abnormal ambient
temperature
(4) The environment exceeds the
permissible ambient operating
temperature.
(4) Check the ambient temperature and
spacing around the G9SX.
78
(5) Failure in internal circuit for S44 and
S54.
(5) Replace the G9SX.
---
(6) OFF-delay time preset switch failed.
(6) Replace the G9SX.
---
Failure in internal
circuit
Fault involved with
OFF-delayed safety
outputs
ED blinks
Failure in internal
circuit
Lights
Fault involved with
logical AND
connection input
(1) Logical AND connection input and 24 V,
0 V, or another I/O terminal short
(1) Check the wiring to T41.
circuited.
---
(2) Make sure that the wiring length for the
T41 and T42 terminals is less than 100 m.
---
(3) Maximum number of connected Units
exceeded.
(3) Check the logical AND connection for
the G9SX.
59
(4) The logical AND connection preset
switch is set to OFF.
(4) When using a logical AND connection,
set the logical AND connection preset
switch to AND.
57
(5) Failure in internal circuit for T41 and
T42.
(5) Replace the G9SX.
---
(6) The logical AND connection preset
switch failed.
(6) Replace the G9SX.
---
(1) Wiring to the external indicator output
and 24 V, 0 V, or another I/O terminal
short circuited.
(1) Check the wiring to UA.
---
(2) External indicator output disconnected.
(external indicator not connected)
(2) Check the wiring to UA.
68
Failure of the
external indicator
(3) External indicator failed.
(3) Replace the connected external
indicator.
---
Fault in the external
indicator diagnosis
switching input
(4) Wiring for external indicator diagnosis
switching input and 24 V disconnected.
(when external indicator was not
connected)
(4) Check the wiring to Y3.
68
(5) Failure in internal circuit for UA.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for Y3.
(6) Replace the G9SX.
---
Fault in internal
circuit
Fault in external
indicator output
Failure in internal
circuit
G9SX
USER'S GUIDE
Appendix
(2) Maximum cable length exceeded.
Incorrect setting for
AND blinks logical AND
connection setting
switch
UA blinks
Check points and measures to take
89
1. Troubleshooting
ERR
indicator
Other
indicator
Fault
Page
(1) Check the wiring to UB.
---
(2) External indicator output disconnected.
(external indicator not connected)
(2) Check the wiring to UB.
68
Failure of the
external indicator
(3) External indicator failed.
(3) Replace the external indicator.
---
Fault in the external
indicator diagnosis
switching input
(4) Wiring for external indicator diagnosis
switching input and 24 V disconnected.
(when external indicator was not
connected)
(4) Check the wiring to Y4.
68
Failure in internal
circuit
Fault involved with
the Switching
Function
Lights
Check points and measures to take
(1) Wiring to the external indicator output
and 24 V, 0 V, or another I/O terminal
short circuited.
Fault in external
indicator output
UB blinks
Expected causes of the fault
UA and UB
alternately
blink
Mode selector error
Failure in internal
circuit
Supply voltage
All indicators outside the rated
except PWR value
blink
(5) Failure in internal circuit for UB.
(5) Replace the G9SX.
---
(6) Failure in internal circuit for Y4.
(6) Replace the G9SX.
---
(1) Incorrect setting of the Switching
Function setting switch or incorrect
wiring to the mode selector input.
(1) Check the wiring to the M1 and M2, and
the setting of the Switching Function
setting switch.
67
(2) Wiring to the mode selector input and
24 V, 0 V, or another I/O terminal short
circuited.
(2) Check the wiring to M1 and M2.
67
(3) Incorrect mode selector input switching
time.
(3) Check the mode selector input
switching time.
78
(4) Mode selector failed.
(4) Replace mode switch.
---
(5) Internal circuit of the mode selector
input failed.
(5) Replace the G9SX.
---
(1) Supply voltage outside the rated value.
(1) Connect to a supply voltage of 24 VDC
-15% to +10%.
---
(2) Voltage fluctuation caused by
insufficient supply voltage current
capacity.
(2) Change to a power supply with a
greater current capacity.
---
When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table.
ERR
indicator
Other
indicator
Fault
Check points and measures to take
Page
Safety input A
mismatch
The input status between safety input A
channel 1 and safety input A channel 2 is
different due to contact failure or a short
circuit of safety input device or a wiring
fault.
Check the wiring from safety input devices
to the G9SX-GS@. Or check the input
sequence of safety input devices.
After removing the fault, turn both safety
input A channels 1 and 2 to the OFF state.
---
Safety input B
mismatch
The input status between safety input B
channel 1 and safety input B channel 2 is
different due to contact failure or a short
circuit of safety input device or a wiring
fault.
Check the wiring from safety input devices
to the G9SX-GS@. Or check the input
sequence of safety input devices.
After removing the fault, turn both safety
input B channels 1 and 2 to the OFF state.
---
Check points and measures to take
Page
T1
Appendix
T2
Off
Blinks
T6
T7
Expected causes of the fault
G9SX-EX401-@/G9SX-EX041-T-@
ERR
indicator
Other
indicator
---
Lights
90
G9SX
USER'S GUIDE
Fault
Failure of the
Expansion Unit
Expected causes of the fault
Internal safety relay contact is welded.
Replace the G9SX-EX@.
---
Internal circuit failed.
Replace the G9SX-EX@.
---
2. Logical AND Connections
The logical AND connection is used to build logic between multiple safety inputs and safety outputs. This technology
is unique to the G9SX Series.
■ Logical AND Connection Signals
Pulse signals are used in the G9SX logical AND connection and dynamic processing is used to monitor the signals.
Information on safety between Units is passed by these pulse signals, which are also used to detect faults in the
connection and short circuits.
24 VDC
24 VDC
G9SX
G9SX
A1
A1
Internal
circuit
A2
Internal
circuit
L1
Logical AND connection signal
A2
T41
T42
For this reason, up to safety category 4 can be achieved without redundant logical AND connection signal lines.
■ Insulation
The logical AND connection input section of the G9SX is insulated. Therefore, even when the G9SX logical AND
connection cable is configured across multiple devices, it is not necessary to use a shared power source.
Device A
Power
supply A
Appendix
Unit A
Device B
Power
supply B
Unit B
Logical AND connection
Insulation
provided
here.
G9SX
USER'S GUIDE
91
2. Logical AND Connections
■ Simplifying Safety Circuits
Safety circuits were traditionally built by combining relay contacts, but now the logical AND connections of the G9SX
simplify building safety circuits.
A safety system will be described in which the power is turned ON when safety input 1 and safety input 2 are
simultaneously input.
Previous Circuit with Relay Units
Safety Input 1
Safety Input 2
(1)
Internal
circuit
Unit 1
Feedback
Input
Internal
circuit
Unit 2
Feedback
Input
Motor controller
KM1
KM2
M
Robot
Safety Circuit with G9SX
Safety Input 1
Appendix
Unit 1
Safety Input 2
Internal
circuit
Logical AND
connection
Internal
circuit
Unit 2
Feedback
Input
Section (1) in the above figure can
be constructed with only 2 wires.
Motor controller
KM1
KM2
M
Robot
92
G9SX
USER'S GUIDE
3. Accessories and Related Products
3. Accessories and Related Products
Accessories: Terminal Blocks
Appearance
(See note 1.)
Specifications
Applicable Units
Terminal Block with
screw terminals (3-pin)
G9SX-AD-@-RT
G9SX-ADA-@-RT
G9SX-NSA-@-RT
Terminal Block with
screw terminals (4-pin)
G9SX-BC-@-RT
G9SX-EX-@-RT
G9SX-NS-@-RT
G9SX-GS-@-RT
Terminal Block with
Spring-cage Terminals
(3-pin)
G9SX-AD-@-RC
G9SX-ADA-@-RC
G9SX-NSA-@-RC
Terminal Block with
Spring-cage Terminals
(4-pin)
G9SX-BC-@-RC
G9SX-EX-@-RC
G9SX-NS-@-RC
G9SX-GS-@-RC
Model
Remarks
Y9S-03T1B-02A
Set including two terminal blocks
(black) with screw terminals and
six code marks to prevent
incorrect insertion.
Y9S-04T1B-02A
Set including two terminal blocks
(black) with screw terminals and
six code marks to prevent
incorrect insertion.
Y9S-03C1B-02A
Set including two terminal blocks
(black) with spring-cage terminals
and six code marks to prevent
incorrect insertion.
Y9S-04C1B-02A
Set including two terminal blocks
(black) with spring-cage terminals
and six code marks to prevent
incorrect insertion.
Note: 1. The illustrations show 3-pin models.
2. The G9SX comes with the terminal blocks attached. The accessories shown here can be ordered as replacements.
Related Products
Name
Compact Safety
Door Switch
Compact Safety
Limit Switch
Compact Noncontact Door
Switch/
Flexible Safety
Unit
Certified
Body
Safety
Category
D4NS
• Lineup includes models with 3 contacts (DPST-NC +
SPST-NO and TPST-NC models) in addition to the
previous DPST-NC + SPST-NO and DPST-NC models.
• Models with M12 connectors are available to save
labor and simplify replacement work.
• Standard-feature gold-clad contacts provide high
contact reliability.
Can be used with both standard loads and microloads.
4
D4NL
• Built-in switches with four- or five-terminal contact
construction are available.
• Key holding force of 1,300 N minimum.
• Can be used for either standard loads or microloads.
• Lineup includes models with a conduit size of M20.
• IP67 degree of protection.
4
D4N
• Lineup includes models with 3 contacts (DPST-NC +
SPST-NO and TPST-NC models) in addition to the
previous DPST-NC + SPST-NO and DPST-NC models.
• Models with M12 connectors are available to save
labor and simplify replacement work.
• Standard-feature gold-clad contacts provide high
contact reliability.
Can be used with both standard loads and microloads.
4
D40A/
G9SX-NS
• Stable operation reduces Controller errors caused
by unstable doors.
• Connect up to 30 Non-contact Door Switches with LED
indicators to one Controller.
• Reversible switch provides flexibility in installation.
• Two-color LED indicator enables easier
maintenance by providing identification of door
status and cable disconnections.
• Both Non-contact Door Switches and conventional
Key-type Safety-door Switches can be input to one
Controller, saving space.
3
(EN954-1)
SIL3
(IEC/EN
61508)
Appearance
G9SX
USER'S GUIDE
Appendix
Compact Guard
Lock Safety Door
Switch
Features
Model
93
3. Accessories and Related Products
Name
Safety Light
Curtain
Emergency Stop
Switch
Emergency Stop
Switch
Appearance
Features
Safety
Category
F3SJ
Ver.2
4
A165E
• Same length as the 16-dia. Short-body A3B Switch and
allows mounting or dismounting of the Switch Unit.
• Operational Unit design remains the same as
previous models.
• Large terminals for easy wiring.
• Switch Unit can be easily mounted or dismounted
using a special tool.
4
A22E
• Easy mounting or dismounting of the Switch Unit
from the Operational Unit using a lever (provided).
• Not only round or forked crimp terminals, but also
solid wires can be connected to the Switch.
• Safety lock mechanism provided for the first time for
22-dia. models.
• Applicable to 22.3-dia. or 25-dia. panel cutouts.
IP65 degree of protection. (However, also use
A22Z-R25 for 25-dia. cutout)
• Employs a three-tier terminal block (for lighted
model) for easy wiring in narrow spaces.
4
• Sure click feel to ensure operation.
• Easy configuration of safety circuits when combined
with the G9SX-GS.
4
• For changing modes when using the manual
switching function of the G9SX-GS.
• Direct opening mechanism (NC contacts only).
---
A4EG
Key-type Selector
Switch
A22K
G9SX
USER'S GUIDE
Certified
Body
• Conforms to EN and IEC standards and
incorporates the highest level of safety design.
• Can be front-mounted, top-mounted, or backmounted in series.
• Finger, hand, or hand to body protection.
• Sensing width of 245 to 2,500 mm.
Enabling Grip
Switch
Appendix
94
Model
Scheduled
for release
in autumn
of 2007.
Precautions
Precautions
G9SX
USER'S GUIDE
95
Safety Precautions
!WARNING
<Precautions for All G9SX Models>
Serious injury may possibly occur due to breakdown
of safety outputs.
Do not connect loads beyond the rated value to the
safety outputs.
Serious injury may possibly occur due to loss of
required safety functions.
Wire G9SX properly so that supply voltages or
voltages for loads do NOT touch the safety inputs
accidentally or unintentionally.
Serious injury may possibly occur due to damages of
safety inputs.
Apply protection circuitry against back electromotive
force in case connecting inductive loads to safety
outputs.
Serious injury may possibly occur due to loss of
safety functions. Use devices appropriate for the
application and the condition where G9SX is used.
Control Devices
Serious injury may possibly occur due to loss of
safety functions. Construct an appropriate safety
system as shown in the following table.
Switching
function
Emergency Stop Switches
Door interlocking switches or
limit switches.
Use approved devices with Direct Opening
Mechanism complying with IEC/EN 609475-1 and capable of switching micro loads of
24VDC, 5mA.
Safety Sensors
Use approved devices complying with the
relevant product standards, regulations and
rules in the country where it is used.
Consult a certification body to assess that
the entire system satisfies the required
safety category level.
Precautions
Relays with forcibly guided
contacts
Use approved devices with forcibly guided
contacts complying with EN 50205.
For feedback purpose use devices with
contacts capable of switching micro loads
of 24VDC, 5mA.
Contactors
Use contactors with forcibly guided
mechanism to input the signal to Feedback/
Reset input of G9SX through the NC
contact of the contactor.
For feedback purpose use devices with
contacts capable of switching micro loads
of 24VDC, 5mA.
Failure to open contacts of a contactor
cannot be detected by monitoring its
auxiliary NC contact without forcibly guided
mechanism.
Safety system
configuration
example
G9SX
USER'S GUIDE
Safety Sensor A
Area A
Safety Sensor B
Person
Safety
precautions
(1) Select Safety Sensors that satisfy the following
condition:
1. Diameter of the smallest detectable object <
Diameter of the object to be detected.
(2) Install the Safety Sensors so that they satisfy the
following conditions:
1. Use Safety Sensor A to detect the entry of the
machine into area A, and Safety Sensor B to detect
the entry of a person into area A.
2. Make sure that the machine can reach area A only
by passing through Safety Sensor A, and that a
person can reach area A only by passing through
Safety Sensor B.
(3) Provide a protective structure to prevent a person from
passing completely through Safety Sensor B and
stepping into area A. If this is not possible, install a
sensor that will detect the presence of a person inside
area A and prevent the machine from being restarted
while the person is inside area A.
(4) Provide a sufficient safety distance (S1) considering
the entry speed of a person and a sufficient safety
distance (S2) considering the entry speed of the
machine. For details, refer to Safety Distance on
page 97.
Switching
function
Manual switching
Machine
Safety system
configuration
example
Safety Sensor
Area A
Mode
selector
Safety Door Switch
Safety Limit Switch
Person
Evaluate whether devices used are
appropriate to satisfy the requirements of
safety category level.
Safety
precautions
96
Auto switching
Machine
Requirements
Use approved devices with Direct Opening
Mechanism complying with IEC/EN 609475-1.
Do not connect an Emergency Stop Switch
to the G9SX-GS@.
Other devices
<G9SX-GS@>
(1) Select Safety Sensors that satisfy the following
condition:
1. Diameter of the smallest detectable object <
Diameter of the object to be detected.
(2) Install the Safety Sensors so that they satisfy the
following conditions:
1. Use the Safety Sensor to detect the entry of the
machine into area A.
2. Make sure that the machine can reach area A only
by passing through the Safety Sensor.
(3) Provide a protective structure to prevent a person from
stepping into area A when the door is opened. If this is
not possible, install a sensor that will detect the
presence of a person inside area A and prevent the
machine from being restarted while the person is
inside area A.
(4) Provide a sufficient safety distance (S2) considering
the entry speed of the machine. For details, refer to
Safety Distance on page 97.
(5) Position the mode selector in a location where it
cannot be operated from inside area A.
Safety Precautions
Safety Distance
The safety distance is the minimum distance that must be
provided between the safety input device and a machine's
hazardous part to stop the hazardous part before a person or
object reaches it. The safety distance varies according to the
standards of each country and the specifications of each machine.
In addition, the calculation of the safety distance differs if the
direction of approach is not perpendicular to the detection zone of
the safety input device. Always refer to the relevant standards.
Safety Distance Concepts
( 1 ) To determine the approach speed K1, consider all factors,
including the operator's physical abilities.
( 2 ) To determine the maximum approach speed K2, consult
with a notified body or other authoritative institutes.
( 3 ) The response time of a machine is the time from when the
machine receives a stop signal to the time when the
machine's hazardous part stops. Measure the response
time on the actual system. Also, periodically check that the
machine's response time has not changed.
( 4 ) For information on the response time of the G9SX system,
refer to item 10 of Precautions for Correct Use on page 98.
■ Precautions for Safe Use
Machine
<Precautions for All G9SX Models>
Safety Sensor A
P1
When a person
approaches a
hazard (machine)
Area A
S1
Safety Sensor B
Person
• S1: Safety distance 1
• P1: The closest that a machine can come to a person
while operating (the boundary of the machine's
operating area)
Machine
Safety Sensor A
When a hazard
(machine)
approaches a
person
S2
Area A
P2
Safety Sensor B
Person
• S2: Safety distance 2
• P2: The closest that a part of a person can come to a
machine.
Safety Distance Calculation Examples (Reference)
S1:
S2:
K1:
K2:
T:
C:
Safety distance 1
Safety distance 2
Approach speed of a person to the detection
zone (area A)
Maximum approach speed of a machine to the
detection zone (area A)
Total response time of the machine and G9SX
system
Additional distance calculated by the detection
capability (the diameter of the smallest
detectable object) of the Safety Sensor.
If a person approaches the detection zone
perpendicularly, calculate the safety distance as
shown below.
S1 = K1 × (Ts + Tc + Tr + Tbm) + Dpf
S2 = K2 × (Ts + Tc + Tr + Tbm) + Dpf
Calculating the
safety distance
specified by
American standard
ANSI B11.19
S1:
S2:
K1:
Safety distance 1
Safety distance 2
Approach speed of a person to the detection
zone (area A)
K2: Maximum approach speed of a machine to the
detection zone (area A)
Ts: Machine's stop time (s)
Tr:
Response time of the G9SX system from ON to
OFF (s)
Tc: Machine control circuit's maximum response
time required to activate its brake (s)
Tbm: Additional time (s)
Dpf: Additional distance
G9SX
USER'S GUIDE
Precautions
Calculating the
safety distance
specified by
international
standard ISO 138552002 (European
standard EN 9991999)
If a person approaches the detection zone
perpendicularly, calculate the safety distance as
shown below.
S1 = K1 × T + C
S2 = K2 × T + C
( 1 ) Use G9SX within an enclosure with IP54 protection or
higher of IEC/EN60529.
( 2 ) Incorrect wiring may lead to loss of safety function. Wire
conductors correctly and verify the operation of G9SX before
commissioning the system in which G9SX is incorporated.
( 3 ) Do not apply DC voltages exceeding the rated voltages, or
any AC voltages to the G9SX power supply input.
( 4 ) Use DC supply satisfying requirements below to prevent
electric shock.
• DC power supply with double or reinforced insulation, for
example, according to IEC/EN60950 or EN50178 or a
transformer according to IEC/EN61558.
• DC supply satisfies the requirement for class 2 circuits or
limited voltage/current circuit stated in UL 508.
( 5 ) Apply properly specified voltages to G9SX inputs.
Applying inappropriate voltages cause G9SX to fail to
perform its specified function, which leads to the loss of
safety functions or damages to G9SX.
( 6 ) Auxiliary error outputs and auxiliary monitoring outputs are
NOT safety outputs. Do not use auxiliary outputs as any
safety output.
Such incorrect use causes loss of safety function of G9SX
and its relevant system.
Also Logical AND connection outputs can only be used for
logical AND connections between G9SXs.
( 7 ) After installation of G9SX, qualified personnel should
confirm the installation, and should conduct test operations
and maintenance.
The qualified personnel should be qualified and authorized
to secure the safety on each phases of design, installation,
running, maintenance and disposal of system.
( 8 ) A person in charge, who is familiar to the machine in which G9SX
is to be installed, should conduct and verify the installation.
( 9 ) Perform daily and 6-month inspections on the G9SX.
Otherwise, the system may fail to work properly, resulting in
serious injury.
(10) Do not dismantle, repair, or modify G9SX. It may lead to
loss of its safety functions.
(11) Use only appropriate components or devices complying
with relevant safety standards corresponding to the
required level of safety categories.
Conformity to requirements of safety category is
determined as an entire system.
It is recommended to consult a certification body regarding
assessment of conformity to the required safety level.
(12) OMRON shall not be responsible for conformity with any
safety standards regarding to customer's entire system.
(13) Disconnect G9SX from power supply when wiring, to
prevent electric shock or unexpected operation.
Doing so may lead to the loss of its safety functions.
(14) Be cautious not to have your fingers caught when attaching
terminal sockets to the plugs on G9SX.
(15) Do not use in combustible gases or explosive gases.
97
Safety Precautions
<G9SX-GS@>
( 1 ) Be sure to correctly connect safety input devices to safety
input A and safety input B to ensure proper operation of the
safety functions.
( 2 ) When setting the Switching Function, be sure to consider
safety control requirements, safety level and safety
category of the entire system.
( 3 ) A qualified personnel who has a thorough understanding of
the installed machine must switch the mode selector input.
For example, a Switching Unit with Key must be used for
the mode selector, and the key must be managed and used
in such a way that the machine cannot be operated by
unauthorized persons.
( 5 ) Wiring
1. G9SX
• Wire the G9SX as described below.
<G9SX-EX@>
( 1 ) The durability of relays depend greatly on the switching
condition. Confirm the actual conditions of operation in
which the relay will be used in order to make sure of the
permissible number of switching operations.
(6)
■ Precautions for Correct Use
<Precautions for All G9SX Models>
Precautions
( 1 ) Handle with care
Do not drop G9SX to the ground or expose to excessive
vibration or mechanical shocks. G9SX may be damaged
and may not function properly.
( 2 ) Conditions of storage
Do not store in such conditions stated below.
1. In direct sunlight
2. At ambient temperatures out of the range of −10 to 55°C.
3. At relative humidity out of the range of 25% to 85% or
under such temperature change that causes
condensation.
4. In corrosive or combustible gases
5. With vibration or mechanical shocks out of the rated
values.
6. Under splashing of water, oil, chemicals
7. In the atmosphere containing dust, saline or metal
powder.
G9SX may be damaged and may not function properly.
( 3 ) Mounting
Mount G9SX to DIN track with attachments (PFP-M, not
incorporated to this product), not to drop off the track by
vibration or other force especially when the length of DIN
track is short compared to the widths of G9SX.
( 4 ) Following spacing around G9SX should be available to
apply rated current to outputs of G9SX and for enough
ventilation and wiring:
1. At least 25 mm beside side faces of the G9SX.
2. At least 50 mm above top face of G9SX and below
bottom face of G9SX.
(7)
(8)
(9)
(10)
50 mm min.
T31 T32 T33
D1 D2 X1
D3
A1
G9SX-NS202
24VDC
T31 T32 T33 Y1 M1 M2 UA UB
T11 T12 T61 T62 Y2 Y3 Y4 A1
13
G9SX-GS226-T15
G9SX-EX401-T
24VDC
24VDC
PWR
PWB
T1
FB
AND
NS
EI
ERR
T6
EI
1.5 2
3
0.7 1
4
0.6
5
0.5
7
0.4
10
0.3
0.2 0 15
OFF-DELAY
No.
T41 T42
S14 S24
25 mm min.
X2
L1
A2
D4
FB
AND
UA
T2
UB
T7
23
33
43
13
33
43
PWR
ED
ED
ERR
ED
23
G9SX-EX401-T
24VDC
PWR
ERR
ERR
No.
T21 T22 T71 T72 T41 T42 L1 A2
X1 X2 X3 X4 S14 S24 S44 S54
No.
14
A1
24
X2
34
No.
A2
44
14
A1
24
X2
34
A2
44
25 mm min.
50 mm min.
(11)
98
G9SX
USER'S GUIDE
Solid wire
0.2 to 2.5 mm2 (AWG24 to AWG12)
Stranded wire
0.2 to 2.5 mm2 (AWG24 to AWG12)
• Strip no more than 7 mm of insulation from the end of
the wire.
• It is recommended that stranded wire be covered with
insulated 0.25- to 2.5-mm2 ferrules before connecting it.
2. G9SX-@-RT (with Screw Terminals)
• Tighten each screw to 0.5 to 0.6 N·m or the G9SX-@RT may malfunction or generate heat.
3. Wiring for a Logical AND Connection
• Use a 2-conductor cabtire cable or shielded cable to
wire a logical AND connection between Units.
Connecting Expansion Units (G9SX-EX@-@):
(Only G9SX-AD@/-ADA@/-NSA@/-GS@)
1. Remove the termination connector from the G9SX, and
insert the connector of the Expansion Unit into the
G9SX to connect it.
2. Insert the termination connector into the last Expansion
Unit as viewed from the G9SX. When the G9SX is used
without any Expansion Units, do not remove the
termination connector from the G9SX.
3. Do not remove the termination connector while the
system is operating.
4. Before applying the power supply voltage, confirm that
the connecting sockets and plugs are locked.
5. Make sure that all connected Expansion Units are
supplied with power within 10 s after the power to the
G9SX is turned ON. Otherwise, the G9SX will detect a
power supply error for the Expansion Units.
Use cables with length less than 100m to connect to Safety
Inputs, Feed-back/Reset inputs, or between Logical AND
connection inputs and Logical AND connection outputs,
respectively.
Set the time duration of OFF-delay to an appropriate value
that does not cause the loss of safety function of system.
Logical AND connection between Units:
1. When using Logical AND connection inputs, set the
Logical AND connection preset switch to 'AND' position
for the units which the logical AND connection signal
are input to.
2. Connect Logical AND connection outputs appropriately
to Logical AND connection inputs of the relevant unit.
Verify the operation of G9SX before commissioning the
system.
3. When configuring the safety related system, be sure to
consider that the delay of response time caused by
logical AND connections do not degrade the safety
function of the system.
4. Use 2-conductor cabtire cable or shielded cable for
logical AND connections between Units.
To determine the safety distance to hazards, take into
account the delay of safety outputs caused by the following
times:
1. Response time of safety inputs
2. Response time of logical AND connection input
(Also consider the precaution in "Note" below)
3. Preset OFF-delay time
4. Accuracy of OFF-delay time
Note: When connecting multiple Units with logical AND
connections, the operating time and response time
after logical AND connection inputs will be the sum
of the operating times and response times of the
Units that are connected in series by logical AND
connections.
Start entire system after more than 5s have passed since
applying supply voltage to all G9SXs in the system.
Safety Precautions
(12) Power Supply
1. The G9SX may malfunction due to electromagnetic
disturbances. Be sure to connect terminal A2 to ground.
2. When sharing a power supply with a Safety Light
Curtain, use a power supply that will not fail for a
momentary power interruption of 20 ms or less.
(13) Devices connected to G9SX may operate unexpectedly.
When replacing G9SX, disconnect it from power supply.
(14) Adhesion of solvent such as alcohol, thinner,
trichloroethane or gasoline on the product should be
avoided. Such solvents make the marking on G9SX
illegible and cause deterioration of parts.
<G9SX-NS/-NSA, D40A>
For details, refer to D40A/G9SX-NS catalog (Cat. No. C160).
( 1 ) Connection with Non-contact Door Switch
Wire conductors between the G9SX-NS@ and the D40A
Non-contact Door Switch correctly and verify operation,
before using the system.
( 2 ) The D40A must be used with a designated actuator and
G9SX-NS@ Controller.
( 3 ) Use cables with a length of less than 100 m total to connect
D40A Switches.
(11) Check that the machine is stopped whenever the
interlocked guard door is open.
(12) Do not mount the switch and actuator on magnetic
materials, otherwise it may affect the operating distance.
Below are reference values of the effect to the operating
distance.
Distance from surface of
magnetic material
Operating distance
0 to 5 mm
Decrease to approx. 90% of
rated value.
> 5 mm
No effect
(13) Tighten all screws to the specified torque by using nonmagnetic M4 screws and washer for the installation of the
switch and actuator. After installation and using, the
actuator and switch fixing screws must be coated with
tamper proof varnish or similar compound. Using
anaerobic locking compounds can have a detrimental
effect on the plastic switch case if the compounds come
into contact with the switch case.
Actuator
Total wiring length 100 m max.
D1 D2 D3 D4
G9SX-NS202-@
G9SX-NSA222-T03-@
Switch
(14) Wiring
1. Use the following to wire to the product.
Stranded wire (flexible wire): 0.2 to 2.5 mm2 (AWG24 to
AWG12)
Solid wire (steel wire): 0.2 to 2.5 mm2 (AWG24 to
AWG12)
2. When an auxiliary output is not used, cut off the wiring
and cover it with tape so that it does not contact other
terminals.
<G9SX-GS>
( 1 ) Use a mode selector that has an SPST-NO + SPST-NC
contact form (e.g., OMRON's A22K-@-11).
Precautions
( 4 ) Disconnect the G9SX-NS@ from the power supply when
replacing the D40A. Devices connected to the G9SX-NS@
may operate unexpectedly.
( 5 ) Do not use the D40A in a magnetic field of 1.5 mT or
higher. The D40A may not function properly.
( 6 ) Do not use the D40A in the water or in an environment
continuously exposed to water. Water may penetrate into
the D40A. (The IP67 degree of protection for this switch
means that it has been checked for penetration of water
after having been left in water for a fixed period of time.)
( 7 ) Be sure to mount a guard stopper and guide to prevent the
D40A Non-contact Door Switch from being subjected to
impact.
( 8 ) Do not use the switch or actuator as a stopper. Protect the
switch and the actuator by installing a stopper. Separate
the switch and the actuator to a distance of 1 mm or more.
( 9 ) Install the actuator and switch at an appropriate distance
so that they do not create a gap that provides access to the
hazard.
(10) Where two or more Switches are mounted side-by-side,
they must be no closer than 25 mm.
25 mm min.
G9SX
USER'S GUIDE
99
Safety Precautions
■ Category of EN 954-1
In the condition shown in Application Examples, G9SX can be
used for the corresponding categories up to category 4.
This does NOT mean that G9SX can always be used for required
category under all the similar conditions and situations.
Conformity to the categories must be assessed as a whole
system.
When using G9SX for safety categories, be sure to confirm the
conformity as a whole system.
To conform with Safety Category 4 (EN954-1)
When using Non-contact Door Switch D40A/G9SX-NS@, the
system can be used for the corresponding categories up to
category 3.
1. Input the signals to both of the safety inputs (T11-T12, T21-T22,
T61-T62 and T71-T72).
2. Input a signal to the safety inputs (T11-T12, T21-T22, T61-T62
and T71-T72) through switches with Direct Opening
Mechanism.
When using Limit Switches, at least one of them must have
Direct Opening Mechanism.
3. When connecting Safety sensor with G9SX, use TYPE 4
safety sensor.
4. Input the signal through a NC contact of the contactor to
Feedback/Reset input (T31-T32 for manual reset or T31-T33
for auto reset). (Refer to Application Examples)
5. Keep Cross fault detection mode input (Y1 and Y2) open.
However, when connecting devices with self-diagnosis
function, such as safety sensors, apply 24VDC to Y1 and Y2.
6. Be sure to Connect A2 to ground.
7. When using a G9SX-EX-@-@ Expansion Unit, connect fuses
with a current rating of 3.15 A max. to the safety relay outputs
to prevent the contacts from welding.
■ Compliance with International Standards
Model
G9SX-AD
G9SX-ADA
G9SX-NS
G9SX-NSA
G9SX-BC
G9SX-GS
G9SX-EX
EN50178
❍
❍
❍
❍
❍
IEC/EN60204-1
❍
❍
❍
❍
❍
EN954-1 Cat.4
❍
❍
❍
❍
❍
❍
❍
Item
❍
EN954-1 Cat.3
Approved by
TÜV Product
Service
Precautions
100
Approved by UL
IEC/EN61508 SIL3
❍
❍
IEC/EN62061 SIL3
IEC/EN61000-6-2
❍
IEC/EN61000-6-4
❍
IEC/EN60947-5-2
❍
IEC/EN60947-5-3 PDF-M
❍
❍
❍
❍
❍
❍
❍
UL508
❍
❍
❍
❍
❍
UL1998
❍
❍
❍
❍
❍
NFPA79
❍
❍
❍
❍
❍
IEC61508
❍
❍
❍
❍
❍
CAN/CSA C22.2 No.142
❍
❍
❍
❍
❍
❍
❍
❍
Approved by KOSHA
G9SX
USER'S GUIDE
❍
❍
MEMO
G9SX
USER'S GUIDE
101
MEMO
102
G9SX
USER'S GUIDE
READ AND UNDERSTAND THIS CATALOG
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any
questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other
period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES
THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF
THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR
COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT,
WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS
UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND
MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the
customer’s application or use of the product.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use
that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in
combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list
of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this
document.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines,
vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING
THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be
assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at
any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for
clerical, typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It
may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual
performance is subject to the OMRON Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
Copyright and Copy Permission
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission.
This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or
reproducing this document in any manner, for any other purpose. If copying or transmitting this document to another, please copy or
transmit it in its entirety.
OMRON Corporation
Industrial Automation Company
OMRON SCIENTIFIC TECHNOLOGIES INC.
6550 Dumbarton Circle, Fremont
CA 94555-3605 U.S.A.
Tel: (1) 510-608-3400/Fax: (1) 510-744-1442
Authorized Distributor:
Safety Devices Division
Shiokoji Horikawa, Shimogyo-ku,
OMRON ASIA PACIFIC PTE. LTD.
Kyoto, 600-8530 Japan
Tel: (81) 75-344-7093/Fax: (81) 75-344-8197 No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
Regional Headquarters
OMRON (CHINA) CO., LTD.
OMRON EUROPE B.V.
Room 2211, Bank of China Tower,
Wegalaan 67-69, NL-2132 JD Hoofddorp
200 Yin Cheng Zhong Road,
The Netherlands
Pu Dong New Area, Shanghai, 200120, China
Tel: (31)2356-81-300/Fax: (31)2356-81-388
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
Note: Specifications subject to change without notice.
Cat. No. Z255-E1-01
Printed in Japan
0807-0.3M (0307) (M)