Download USER'S GUIDE
Transcript
G9SX USER'S GUIDE G9SX G9SX-NS G9SX-GS Flexible Safety Unit Non-Contact Door Switch Controller Safety Guard Switching Unit Cat.No. Z255-E1-01 Introduction This User’s Guide describes the usage of the G9SX Series-Flexible Safety Units mainly through application examples. Humans make mistakes and machines fail. Therefore it is necessary to design machines and equipment based on the assumption that humans will make mistakes and machines will fail. Thus, a circuit configuration is required to ensure safety, even when an onsite operator makes a mistake in machine operation or when a part of the machine fails. Flexible Safety Units, which enable various safety circuit patterns to be configured only by simple wiring, provide the core components of such safety circuits. Use the OMRON Flexible Safety Units in your machine and equipment to improve the safety designs and onsite worker safety measures. Outline of this User’s Guide Section 1 Section 2 Section 3 Section 4 Appendix 2 G9SX USER'S GUIDE Application Examples Introduces applications that can be configured with the G9SX. Functions of G9SX Describes the functions of each unit of G9SX Series. Wiring and Setup Describes the wiring and settings required for use. Ratings and Specifications Provides specifications, dimensions and terminal arrangements. Describes troubleshooting, accessories, and related products. Ordering Information ■ List of Models Advanced Unit Safety outputs (solid state) (See note 3.) Auxiliary outputs Logical AND connection Max. OFFNo. of input (solid state) delay time channels OFF-delayed (See note 4.) (See note 1.) Instantaneous Inputs Outputs (See note 2.) 3 (Semiconductor) 15 s 1 1 (Semiconductor) (Semiconductor) 2 2 (Semiconductor) (Semiconductor) 150 s 1 or 2 channels 24 VDC 15 s 2 2 (Semiconductor) (Semiconductor) 2 (Semiconductor) Rated voltage 150 s Terminal block type Model Screw terminals G9SX-AD322-T15-RT Spring-cage terminals G9SX-AD322-T15-RC Screw terminals G9SX-AD322-T150-RT Spring-cage terminals G9SX-AD322-T150-RC Screw terminals G9SX-ADA222-T15-RT Spring-cage terminals G9SX-ADA222-T15-RC Screw terminals G9SX-ADA222-T150-RT Spring-cage terminals G9SX-ADA222-T150-RC Note: 1. The OFF-delay time can be set in 16 steps as follows: T15: 0/0.2/0.3/0.4/0.5/0.6/0.7/1/1.5/2/3/4/5/7/10/15 s T150: 0/10/20/30/40/50/60/70/80/90/100/110/120/130/140/150 s 2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s. 3. P channel MOS FET transistor output 4. PNP transistor output Basic Unit Safety outputs (solid state) (See note 1.) Instantaneous OFF-delayed 2 (Semiconductor) --- Logical AND connection Auxiliary outputs (solid state) (See note 2.) Inputs Outputs 0 2 2 (Semiconductor) No. of input channels Rated voltage 1 or 2 channels 24 VDC Terminal block type Model Screw terminals G9SX-BC202-RT Spring-cage terminals G9SX-BC202-RC Note: 1. P channel MOS FET transistor output 2. PNP transistor output Non-Contact Door Switch Controller (Controllers for D40A) Safety outputs (See note.1) Instantaneous 2 (Semiconductor) Note: 1. 2. 3. 4. OFF-delayed (See note 2.) 0 2 (Semiconductor) Auxiliary outputs (See note 3.) Logical AND Logical AND Max. OFFconnection connection delay time input output (See note 4.) 2 (Semiconductor) Rated voltage --1 1 24 VDC 3.0 s Terminal block type Model Screw terminals G9SX-NS202-RT Spring-cage terminals G9SX-NS202-RC Screw terminals G9SX-NSA222-T03-RT Spring-cage terminals G9SX-NSA222-T03-RC P channel MOS FET transistor output The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s. PNP transistor output The OFF-delay time can be set in 16 steps as follows: 0/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1.0/1.2/1.4/1.8/2.0/2.5/3.0 s Safety Guard Switching Unit Safety outputs (See note 3.) Instantaneous OFF-delayed (See note 2.) Auxiliary outputs (See note 4.) Logical AND connection Inputs Max. OFFRated delay time voltage (See note 1.) Outputs 2 (semiconductor) 2 (semiconductor) 6 (semiconductor) 1 (semiconductor) 1 (semiconductor) 15 s 24 VDC Terminal block type Model Screw terminals G9SX-GS226-T15-RT Spring-cage terminals G9SX-GS226-T15-RC Note: 1. The OFF-delay time can be set in 16 steps as follows: T15: 0/0.2/0.3/0.4/0.5/0.6/0.7/1/1.5/2/3/4/5/7/10/15 s 2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s. 3. P channel MOS FET transistor output 4. PNP transistor output (except for the external indicator outputs, which are P channel MOS FET transistor outputs) Expansion Unit Safety outputs Instantaneous OFF-delayed 4 PST-NO (contact) --- Auxiliary outputs (See note 1.) OFF-delay time 4 PST-NO (contact) 24 VDC (See note 2.) Terminal block type Screw terminals --1 (semiconductor) --- Rated voltage Model G9SX-EX401-RT Spring-cage terminals G9SX-EX401-RC Screw terminals G9SX-EX041-T-RT Spring-cage terminals G9SX-EX041-T-RC Note: 1. PNP transistor output 2. The OFF-delay time is synchronized to the OFF-delay time setting in the connected Unit (G9SX-AD-@, G9SX-ADA-@, G9SX-NSA@ and G9SX-GS-@). G9SX USER'S GUIDE 3 Model Number Structure ■ Model Number Legend G9SX - @@@@@@ - @@@ - @@ 1 2 3 4 5 6 1. Functions AD/ADA :Advanced Unit Advanced Unit BC :Basic Unit T15 : 15 s GS :Safety Guard Switching Unit T150 : 150 s NS/NSA :D40A Controller EX :Expansion Unit 2. Output Configuration (Instantaneous Safety Outputs) 0 : None 2 : 2 outputs 3 : 3 outputs 4 : 4 outputs 3. Output Configuration (OFF-delayed Safety Outputs) 0 : None 2 : 2 outputs 4 : 4 outputs 4. Output Configuration (Auxiliary Outputs) 1 : 1 output 2 : 2 outputs 6 : 6 outputs 4 5. Max. OFF-delay Time G9SX USER'S GUIDE Basic Unit No indicator : No OFF delay Safety Guard Switching Unit T15 : 15 s D40A Controller T03 : 3 s Expansion Unit No indicator : No OFF delay T : OFF delay 6. Terminal Block Type RT : Screw terminals RC : Spring-cage terminals CONTENTS Section 1 Application Examples 1. Partial control of machine 1-1 Parts Processing Machine 7 8 Section 2 Functions of G9SX 37 1. Function list of G9SX-series 38 2. Functions of each Unit 39 8 1-2 Machining Center 11 1-3 Semiconductor Manufacturing Equipment 15 2-1 Basic Unit 39 1-4 Machine Tool 17 2-2 Advanced Unit 40 2-3 Non-Contact Door Switch Controller 42 20 2-4 Safety Guard Switching Unit 44 2-1 Pick and Place Machine 20 2-5 Expansion Unit 48 2-2 Small Assembly System 22 2. Using Non-contact Door Switch 3. Coordinated operation of worker and machine 3-1 Manufacturing Automotive Parts Using Semi-automatic Processing 4. Safety Measures for limited operations 25 25 28 4-1 Manufacturing Flat-panel Displays (Maintenance) 28 4-2 Machining Center (Enabling Switch) 31 4-3 LCD Manufacturing (Guard Lock Control) 34 G9SX USER'S GUIDE 5 CONTENTS Section 3 Wiring and Setup 1. I/O Terminals 51 52 Section 4 Ratings and Specifications 1. Ratings 72 1-1 Basic Unit 52 1-1 Advanced Unit/Basic Unit 72 1-2 Advanced Unit 53 1-2 Non-contact Door Switch Controller 73 1-3 Non-contact Door Switch Controller 54 1-3 Safety Guard Switching Unit 74 1-4 Safety Guard Switching Unit 55 1-4 Expansion Unit 75 1-5 Expansion Unit 56 2. Characteristics 2. Functions, Wiring and Settings 57 76 2-1 Advanced Unit/Basic Unit 76 2-2 Non-contact Door Switch Controller 77 2-3 Safety Guard Switching Unit 78 2-4 Expansion Unit 79 2-1 Logical AND Connection 57 2-2 Response Time and Operation Time 60 2-3 Reset Mode 62 2-4 Cross Fault Detection 63 2-5 Connecting Safety Sensors and the G9SX 64 2-6 OFF-delay Time 65 3-1 Advanced Unit 80 2-7 Non-contact Door Switch 66 3-2 Basic Unit 80 2-8 Switching Mode 67 3-3 Non-contact Door Switch Controller 81 2-9 External Indicator Fault Diagnosis 68 3-4 Safety Guard Switching Unit 81 2-10 Connecting Expansion Units 69 3-5 Expansion Unit 82 2-11 Confirming Settings 70 3. Dimensions and Terminal arrangements Appendix G9SX USER'S GUIDE 80 83 1. Troubleshooting 84 2. Logical AND Connections 91 3. Accessories and Related Products 93 Precautions 6 71 95 Section 1 1 Section Application Examples Application Examples 1. Partial control of machine 8 1-1 Parts Processing Machine 8 1-2 Machining Center 11 1-3 Semiconductor Manufacturing Equipment 15 1-4 Machine Tool 17 2. Using Non-contact Door Switch 20 2-1 Pick and Place Machine 20 2-2 Small Assembly System 22 3. Coordinated operation of worker and machine 3-1 Manufacturing Automotive Parts Using Semi-automatic Processing 25 25 4. Safety Measures for limited operations 28 4-1 Manufacturing Flat-panel Displays (Maintenance) 28 4-2 Machining Center (Enabling Switch) 31 4-3 LCD Manufacturing (Guard Lock Control) 34 G9SX USER'S GUIDE 7 1. Partial control of machine 1-1 Parts Processing Machine Section The entire device stops when the Emergency Stop Switch is pressed. Only the processing section stops when the Safety Light Curtain is interrupted. 1 (2) Safety Light Curtain (1) Emergency Stop Switch Application Examples (1) Emergency Stop Switch Processing section (2) Safety Light Curtain Basic Unit G9SX-BC Logical AND connection Processing section Segment A Advanced Unit G9SX-AD Operation Example (1) The Emergency Stop Switch is pressed. (2) Safety Light Curtain is interrupted. Stop Stop Stop Stop Segment A Segment A Segment B Segment B Segment B Required Units 8 Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-AD 1 Safety Light Curtains 40 G9SX USER'S GUIDE 1. Partial control of machine ■ Wiring Example G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-AD: Auto reset, Cross fault detection mode: OFF (Category 4 Wiring (with Safety Light Curtains)), 1 Logical AND connections, OFF-delay time setting Application Examples Wiring Example Feedback Loop 11 21 12 22 Section Setup (For details, refer to Section 3.) KM1 KM2 S1 KM 1 S2 +24V KM2 NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 +24V S1 : Emergency Stop Switch S2 : Reset switch KM1 to KM6 : Contactor M1 to M3 : 3-phase motor Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 PLC etc. GND Emitter F3SJ-A Receiver Feedback Loop Motor controller S34 KM3 KM3 KM5 KM 4 KM6 Control output 1 GND NC Control output 2 KM4 KM5 KM6 +24V M2 M3 +24V NC AND A1 T11 T12 T21 T22 T31 T32 T33 Y1 T41 T42 OFF G9SX-AD322-T15 +24V Control circuit A2 S14 S24 S34 S44 S54 L1 X1 X2 KM3 KM4 GND KM5 KM6 PLC etc. Motor controller (Operation command) Note: 1. This example corresponds to category 4. (when using a Type-4 Safety Sensor). 2. For further information on settings and wiring, refer to the datasheet or instruction sheet for the Safety Sensor. 3. Use Safety Sensors with PNP control outputs. G9SX USER'S GUIDE 9 1. Partial control of machine ■ Timing chart Section (2) G9SX-BC202 (upper unit) Emergency Stop Switch S1 1 Reset switch S2 Application Examples KM1, KM2 NC contact KM1, KM2 NO contact Logical AND output L1 G9SX-AD322-T15 (lower unit) (1) Logical AND input T41 Safety Light Curtain KM3, KM4 NC contact KM5, KM6 NC contact KM3, KM4 NO contact KM5, KM6 NO contact Operation command Rotation of motor OFF-delay time (1) Safety Light Curtain is interrupted: Only the lower Unit stops. (2) Emergency stop button pressed: Both the upper and lower Unit stop. 10 G9SX USER'S GUIDE OFF-delay time 1. Partial control of machine 1-2 Machining Center 1 (1) Emergency Stop Switch (2) Main door Section When the Emergency Stop Switch is pressed, the entire machine will stop. When a door is open, the corresponding part will not be activated. (4) Tool changer door (2) Main Door (3) Pallet Changer Door Guard Lock Safety Door Switch Basic Unit G9SX-BC Safety Door Switch (4) Tool Changer Door Application Examples (1) Emergency Stop Switch Safety Door Switch Logical AND connection (3) Pallet changer door Advanced Unit G9SX-AD Advanced Unit G9SX-AD Advanced Unit G9SX-AD Operation Example (1) The Emergency Stop Switch is pressed. (2) The main door is opened. Stop Stop Stop Stop Stop Stop Segment A Segment A Segment B Segment C (3) The pallet changer door is opened. Segment B Segment C Stop Stop Stop Stop Stop Stop Segment A Segment A Segment B Segment C Segment A Segment B Segment C (4) The tool changer door is opened. Segment B Segment C Required Units Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-AD 3 Guard Lock Safety Door Switch Safety Door Switches (Set of two) 40 G9SX USER'S GUIDE 11 1. Partial control of machine ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-AD (main door section): Manual reset, Cross fault detection mode: ON (Category 4 Wiring), 1 Logical AND connections, OFF-delay time setting Application Examples G9SX-AD (pallet changer, tool changer): Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, OFF-delay time setting Wiring Example Feedback Loop 11 21 12 22 KM1 KM2 S1 KM 1 S2 +24V KM2 NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 +24V Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 S1 : Emergency Stop Switch S2, S6 : Reset switch S3 : Guard Lock Safety Door Switch S4 : Safety Limit Switch S5 : Lock release switch S7, S8 : Safety Door Switch KM1 to KM8 : Contactor M1 to M4 : 3-phase motor PLC etc. GND Feedback Loop Motor controller S34 4 S8 KM7 Lock release signal KM7 Open KM8 KM8 KM3 KM4 S3 S5 M4 +24V +24V NC 41 A1 T11 T12 T21 T22 T31 T32 T33 Y1 42 11 AND T41 T42 OFF G9SX-AD322-T15 (Tool changer door) 12 Control circuit Guard Feedback Loop S4 A2 KM3 S14 S24 S34 S44 S54 L1 X1 X2 KM7 KM8 KM4 PLC etc. Stop signal S6 +24V GND +24V NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 AND T41 T42 Motor controller (Operation command) OFF G9SX-AD322-T15 (Main door) Feedback Loop Motor controller S7 Control circuit KM5 KM5 Open KM6 A2 KM6 S14 S24 S34 S44 S54 L1 X1 X2 M3 KM3 KM4 PLC etc. +24V +24V NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 GND Motor controller (Operation command) Motor controller S34 4 Control circuit KM4 A2 S14 S24 S34 S44 S54 L1 X1 X2 KM5 KM6 Note: This example corresponds to category 4. 12 G9SX USER'S GUIDE OFF G9SX-AD322-T15 (Pallet changer door) KM3 M2 AND T41 T42 GND Motor controller (Operation command) PLC etc. S34 4 1. Partial control of machine ■ Timing chart Section G9SX-BC202 (upper unit) (8) Emergency Stop Switch S1 1 Reset switch S2 Application Examples KM1, KM2 NC contact KM1, KM2 NO contact Logical AND output L1 G9SX-AD322-T15 (lower unit : Main door) Logical AND input T41 (1) (2) (3) Safety Limit Switch S4 Guard Lock Safety Door Switch S3 Lock release signal Lock release switch S5 Door can be opened. Stop signal Reset switch S6 KM3, KM4 NC contact KM3, KM4 NO contact Operation command Rotation of motor OFF-delay time OFF-delay time G9SX-AD322-T15 (lower unit : Pallet changer door) Logical AND input T41 (4) (5) Safety Door Switch S7 KM5, KM6, NC contact KM5, KM6, NO contact Operation command Rotation of motor OFF-delay time OFF-delay time G9SX-AD322-T15 (lower unit : Tool changer door) Logical AND input T41 (6) (7) Safety Door Switch S8 KM7, KM8, NC contact KM7, KM8, NO contact Operation command Rotation of motor OFF-delay time OFF-delay time (1) Before operation is started. (2) Main door is unlocked and opened, and then work is performed. (3) Restart operation after the main door is closed. (4) The pallet changer door opens and the pallet changer section stops. (5) The pallet changer door is closed and the pallet changer is reset. (6) The tool changer door opens and the tool changer section stops. (7) The tool changer door is closed and the tool changer section is reset. (8) If the Emergency Stop Switch is pressed, the upper unit and lower units will stop. G9SX USER'S GUIDE 13 1. Partial control of machine ■ Timing chart Section G9SX-BC202 (Unit A) (6) Emergency Stop Switch S1 Reset switch S2 1 KM1, KM2 NC contact Application Examples KM1, KM2 NO contact Logical AND output L1 G9SX-AD322-T15 (Unit B:Processing section cover) Logical AND input T41 (1) (2) (3) Safety Door Switch S3 KM3, KM4 NC contact KM3, KM4 NO contact Operation command Rotation of motor OFF-delay time OFF-delay time Logical AND output L1 G9SX-AD322-T15 (Unit C:Conveyor section cover) Logical AND input T41 (4) (5) Safety Door Switch S4 KM5, KM6, NC contact KM5, KM6, NO contact Operation command Rotation of motor OFF-delay time OFF-delay time OFF-delay time (1) Before operation is started. (2) The processing section cover is opened, and the processing section and the conveyor section stops. (3) The processing section cover is closed and the processing section and conveyor section restart. (4) The conveyor section cover is opened and the conveyor section stops. (5) The transport section cover is closed and the conveyor section restarts. (6) If the Emergency Stop Switch is pressed, unit A, unit B, and unit C will stop. 14 G9SX USER'S GUIDE 1. Partial control of machine 1-3 Semiconductor Manufacturing Equipment (2) Processing section cover (1) Emergency Stop Switch Basic Unit G9SX-BC Safety Door Switch Safety Door Switch Advanced Unit G9SX-AD Advanced Unit G9SX-AD Logical AND connection Logical AND connection (1) Emergency Stop Switch Segment A (3) Conveyor section cover Application Examples (2) Processing section cover 1 (3) Conveyor section cover Section When the Emergency Stop Switch is pressed, all of the equipment stops. When the processing section cover is opened, the processing section and conveyor section stop. When the conveyor section cover is opened, only the conveyor section stops. Segment B Segment C Operation Example (1) The Emergency Stop Switch is pressed. (2) The processing section cover is opened. Stop Stop Stop Stop Stop Segment A Segment B Segment C (3) The conveyor section cover is opened. Segment A Segment B Segment C Stop Segment A Segment B Segment C Required Units Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-AD 2 Safety Door Switches (Set of two) 40 G9SX USER'S GUIDE 15 1. Partial control of machine ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-AD: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, 1 OFF-delay time setting Application Examples Wiring Example Feedback Loop 11 21 12 22 KM1 KM2 S1 KM 1 S2 +24V KM2 NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 S1 : Emergency Stop Switch S2 : Reset switch S3, S4 : Safety Door Switch KM1 to KM6 : Contactor M1 to M3 : 3-phase motor M1 G9SX-BC202 (Unit A) +24V Control circuit A2 S14 S24 L1 L2 KM1 KM2 X1 X2 PLC etc. GND Motor controller S34 4 Feedback Loop KM3 S3 KM3 Open KM4 KM4 M2 +24V +24V NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 AND T41 T42 OFF G9SX-AD322-T15 (Unit B) Control circuit A2 S14 S24 S34 S44 S54 L1 X1 X2 KM3 KM4 GND PLC etc. Motor controller (Operation command) Motor controller Feedback Loop KM5 S4 KM5 Open KM6 KM6 M3 +24V +24V NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 G9SX-AD322-T15 (Unit C) Control circuit A2 S14 S24 S34 S44 S54 L1 X1 X2 KM5 KM6 GND Note: This example corresponds to category 4. 16 G9SX USER'S GUIDE Motor controller (Operation command) PLC etc. AND T41 T42 OFF S34 4 1. Partial control of machine 1-4 Machine Tool (2) Left door (1) Emergency Stop Switch Safety Door Switch Safety Door Switch Advanced Unit G9SX-AD Basic Unit G9SX-BC Logical AND connection (1) Emergency Stop Switch (3) Right door Application Examples (3) Right door 1 (2) Left door Section When the Emergency Stop Switch is pressed, the entire machine will stop. If the left door is opened, the left drive section and transport section will stop. If the right door is opened, the right drive section and transport section will stop. Advanced Unit G9SX-AD Segment A Segment B Logical AND connection Logical AND connection Operation Example (1) The Emergency Stop Switch is pressed. (2) The left door is opened. (3) The right door is opened. Stop Stop Stop Stop Stop Stop Segment A Segment A Segment A Segment B A Segment B Advanced Unit G9SX-ADA Segment B A Transport section Stop Stop Stop Segment C A Segment C A Segment C A Segment C Required Units Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-AD 2 Safety Door Switches (Set of two) 40 G9SX-ADA 1 --- 41 G9SX USER'S GUIDE 17 1. Partial control of machine ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-AD: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, 1 No OFF-delay time setting Application Examples G9SX-ADA: Auto reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, OFF-delay time setting Wiring Example Feedback Loop 11 21 12 22 KM1 KM2 S1 KM 1 S2 +24V KM2 NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 S1 : Emergency Stop Switch S2 : Reset switch S3, S4, S5 : Safety Door Switch KM1 to KM8 : Contactor M1 to M4 : 3-phase motor M1 G9SX-BC202 +24V Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 PLC etc. GND Feedback Loop Feedback Loop S3 S4 KM3 KM3 KM5 KM5 Open Open KM4 KM4 KM6 KM6 M2 M3 Right drive section Left drive section +24V +24V +24V NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 +24V NC AND T41 T42 A1 T11 T12 T21 T22 T31 T32 T33 Y1 OFF G9SX-AD322-T15 (Left door) G9SX-AD322-T15 (Right door) Control circuit A2 Control circuit S14 S24 S34 S44 S54 L1 X1 X2 KM3 KM4 A2 S14 S24 S34 S44 S54 L1 X1 X2 KM5 KM6 PLC etc. GND GND Feedback Loop KM1 KM2 +24V +24V NC Motor controller S34 4 A1 T11 T12 T21 T22 T31 T32 T33 Y1 AND T41 T42 G9SX-ADA222-T150 KM7 Control circuit KM8 M4 Transport section A2 S14 S24 S34 S44 S54 L1 X1 X2 KM7 KM8 Note: This example corresponds to category 4. 18 G9SX USER'S GUIDE GND AND T41 T42 Motor controller (Operation command) PLC etc. T51 T52 OFF PLC etc. OFF 1. Partial control of machine ■ Timing chart G9SX-BC202 (upper unit) Section (6) Emergency Stop Switch S1 Reset switch S2 1 KM1, KM2 NC contact Application Examples KM1, KM2 NO contact Logical AND output L1 G9SX-AD322-T15 (middle unit: Left door) Logical AND input T41 (1) (2) (3) Safety Door Switch S3 KM3, KM4 NC contact KM3, KM4 NO contact Logical AND output L1 G9SX-AD322-T15 (middle unit: Right door) Logical AND input T41 (4) (5) Safety Door Switch S4 KM5, KM6, NC contact KM5, KM6, NO contact Logical AND output L1 G9SX-ADA222-T150 (lower unit) Logical AND input T41 Logical AND input T51 KM7, KM8, NC contact KM7, KM8, NO contact Operation command Rotation of motor OFF-delay time OFF-delay time OFF-delay time (1) Before operation is started. (2) The left door is opened and the left drive section and transport section stop. (3) The left door is closed and the left drive section and transport section restart. (4) The right door is opened and the right drive section and transport section stop. (5) The right door is closed and the right drive section and transport section restart. (6) If the Emergency Stop Switch is pressed, the Upper Unit, Middle Unit, and Lower Unit will stop. G9SX USER'S GUIDE 19 2. Using Non-contact Door Switch 2-1 Pick and Place Machine Section If the Emergency Stop Switch is pressed, the entire machine will stop. If the cover is opened, the entire machine will stop. 1 Cover (2) Non-contact Door Switch Cover Application Examples (1) Emergency Stop Switch (2) Non-contact Door Switch D40A (1) Emergency Stop Switch G9SX-NSA Motor Operation Example (1) The Emergency Stop Switch is pressed. (2) Cover is opened. Stop Stop Segment Motor A Segment Motor A Required Units 20 Unit Qty. Safety input to be applied Page G9SX-NSA 1 Emergency Stop Switch + Non-contact Door Switch D40A 43 G9SX USER'S GUIDE 2. Using Non-contact Door Switch ■ Wiring Example G9SX-NSA: Manual reset, Cross fault detection mode: OFF (Category 2 Wiring), Logical AND connections: OFF, OFF-delay time setting Section Setup (For details, refer to Section 3.) 1 Application Examples Wiring Example Actuator Feedback Loop Non-contact Door Switch S2 +24V KM1 11 Motor controller KM2 S3 12 KM1 S1 KM2 blue Brown Black White +24V NC NC A1 S14 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 NC NC AND T41 T42 OFF M1 G9SX-NSA222-T03 +24V Control circuit A2 S14 S24 S44 S54 L1 X1 X2 KM1 KM2 GND PLC etc. Motor controller (Operation command) S1 : Emergency Stop Switch S2 : Non-contact Door Switch S3 : Reset switch KM1, KM2 : Contactor M1 : 3-phase motor Note: This example corresponds to category 2. ■ Timing chart Emergency Stop Switch operation Emergency Stop Switch S1 Non-contact Door Switch S2 Reset switch S3 KM1, KM2 NC contact KM1, KM2 NO contact Operation command Rotation of motor OFF-delay time OFF-delay time G9SX USER'S GUIDE 21 2. Using Non-contact Door Switch 2-2 Small Assembly System Section 1 When the Emergency Stop Switch is pressed, both robots will stop. When robot door A is opened, robot A will stop. When robot door B is opened, robot B will stop. Application Examples (1) Emergency Stop Switch (2) Robot door A (3) Robot door B D40A D40A G9SX-BC Logical AND connections (3) Robot door B (2) Robot door A (1) Emergency Stop Switch G9SX-NS G9SX-NS Operation Example (1) The Emergency Stop Switch is pressed. Stop Stop Robot A Robot B (2) Robot door A opened. Stop Stop Robot A Robot B (3) Robot door B opened. Stop Stop Robot A Robot A Robot B Robot B Required Units 22 Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-NS 2 Non-contact Door Switches D40A (Set of two) 42 G9SX USER'S GUIDE 2. Using Non-contact Door Switch ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-NS: Auto reset, Logical AND connections (Category 3 Wiring) 1 Application Examples Wiring Example Feedback Loop 11 21 12 22 KM1 KM2 S1 KM1 S2 +24V KM2 NC A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 S1 : Emergency Stop Switch S2 : Reset switch S3, S4 : Non-contact Door Switch KM1 to KM6 : Contactor M1 to M3 : 3-phase motor +24V Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 PLC etc. GND +24V Non-contact Door Switch S4 Feedback Loop Actuator Non-contact Door Switch Actuator S3 KM3 KM5 KM4 KM6 +24V +24V NC A1 D1 D2 D3 D4 T31 T32 T33 Y1 +24V NC AND T41 T42 OFF G9SX-NS202 (Robot door A) A1 D1 D2 D3 D4 T31 T32 T33 Y1 S14 S24 L1 X1 X2 KM3 KM4 PLC etc. GND AND T41 T42 OFF G9SX-NS202 (Robot door B) Control circuit A2 Feedback Loop Control circuit A2 KM3 GND KM4 S14 S24 L1 X1 X2 KM5 KM6 PLC etc. KM5 KM6 M2 M3 Note: This example corresponds to category 3. G9SX USER'S GUIDE 23 2. Using Non-contact Door Switch ■ Timing chart Section G9SX-BC202 (upper unit) (6) Emergency Stop Switch S1 Reset switch S2 1 KM1, KM2 NC contact Application Examples KM1, KM2 NO contact Logical AND output L1 Rotation of motor M1 G9SX-NS202 (lower unit : Robot A) Logical AND input T41 Non-contact Door Switch S3 (1) (2) (3) KM3, KM4 NC contact KM3, KM4 NO contact Rotation of motor M2 G9SX-NS202 (lower unit : Robot B) Logical AND input T41 (4) (5) Non-contact Door Switch S4 KM5, KM6 NC contact KM5, KM6 NO contact Rotation of motor M3 (1) Before operation is started. (2) Robot door A is opened and robot A stops. (3) Robot door A is closed and robot A restarts. (4) Robot door B is opened and robot B stops. (5) Robot door B is closed and robot B restarts. (6) If the Emergency Stop Switch is pressed, the upper unit, lower unit A, and lower unit B will all stop. 24 G9SX USER'S GUIDE 3. Coordinated operation of worker and machine 3-1 Manufacturing Automotive Parts Using Semi-automatic Processing Safety Light Curtain F3SJ Safety Light Curtain F3SJ Basic Unit G9SX-BC Application Examples (1) Emergency Stop Switch A22E (3) Safety Light Curtain B 1 (2) Safety Light Curtain A (2) Safety Light Curtain A (3) Safety Light Curtain B Section Two pairs of Light Curtains are automatically enabled and disabled according to the operations of the operator and robot. Safety Guard Switching Unit G9SX-GS Logical AND connection Contactor (1) Emergency Stop Switch Robot Emergency Stop Switch When pressed, processing will stop. Safety Light Curtain A When both are interrupted simultaneously, processing will stop. Auto switching Safety Light Curtain B Required Units Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-GS 1 Light Curtain + Light Curtain 44 G9SX USER'S GUIDE 25 3. Coordinated operation of worker and machine ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-GS: Auto reset, Cross fault detection mode: OFF (Category 4 Wiring (with Safety Light Curtains)), 1 Logical AND connections, Application Examples OFF-delay time setting Switching mode: Auto Diagnostic check of Indicator : Enabled (UB only) Wiring Example Feedback loop Emergency Stop Switch 11 21 12 22 KM1 KM2 S1 S2 KM1 S1 : Emergency Stop Switch S2 : Reset switch KM1 to KM4 : Contactor M1 to M2 : 3-phase motor +24V NC KM2 A1 T11 T12 T21 T22 T31 T32 T33 Y1 G9SX-BC202 M1 +24V Control circuit A2 L1 L2 S14 S24 KM1 KM2 X1 X2 PLC etc. GND Safety Sensor A F3SJ-A Emitter Safety Sensor B F3SJ-A Receiver Emitter Receiver NC GND +24V +24V NC A1 T11 T12 T21 T22 Y1 Y3 NC NC M1 M2 NC Control output 2 Control output 1 Control output 1 GND Control output 2 Feedback Loop KM3 KM4 +24V +24V NC NC T61 T62 T71 T72 Y2 Y4 AND T31 T32 T33 T41 T42 OFF G9SX-GS226-T15 KM3 Manual +24V Control circuit Auto KM4 M2 A2 S14 S24 S44 S54 KM3 KM4 GND Note: This example corresponds to category 4. 26 G9SX USER'S GUIDE L1 X1 X2 X3 X4 UA UB PLC etc. Indicator Indicator (Diagnostic (Diagnostic check disabled) check enabled) 3. Coordinated operation of worker and machine ■ Timing chart Section G9SX-BC202 (6) Emergency Stop Switch S1 1 Reset switch S2 KM1, KM2 NC contact Application Examples KM1, KM2 NO contact Logical AND output L1 G9SX-GS226-T15 Logical AND input T41 (3) (1) Safety Sensor A control output (monitoring the robot) (2) (4) (5) Safety Sensor B control output (monitoring the operator) KM3, KM4 NC contact KM3, KM4 NO contact Input A monitor output X3 Input B monitor output X4 External indicator output UA External indicator output UB Controls not related to safety Robot movement enabled Robot movement enabled in specific area only Robot movement disabled (1) Before operation is started. (2) Operator inserts workpiece (3) Robot processes workpiece (4) Both operator and robot enter the coordinated area: Only the G9SX-GS stops. (5) The G9SX-GS restarts. (6) Emergency stop button pressed: All units stop. G9SX USER'S GUIDE 27 4. Safety Measures for limited operations 4-1 Manufacturing Flat-panel Displays (Maintenance) Section 1 Switching between Normal Operating Mode and Maintenance Mode is performed manually. In Normal Operating Mode, the Safety Door Switch is enabled, and in Maintenance Mode the Safety Limit Switch is enabled. Application Examples (2) Cover (Safety Door Switch) (3) Conveyor cart (Safety Limit Switch) (2) Cover (1) Emergency Stop Switch A22E (3) Conveyor cart Safety Door Switch D4NS Basic Unit G9SX-BC (4) Mode selector Safety Limit Switch D4F Key-type Selector Switch A22K Safety Guard Switching Unit G9SX-GS (4) Mode selector Logical AND connection Contactor (1) Emergency Stop Switch Conveyor cart Normal operating mode Manual switching Emergency Stop Switch When pressed, processing will stop. Cover When the cover is opened, processing will stop. Conveyor cart Processing will continue regardless of the conveyor cart position. Maintenance mode Manual switching Emergency Stop Switch When pressed, processing will stop. Cover Processing will continue regardless of whether the cover is opened or closed. Conveyor cart When the conveyor cart moves away from its safe position, processing will stop. Required Units 28 Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-GS 1 Door Switch + Limit Switch 44 G9SX USER'S GUIDE 4. Safety Measures for limited operations ■ Wiring Example G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, 1 OFF-delay time setting Application Examples Switching mode: Manual Diagnostic check of Indicator: Enabled (UA only) Wiring Example Feedback loop Emergency Stop Switch 11 21 12 22 Section Setup (For details, refer to Section 3.) KM1 KM2 S1 S2 KM1 S1 : Emergency Stop Switch S2, S7 : Reset switch S3, S4 : Safety Limit Switch S5 : Safety Door Switch S6 : Selector switch KM1 to KM4 : Contactor M1 to M2 : 3-phase motor +24V NC KM2 A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 +24V Control circuit A2 S14 S24 L1 L2 KM1 KM2 X1 X2 PLC etc. 23 S3 Conveyor cart 24 S5 11 S4 21 11 22 12 Feedback loop Cover 12 +24V S6 KM3 Mode selector KM4 +24V +24V NC NC A1 T11 T12 T21 T22 Y1 Y3 NC M1 M2 AND T61 T62 T71 T72 Y2 Y4 T31 T32 T33 T41 T42 OFF G9SX-GS226-T15 KM3 Manual +24V Control circuit Auto KM4 M2 A2 S14 S24 S44 S54 KM3 KM4 GND L1 X1 X2 X3 X4 UA UB PLC etc. Indicator Indicator (Diagnostic (Diagnostic check enabled) check disabled) Note: This example corresponds to category 4. G9SX USER'S GUIDE 29 4. Safety Measures for limited operations ■ Timing chart Section G9SX-BC202 (10) Emergency Stop Switch S1 1 Reset switch S2 Application Examples KM1, KM2 NC contact KM1, KM2 NO contact Logical AND output L1 G9SX-GS226-T15 Logical AND input T41 (4) Safety Limit Switch S3 Limit Switch S4 (3) (6) Safety Door Switch (5) (1) (7) (9) Reset switch S6 (2) (8) Mode selector input M1 Mode selector input M2 KM3, KM4 NC contact KM3, KM4 NO contact Input A monitor output X3 Input B monitor output X4 External indicator output UA External indicator output UB Controls not related to safety Conveyor section movement enabled (with machine in normal operating mode) Conveyor section movement enabled in specific area only (with machine in maintenance mode) Conveyor section movement disabled (1) Start the G9SX-GS in normal operating mode. (2) Switch to maintenance mode. (3) The operator opens the door and performs maintenance. (4) When Safety Limit Switch S3 and Limit Switch S4 are turned OFF in maintenance mode, the G9SX-GS stops. (5) After the door is closed and the operating mode is switched to normal operating mode, restart the G9SX-GS. (6) When the door is opened during normal operating mode, the G9SX-GS stops. (7) Close the door and restart the G9SX-GS. (8) When the operating mode is switched to maintenance mode while Safety Limit Switch S3 and Limit Switch S4 are turned OFF, the G9SX-GS stops. (9) Switch to normal operating mode, and when the door is closed, restart the G9SX-GS. (10) Emergency stop button pressed: All units stop. 30 G9SX USER'S GUIDE 4. Safety Measures for limited operations 4-2 Machining Center (Enabling Switch) (1) Emergency Stop Switch A22E Enabling Switch Guard Lock Safety Door Switches (4) Mode selector Key-type Selector Switch A22K Application Examples (1) Emergency Stop Switch (3) Motor 1 (2) Door (2) Safety Door Switch Section Switching between Normal Operating Mode and Maintenance Mode is performed manually. In Normal Operating Mode, the Safety Door Switch is enabled, and in Maintenance Mode, the Safety Limit Switch is enabled. Basic Unit G9SX-BC Safety Guard Switching Unit G9SX-GS Logical AND connection Contactor (3) Enabling Switch Conveyor cart Normal operating mode Manual switching Emergency Stop Switch When pressed, processing will stop. Door When the door is opened, processing will stop. Enabling Device The enabling switch is disabled. Maintenance mode Manual switching Emergency Stop Switch When pressed, processing will stop. Door Door Switch is disabled. Enabling Device Processing will be possible only when the operator is gripping the enabling switch. Required Units Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-GS 1 Door Switch + Enabling Switch 44 G9SX USER'S GUIDE 31 4. Safety Measures for limited operations ■ Wiring Example Section Setup (For details, refer to Section 3.) G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, 1 OFF-delay time setting Application Examples Switching mode: Manual Diagnostic check of Indicator: Enabled Wiring Example Feedback Loop 11 21 12 22 KM1 KM2 S1 KM1 S2 +24V NC S1 : Emergency Stop Switch S2, S7 : Reset switch S3 : Enabling Switch S4 : Guard Lock Door Switch S5 : Lock release switch S6 : Safety Limit Switch KM1 to KM4 : Contactor M1 to M2 : 3-phase motor KM2 A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 +24V Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 PLC etc. GND Lock release signal KM3 KM4 S4 S5 31 32 11 12 Door S6 Feedback Loop OPEN 2 4 1 3 KM3 Enabling Switch S3 Stop sigmal +24V S7 KM4 Mode selector +24V NC NC A1 T11 T12 T21 T22 Y1 Y3 M1 M2 NC NC T61 T62 T71 T72 Y2 Y4 AND T31 T32 T33 T41 T42 OFF G9SX-GS226-T15 Manual +24V Control circuit KM3 Auto KM4 A2 S14 S24 S44 S54 KM3 KM4 GND 32 G9SX USER'S GUIDE L1 X1 X2 X3 X4 UA UB M2 PLC etc. Indicator Indicator (Diagnostic (Diagnostic check enabled) check enabled) Note: This example corresponds to category 4. 4. Safety Measures for limited operations ■ Timing chart Section G9SX-BC202 (upper unit) (10) Emergency Stop Switch S1 1 Reset switch S2 Application Examples KM1, KM2 NC contact KM1, KM2 NO contact Logical AND output L1 G9SX-GS226-T15 (lower unit) Logical AND input T41 (3) (8) Guard Lock Door Switch S4 (4) (6) Enabling Switch S3 (1) (5) (7) (9) Reset switch S7 (2) Mode selector input M1 Mode selector input M2 KM3, KM4 NC contact KM5, KM6 NC contact KM3, KM4 NO contact KM5, KM6 NO contact OFF-delay time OFF-delay time OFF-delay time OFF-delay time (1) In Normal operating mode, the lower unit starts. (2) Maintenance mode is selected. (3) The operator opens the door and performs maintenance operation. (4) The Enabling Switch is gripped to the middle position. (5) In maintenance mode, the lower unit starts. (6) When the Enabling Switch is released or gripped, the lower unit stops. (7) After closing the door and then switching to Normal operating mode, the lower unit will restart. (8) If the door is opened while in Normal operating mode, the lower unit will stop. (9) The door is closed, and the lower unit restarts. (10) If the Emergency Stop Switch is pressed, the upper unit and lower unit will stop. G9SX USER'S GUIDE 33 4. Safety Measures for limited operations 4-3 LCD Manufacturing (Guard Lock Control) Section When the Safety Limit Switch has confirmed that the hazard source is in a safe position, the Guard Lock Safety Door Switch will be unlocked. 1 (2) Guard Lock Door Switch (2) Door (3) Conveyor cart (3) Safety Limit Switch Application Examples (1) Emergency Stop Switch A22E Guard Lock Safety Door Switches Safety Limit Switch D4F Basic Unit G9SX-BC Safety Guard Switching Unit G9SX-GS Logical AND connection Contactor (1) Emergency Stop Switch Motor Emergency Stop Switch When pressed, processing will stop. Guard Lock Door Switch Auto switching When turned OFF at the same time, the machine will stop. Limit Switch Required Units 34 Unit Qty. Safety input to be applied Page G9SX-BC 1 Emergency Stop Switch 39 G9SX-GS 1 Guard Lock Door Switch + Limit Switch 44 G9SX USER'S GUIDE 4. Safety Measures for limited operations ■ Wiring Example G9SX-BC: Manual reset, Cross fault detection mode: ON (Category 4 Wiring) G9SX-GS: Manual reset, Cross fault detection mode: ON (Category 4 Wiring), Logical AND connections, 1 No OFF-delay time setting Application Examples Switching mode: Auto Diagnostic check of Indicator: Enabled (UA only) Wiring Example Feedback Loop 11 21 12 22 Section Setup (For details, refer to Section 3.) KM1 KM2 S1 S2 KM1 S1 : Emergency Stop Switch S2, S7 : Reset switch S3 : Lock release switch S4 : Guard Lock Door Switch S5, S6 : Limit Switch KM1 to KM4 : Contactor M1 to M2 : 3-phase motor +24V NC KM2 A1 T11 T12 T21 T22 T31 T32 T33 Y1 M1 G9SX-BC202 +24V Control circuit A2 S14 S24 L1 L2 X1 X2 KM1 KM2 PLC etc. GND Lock release switch Guard Lock Door Switch (Mechanical lock) S4 GND E1 E2 42 41 12 22 11 21 Feedback Loop Door Conveyor cart S5 Limit Switch Limit Switch KM3 S7 KM4 OPEN S6 Limit Switch +24V NC NC A1 T11 T12 T21 T22 Y1 Y3 +24V NC M1 M2 T61 T62 T71 T72 Y2 AND Y4 T31 T32 T33 T41 T42 OFF G9SX-GS226-T15 Manual +24V Control circuit A2 S14 S24 S44 S54 L1 X1 X2 X3 X4 Auto UA UB KM3 KM4 KM3 GND Note: This example corresponds to category 4. Indicator (Diagnostic check enabled) KM4 M2 G9SX USER'S GUIDE 35 4. Safety Measures for limited operations ■ Timing chart Section G9SX-BC202 (upper unit) (11) Emergency Stop Switch S1 1 Reset switch S2 Application Examples KM1, KM2 NC contact KM1, KM2 NO contact Logical AND output L1 G9SX-GS226-T15 (lower unit) Logical AND input T41 (1) (2) (5) (6) (7) (8) Safety Limit Switch S5 Safety Limit Switch S6 Lock release signal (External indicator output UA) (3) (4) (9) Guard Lock Door Switch S4 Lock release switch S1 Door can be opened. Door can be opened. Reset switch S7 KM3, KM4 NC contact KM3, KM4 NO contact (1) When the door is closed, operation is initiated with the reset switch. (2) The Limit Switch detects the conveyor cart and the lock release signal turns ON. (3) The door can be opened while the lock release switch pressed. (4) The door is closed again. (5) The conveyor cart moves. (6) The Limit Switch detects the conveyor cart, and the lock release signal turns ON. (7) The door can be opened while the lock release switch is pressed. (8) The conveyor cart moves while the door is open, and the lower unit stops. (9) The door is closed again. The lower unit remains stopped. (10) The reset switch is used to restart operation. (11) If the Emergency Stop Switch is pressed, the upper unit and lower unit will stop. 36 G9SX USER'S GUIDE (10) Section 2 Section Functions of G9SX 2 38 2. Functions of each Unit 39 2-1 Basic Unit 39 2-2 Advanced Unit 40 2-3 Non-Contact Door Switch Controller 42 2-4 Safety Guard Switching Unit 44 2-5 Expansion Unit 48 G9SX USER'S GUIDE Functions of G9SX 1. Function list of G9SX-series 37 1. Function list of G9SX-series Function G9SX-BC G9SX-AD G9SX-ADA G9SX-NS G9SX-NSA G9SX-GS Inputs --- ● ● (2 inputs) ● ● ● Outputs ● ● ● ● ● ● Emergency stop ● ● ● --- ● --- Door switch ● ● ● --- ● ● Non-contact door switch (D40A) --- --- --- ● ● --- Light curtain ● ● ● --- --- ● Number of safety inputs 1 1 1 1 2 2 Instantaneous outputs 2 3 2 2 2 2 OFF-delayed outputs --- 2 2 --- 2 2 OFF-delay time --- 0 to 15 s, 0 to 150 s 0 to 15 s, 0 to 150 s --- 0 to 3 s 0 to 15 s Expansion Unit connection --- ● ● --- ● ● --- --- --- --- --- ● Logical AND connections Section 2 Safety inputs Functions of G9SX Safety outputs Model Guard switching 38 G9SX USER'S GUIDE 2. Functions of each Unit 2-1 Basic Unit It is possible to connect to other Units by using the logical AND connection output. ■ G9SX-BC@ Safety Inputs Safety Input 1 input (2-channel input) Safety input devices Emergency stop switch, door switch, light curtain Section Safety inputs Instantaneous outputs T31 T32 T33 Y1 T11 T12 X1 A1 2 outputs PWR Logical AND Connections None Number of outputs 2 outputs Functions of G9SX G9SX-BC202 24VDC OFF-delayed outputs None Number of inputs 2 Safety Outputs (Semiconductor Outputs) FB T1 T2 EI ERR No. T21 T22 X2 S14 S24 L1 A2 L2 Required Settings and Wiring Item G9SX-BC Page Logical AND connection input enable/disable --- --- Cross fault detection mode ❍ 63 Reset mode ❍ 62 OFF-delay time --- --- Switching mode --- --- External indicator fault diagnosis mode --- --- Safety Instantaneous Output Logical AND Connection Output LED Indicators Marking Color Name PWR Green Power supply indicator T1 Orange Safety input #1 indicator T2 Orange Safety input #2 indicator FB Orange Feedback/reset input indicator EI Orange Safety output indicator ERR Red Error indicator T31 T32 T33 Y1 T11 T12 X1 A1 G9SX-BC202 24VDC PWR FB T1 T2 EI ERR No. T21 T22 X2 S14 S24 L1 A2 L2 G9SX USER'S GUIDE 39 2. Functions of each Unit 2-2 Advanced Unit This Unit has safety OFF-delayed outputs and can be connected to other Units using the logical AND connection input and output. ■ G9SX-AD@ Safety Inputs Section Safety inputs 1 input (2-channel input) Safety Input Emergency stop switch, door switch, Safety input devices light curtain Logical AND Connection Input 2 Functions of G9SX Safety Outputs (Semiconductor Outputs) Instantaneous outputs 3 outputs OFF-delayed outputs 2 outputs T31 T32 T33 T11 T12 Y1 X1 X2 Note: The OFF-delayed outputs can be used as instantaneous outputs by setting the OFF-delay time to 0 s. PWR FB T1 T2 AND EI 0.7 0.6 0.5 0.4 0.3 0.2 Logical AND Connections 1 1.5 2 0 15 ED 3 4 5 7 10 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S34 S44 S54 Number of inputs 1 input Number of outputs 1 output A1 G9SX-AD322-T15 24VDC A2 L1 OFF-delay Time Setting G9SX-AD322-T15-@ 0 to 15 s G9SX-AD322-T150-@ 0 to 150 s Safety Instantaneous Output Safety OFF-delayed Output Required Settings and Wiring Item G9SX-AD Page Logical AND connection input enable/disable ❍ 57 Cross fault detection mode ❍ 63 Reset mode ❍ 62 OFF-delay time ❍ 65 Switching mode --- --- External indicator fault diagnosis mode --- --- LED Indicators Marking Color PWR Green Power supply indicator T1 Orange Safety input #1 indicator T2 Orange Name T31 T32 T33 T11 T12 Y1 X1 X2 A1 G9SX-AD322-T15 24VDC Safety input #2 indicator PWR FB T1 T2 AND FB AND 40 Orange Orange Feedback/reset input indicator Logical AND input indicator EI Orange Safety output indicator ED Orange OFF-delayed safety output indicator ERR Red G9SX USER'S GUIDE Error indicator EI 0.7 0.6 0.5 0.4 0.3 0.2 1 1.5 2 0 15 ED 3 4 5 7 10 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S34 S44 S54 A2 L1 Logical AND Connection Output 2. Functions of each Unit ■ G9SX-ADA@ Safety Inputs Safety inputs 1 input (2-channel input) Safety Input Emergency stop switch, door switch, Safety input devices light curtain Logical AND Connection Input Safety Outputs (Semiconductor Outputs) Section Instantaneous outputs 2 outputs OFF-delayed outputs 2 outputs T31 T32 T33 T51 T52 T11 T12 Y1 X1 X2 PWR FB T2 T1 AND1 AND2 0.7 0.6 0.5 0.4 0.3 0.2 Logical AND Connections 1 1.5 2 0 15 ED 3 4 5 7 10 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S44 S54 L1 Number of outputs 2 outputs Functions of G9SX EI 2 inputs 2 Note: The OFF-delayed outputs can be used as instantaneous outputs by setting the OFF-delay time to 0 s. Number of inputs A1 G9SX-ADA222-T150 24VDC A2 L2 OFF-delay Time Setting G9SX-ADA222-T15-@ 0 to 15 s G9SX-ADA222-T150-@ 0 to 150 s Safety Instantaneous Output Safety OFF-delayed Output Logical AND Connection Output Required Settings and Wiring Item G9SX-ADA Page Logical AND connection input enable/disable ❍ 57 Cross fault detection mode ❍ 63 Reset mode ❍ 62 OFF-delay time ❍ 65 Switching mode --- --- External indicator fault diagnosis mode --- --- LED Indicators Marking Color PWR Green Power supply indicator T1 Orange Safety input #1 indicator T2 Orange Name T31 T32 T33 T51 T52 T11 T12 Y1 X1 X2 A1 G9SX-ADA222-T150 24VDC Safety input #2 indicator PWR FB T1 T2 AND1 AND2 FB AND1 Orange Orange Feedback/reset input indicator Logical AND input indicator AND2 Orange Logical AND input indicator EI Orange Safety output indicator ED Orange OFF-delayed safety output indicator ERR Red EI 0.7 0.6 0.5 0.4 0.3 0.2 1 1.5 2 0 15 ED 3 4 5 7 10 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S44 S54 L1 A2 L2 Error indicator G9SX USER'S GUIDE 41 2. Functions of each Unit 2-3 Non-Contact Door Switch Controller This is a Special Controller for D40A Non-contact Door Switch. It can be connected to other Units using the logical AND connection input and output. ■ G9SX-NS@ Safety Inputs Section Safety inputs 1 input (2-channel input) Safety input devices Non-contact door switch (D40A) Logical AND Connection Input D40A Input 2 Safety Outputs (Semiconductor Outputs) Functions of G9SX Instantaneous outputs 2 outputs OFF-delayed outputs None T31 T32 T33 D3 D1 D2 X1 A1 G9SX-NS202 24VDC Logical AND Connections PWR AND Number of inputs 1 input Number of outputs 1 output EI FB NS ERR No. T41 T42 X2 S14 S24 L1 A2 D4 Required Settings and Wiring Item G9SX-NS Page Logical AND connection input enable/disable ❍ 57 Cross fault detection mode --- --- Reset mode ❍ 62 OFF-delay time --- --- Switching mode --- --- External indicator fault diagnosis mode --- --- Safety Instantaneous Output LED Indicators Marking Color Name PWR Green Power supply indicator NS Orange Non-contact Door Switch input indicator FB Orange Feedback/reset input indicator AND Orange Logical AND input indicator EI Orange Instantaneous safety output indicator ERR Red T31 T32 T33 D3 D1 D2 X1 A1 G9SX-NS202 24VDC PWR FB AND NS EI 42 G9SX USER'S GUIDE Error indicator ERR No. T41 T42 X2 S14 S24 L1 A2 D4 Logical AND Connection Output 2. Functions of each Unit ■ G9SX-NSA@ Safety Inputs Safety inputs 2 inputs (each with 2 channels) Non-contact door switch (D40A), Safety input devices emergency stop switch, door switch Safety Input D40A Input Logical AND Connection Input Safety Outputs (Semiconductor Outputs) 2 outputs OFF-delayed outputs 2 outputs T31 T32 T33 D1 T11 T12 Y1 X1 D2 X2 FB T1 T2 AND NS EI ED 0.8 0.91.0 1.2 1.4 1.8 2.0 2.5 0 3.0 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S44 S54 L1 Number of outputs 1 output Functions of G9SX 0.7 0.6 0.5 0.4 0.3 0.2 2 PWR Logical AND Connections 1 input D3 A1 G9SX-NSA222-T30 24VDC Note: The OFF-delayed outputs can be used as instantaneous outputs by setting the OFF-delay time to 0 s. Number of inputs Section Instantaneous outputs A2 D4 OFF-delay Time Setting G9SX-NSA222-T03-@ 0 to 3 s Safety Instantaneous Output Required Settings and Wiring Item G9SX-NSA Page Logical AND connection input enable/disable ❍ 57 Cross fault detection mode ❍ 63 Reset mode ❍ 62 OFF-delay time ❍ 65 Switching mode --- --- External indicator fault diagnosis mode --- --- Safety OFF-delayed Output Logical AND Connection Output LED Indicators Marking Color Name PWR Green Power supply indicator T1 Orange Safety input #1 indicator T2 Orange Safety input #2 indicator NS Orange Non-contact Door Switch input indicator FB Orange Feedback/reset input indicator AND Orange Logical AND input indicator EI Orange Instantaneous safety output indicator ED Orange OFF-delayed safety output indicator ERR Red T31 T32 T33 D1 T11 T12 Y1 X1 D2 X2 D3 A1 G9SX-NSA222-T30 24VDC PWR 0.7 0.6 0.5 0.4 0.3 0.2 FB T1 T2 AND NS EI ED 0.8 0.91.0 1.2 1.4 1.8 2.0 2.5 0 3.0 OFF-DELAY ERR No. T21 T22 T41 T42 S14 S24 S44 S54 L1 A2 D4 Error indicator G9SX USER'S GUIDE 43 2. Functions of each Unit 2-4 Safety Guard Switching Unit This Unit can alternately enable two safety inputs. It can be used to construct safety systems for semi-automatic processing and maintenance work. ■ G9SX-GS@ Safety Inputs Safety inputs 2 inputs (each with 2 channels) Safety Input Section Safety input devices Door switch, light curtain Safety Input Logical AND Connection Input Safety Outputs (Semiconductor Outputs) 2 Functions of G9SX Instantaneous outputs 2 outputs OFF-delayed outputs 2 outputs Note: The OFF-delayed outputs can be used as instantaneous outputs by setting the OFF-delay time to 0 s. T31 T32 T33 Y1 M1 M2 UA UB T11 T12 T61 T62 Y2 Y3 Y4 A1 G9SX-GS226-T15 24VDC PWR Number of inputs Number of outputs AND T2 UB T7 EI ED 1.5 2 3 0.7 1 4 0.6 5 0.5 7 0.4 10 0.3 0.2 0 15 1 input FB UA T6 T1 Logical AND Connections OFF-DELAY ERR No. T21 T22 T71 T72 T41 T42 L1 A2 X1 X2 X3 X4 S14 S24 S44 S54 1 output OFF-delay Time Setting G9SX-GS226-T15-@ 0 to 15 s Required Settings and Wiring Item G9SX-GS Page Logical AND connection input enable/disable ❍ 57 Cross fault detection mode ❍ 63 Reset mode ❍ 62 OFF-delay time ❍ 65 Switching mode ❍ 67 External indicator fault diagnosis mode ❍ 68 Safety Instantaneous Output Safety OFF-delayed Output Note: Carefully read the Precautions on pages 96 to 99 before configuring a system using the G9SX-GS. LED Indicators Marking Color Name T31 T32 T33 Y1 M1 M2 UA UB T11 T12 T61 T62 Y2 Y3 Y4 A1 PWR Green Power supply indicator T1 Orange Safety input A, channel 1 indicator 24VDC PWR FB T2 Orange Safety input A, channel 2 indicator T1 UA T2 T6 UB T7 G9SX-GS226-T15 44 T6 Orange Safety input B, channel 1 indicator T7 Orange Safety input B, channel 2 indicator FB Orange Feedback/reset input indicator AND Orange Logical AND input indicator EI Orange Safety output indicator ED Orange OFF-delayed safety output indicator UA Orange Safety input A disabled state indicator UB Orange Safety input B disabled state indicator ERR Red G9SX USER'S GUIDE Error indicator EI 1.5 2 3 0.7 1 4 0.6 5 0.5 7 0.4 10 0.3 0.2 0 15 OFF-DELAY AND ED ERR No. T21 T22 T71 T72 T41 T42 L1 A2 X1 X2 X3 X4 S14 S24 S44 S54 Logical AND Connection Output 2. Functions of each Unit Functions Auto Switching Function When the operator inserts the workpiece... Safety Light Curtain A While the robot processes the workpiece... Safety Light Curtain B • Safety Light Curtain A monitors the robot. • The robot can continue monitors the operator. • The robot can continue to operate as long as the operator does not interrupt Safety Light Auto switching Curtain B. Section to operate as long as it does not interrupt Safety Light Curtain A. • Safety Light Curtain B 2 Manual Switching Function During normal operation... During maintenance... • The Door Switch monitors the opening and closing of the door during normal operation. • The machine is able to operate while the door is closed. Door Switch Functions of G9SX Note: If the operator is able to completely enter the zone inside Safety Light Curtain B, a presence detection device, such as a Safety Mat, is necessary as an additional safety measure. • The Limit Switch monitors the conveyor cart position during maintenance. • The machine is able to operate while the conveyor cart is in a specified area. Manual switching Normal operation Maintenance Limit Switch G9SX USER'S GUIDE 45 2. Functions of each Unit Auto Switching Function (2) Safety Light Curtain A (2) Safety Light Curtain A (3) Safety Light Curtain B (1) Emergency Stop Switch A22E (3) Safety Light Curtain B Safety Light Curtain F3SJ Safety Light Curtain F3SJ Section 2 Basic Unit G9SX-BC Auxiliary Output Logical AND connection Programmable Controllers CS/CJ Series Safety Output Functions of G9SX The auxiliary output can be used to notify operators of the input, output, or error status. Safety Guard Switching Unit G9SX-GS (1) Emergency Stop Switch External External indicator A indicator B Robot Working condition External indicator Welding robot Conveying robot External Indicator Output Contactor The external indicator output can be used to notify operators of Safety Light Curtains that may safely be interrupted. Note: External indicator output may be used as necessary. G9SX-GS Safety input Safety output Monitor output External indicator Safety input A ON ON Input A monitor ON Safety Light Curtain A Indicator A Safety input B Safety output Normal operation Safety Light Curtain B ON Emergency Stop Switch Welding robot Conveying robot Indicator B Safety input A Monitoring ON ON Input A monitor ON Safety Light Curtain A Indicator A Safety input B Safety output Safety Light Curtain B OFF Emergency Stop Switch OFF Input B monitor OK to work Indicator B Safety input A Welding robot Conveying robot OFF Safety Light Curtain B OFF Input A monitor ON Input B monitor ON Safety Light Curtain A Indicator A Safety input B Monitoring Safety output ON Emergency Stop Switch Indicator B Not OK to work 3 Hazardous condition Input B monitor OK to work 1 2 46 ON Welding robot Conveying robot Safety input A OFF OFF OFF Input A monitor OFF Safety Light Curtain A Indicator A Safety input B Safety output Safety Light Curtain B 4 G9SX USER'S GUIDE OFF Emergency Stop Switch Not OK to work OFF Input B monitor Indicator B 2. Functions of each Unit Manual Switching Function (2) Cover (2) Safety Door Switch (3) Conveyor cart (3) Safety Limit Switch (1) Emergency Stop Switch A22E Safety Door Switch D4NS Safety Limit Switch D4F Normal operation Working condition External indicator External External indicator A indicator B Safety output The external indicator output can be used to notify operators that the cover may be opened. Note: External indicator output may be used as necessary. G9SX-GS Safety input Disabled Limit Switch Mode selector Safety output Mode selector Monitor output External indicator Normal operating mode Monitoring Input A monitor ON Indicator A Safety output Door Switch OFF Safety input B ON ON Emergency Stop Switch Input B monitor Indicator B Not OK to open 1 Safety input A Limit Switch Input A monitor Indicator A Safety input B Emergency Stop Switch OK to open 2 ON ON Disabled Door Switch Maintenance mode ON Mode selector Maintenance Conveyor cart External Indicator Output Safety input A Disabled Monitoring Disabled Safety output OFF Input B monitor Indicator B Safety input A Monitoring Limit Switch OK to open OFF Input B monitor Limit Switch Disabled Safety output Indicator B Maintenance mode OFF OFF Input A monitor OFF Input B monitor OFF Mode selector Indicator A Safety input B Disabled Door Switch Indicator A Safety input A OFF Monitoring Input A monitor Safety input B Emergency Stop Switch 3 ON ON Mode selector Door Switch Maintenance mode ON Disabled Hazardous condition Contactor Functions of G9SX (1) Emergency Stop Switch Programmable Controllers CS/CJ Series 2 Auxiliary Output The auxiliary output can be used to notify operators of the input, output, or error status. Safety Guard Switching Unit G9SX-GS Logical AND connection (4) Mode selector Key-type Selector Switch A22K Section Basic Unit G9SX-BC 4 (4) Mode selector Emergency Stop Switch OK to open Disabled Safety output Indicator B G9SX USER'S GUIDE 47 2. Functions of each Unit 2-5 Expansion Unit By connecting an Expansion Unit to the G9SX-AD/ADA, G9SX-NSA, or G9SX-GS, safety relay contact outputs can be added that are synchronized with the safety outputs of the Unit to which the Expansion Unit is connected. ■ G9SX-EX-@ Safety Outputs (Safety Relay Outputs) Section Instantaneous outputs 4 outputs OFF-delayed outputs None 2 Functions of G9SX G9SX-AD G9SX-ADA G9SX-NSA G9SX-GS G9SX-EX Logical AND Connections Number of inputs None Number of outputs None Insert the connector G9SX-EX Required Settings and Wiring Item G9SX-EX Page Logical AND connection input enable/disable --- --- Cross fault detection mode --- --- Reset mode --- --- OFF-delay time --- --- Switching mode --- --- External indicator fault diagnosis mode --- --- Safety Instantaneous Output Note: Refer to 2-10 Connecting Expansion Units on page 69. LED Indicators Marking Color PWR Green Power supply indicator EI Orange Safety output indicator ERR Red Name Error indicator PWR EI ERR 48 G9SX USER'S GUIDE Insert the connector 2. Functions of each Unit ■ G9SX-EX-T@ Safety Outputs (Safety Relay Outputs) Instantaneous outputs None OFF-delayed outputs 4 outputs Logical AND Connections Number of inputs None Number of outputs None Insert the connector G9SX-EX041-T Insert the connector G9SX-EX Section G9SX-AD G9SX-ADA G9SX-NSA G9SX-GS G9SX-EX 2 Required Settings and Wiring G9SX-EX-T Page Logical AND connection input enable/disable --- --- Cross fault detection mode --- --- Reset mode --- --- OFF-delay time --- (See note) 65 Switching mode --- --- External indicator fault diagnosis mode --- --- Functions of G9SX Item Safety OFF-delayed Output Note: 1. The OFF-delay time on G9SX-EX-T is set from the OFF-delay preset time on the connected unit (G9SX-AD/-ADA/-NSA/-GS). 2. Refer to 2-10 Connecting Expansion Units on page 69. LED Indicators Marking Color PWR Green Power supply indicator Orange OFF-delayed safety output indicator ED ERR Red Name Error indicator G9SX-EX041-T PWR ED ERR G9SX USER'S GUIDE 49 MEMO 50 G9SX USER'S GUIDE Section 3 Wiring and Setup 52 1-2 Advanced Unit 53 1-3 Non-contact Door Switch Controller 54 1-4 Safety Guard Switching Unit 55 1-5 Expansion Unit 56 2. Functions, Wiring and Settings Wiring and Setup 1-1 Basic Unit 3 52 Section 1. I/O Terminals 57 2-1 Logical AND Connection 57 2-2 Response Time and Operation Time 60 2-3 Reset Mode 62 2-4 Cross Fault Detection 63 2-5 Connecting Safety Sensors and the G9SX 64 2-6 OFF-delay Time 65 2-7 Non-contact Door Switch 66 2-8 Switching Mode 67 2-9 External Indicator Fault Diagnosis 68 2-10 Connecting Expansion Units 69 2-11 Confirming Settings 70 G9SX USER'S GUIDE 51 1. I/O Terminals 1-1 Basic Unit Signal name Terminal name Section Power supply inputs A1, A2 Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Safety inputs T11, T12, T21, T22 Refer to 2-4 Cross Fault Detection and 2-5 Connecting Safety Sensors and the G9SX. Feedback/reset inputs T31, T32, T33 Refer to 2-3 Reset Mode. Cross fault detection input Y1 Refer to 2-4 Cross Fault Detection. Instantaneous safety outputs S14, S24 Keep these outputs open when they are not used. Logical AND connection output L1, L2 Refer to 2-1 Logical AND Connection. Auxiliary monitor outputs X1, X2 Keep these outputs open when they are not used. 3 Wiring and Setup G9SX-BC A1 T11 T12 T21 T22 T31 T32 T33 Y1 (See note 1.) Power supply circuit A2 Safety Input 1 Safety Input 2 Reset/Feedback Input Safety outputs control S14 S24 L1 L2 Cross fault detection input Auxiliary outputs control X1 X2 (See note 2.) Note: 1. Internal power supply circuit is not isolated. 2. Outputs S14 and S24 are internally redundant. 52 Wiring G9SX USER'S GUIDE 1. I/O Terminals 1-2 Advanced Unit Signal name Terminal name Wiring Safety inputs T11, T12, T21, T22 Refer to 2-4 Cross Fault Detection and 2-5 Connecting Safety Sensors and the G9SX Feedback/reset inputs T31, T32, T33 Refer to 2-3 Reset Mode. Logical AND connection inputs T41, T42, T51, T52 Refer to 2-1 Logical AND Connection. Cross fault detection input Y1 Refer to 2-4 Cross Fault Detection. Instantaneous safety outputs S14, S24, S34 Keep these outputs open when they are not used. OFF-delayed safety outputs S44, S54 Keep these outputs open when they are not used. Logical AND connection output L1, L2 Refer to 2-1 Logical AND Connection. Auxiliary monitor outputs X1, X2 Keep these outputs open when they are not used. G9SX-ADA A1 T11 T12 T21 T22 T31 T32 T33 Y1 T41 T42 (See note 1.) Power supply circuit A2 (See note 2.) Safety Input 1 Safety Input 2 Logical AND input Expansion Unit Auxiliary output control output control S14 S24 S34 S44 S54 L1 X1 X2 (See note 3.) Note: 1. Internal power supply circuit is not isolated. 2. Logical AND input is isolated. 3. Outputs S14 to S54 are internally redundant. (See note 2.) (See note 1.) Cross Reset/Feedback fault detection Input input Safety output control A1 T11 T12 T21 T22 T31 T32 T33 Y1 T41 T42 T51 T52 Power supply circuit A2 Safety Input 1 Safety Input 2 Wiring and Setup G9SX-AD 3 A1, A2 Section Power supply inputs Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Cross Logical Logical Reset/Feedback fault detection AND input AND input 2 Input input Safety output control Auxiliary Expansion Unit output control output control S14 S24 S44 S54 L1 L2 X1 X2 (See note 3.) Note: 1. Internal power supply circuit is not isolated. 2. Logical AND input is isolated. 3. Outputs S14 to S54 are internally redundant. G9SX USER'S GUIDE 53 1. I/O Terminals 1-3 Non-contact Door Switch Controller Signal name Terminal name Wiring Section 3 Wiring and Setup Power supply inputs A1, A2 Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Safety inputs T11, T12, T21, T22 Refer to 2-4 Cross Fault Detection and 2-5 Connecting Safety Sensors and the G9SX. Non-contact Door Switch (D40A) inputs D1, D2, D3, D4 Refer to 2-7 Non-contact Door Switch. Feedback/reset inputs T31, T32, T33 Refer to 2-3 Reset Mode. Logical AND connection inputs T41, T42 Refer to 2-1 Logical AND Connection. Cross fault detection input Y1 Refer to 2-4 Cross Fault Detection. Instantaneous safety outputs S14, S24 Keep these outputs open when they are not used. OFF-delayed safety outputs S44, S54 Keep these outputs open when they are not used. Logical AND connection output L1 Refer to 2-1 Logical AND Connection. Auxiliary monitor outputs X1, X2 Keep these outputs open when they are not used. G9SX-NS A1 G9SX-NSA D1 D2 D3 D4 T31 T32 T33 T41 T42 A1 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42 (See note 2.) (See note 2.) Power Non-contact Door Reset/Feedback Logical AND input supply Input Switch control circuit Auxiliary (See Safety output control output control note 1.) A2 S14 S24 L1 X1 X2 (See note 3.) Note: 1. Internal power supply circuit is not isolated. 2. Logical AND input is isolated. 3. Outputs S14 to S24 are internally redundant. 54 G9SX USER'S GUIDE Power supply circuit (See note 1.) A2 Safety input 1 Safety input 2 fault Reset/Feedback Cross detection Non-contact Door Input Switch control input Safety output control S14 S24 S44 S54 L1 Auxiliary output control X1 Logical AND input Expansion Unit output control X2 (See note 3.) Note: 1. Internal power supply circuit is not isolated. 2. Logical AND input is isolated. 3. Outputs S14 to S54 are internally redundant. 1. I/O Terminals 1-4 Safety Guard Switching Unit Signal name Terminal name Wiring Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. T11, T12, T21, T22 Safety inputs B T61, T62, T71, T72 Refer to 2-4 Cross Fault Detection and 2-5 Connecting Safety Sensors and the G9SX. Mode switching inputs M1, M2 Refer to 2-8 Switching Mode. Feedback/reset inputs T31, T32, T33 Refer to 2-3 Reset Mode. Logical AND connection inputs T41, T42 Refer to 2-1 Logical AND Connection. Cross fault detection inputs Y1, Y2 Refer to 2-4 Cross Fault Detection. Instantaneous safety outputs S14, S24 Keep these outputs open when they are not used. OFF-delayed safety outputs S44, S54 Keep these outputs open when they are not used. Logical AND connection output L1 Refer to 2-1 Logical AND Connection. Auxiliary monitor outputs X1, X2, X3, X4 Keep these outputs open when they are not used. External indicator outputs UA, UB Refer to 2-9 External Indicator Fault Diagnosis. External indicator diagnosis switching inputs Y3, Y4 Refer to 2-9 External Indicator Fault Diagnosis. Wiring and Setup Safety inputs A 3 A1, A2 Section Power supply inputs G9SX-GS A1 T11 T12 T21 T22 Y1 M1 M2 T61 T62 T71 T72 Y2 Y3 Y4 T31 T32 T33 T41 T42 (See note 2.) Cross Power Safety input A Safety input A fault Mode selector Safety input B Safety input B detection supply Ch. 1 Ch. 2 input Ch. 1 Ch. 2 input A circuit (See Safety output control Auxiliary output control note 1.) A2 S14 S24 S44 S54 L1 X1 X2 X3 X4 Cross fault detection input B External indicator diagnosis switching input Reset/ feedback input External indicator output control Logical AND input Expansion Unit output control UA UB (See note 3.) Note: 1. Internal power supply circuit is not isolated. 2. Logical AND input is isolated. 3. Outputs S14 to S54 and L1 are internally redundant. G9SX USER'S GUIDE 55 1. I/O Terminals 1-5 Expansion Unit Signal name Terminal name Wiring Power supply inputs A1, A2 Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Safety outputs (See note.) 13-14, 23-24, 33-34, 43-44 Keep these outputs open when not used. Note: The safety outputs are instantaneous safety outputs for the G9SX-EX401, and OFF-delayed safety outputs for the G9SX-EX041-T. G9SX-EX401/G9SX-EX041-T A1 Section 3 Wiring and Setup 56 (See note 1.) Exp. sig. IN 13 23 33 43 Safety output Power control supply circuit Auxiliary output control A2 X2 (See note 2.) K1 Exp. sig. OUT K2 14 24 34 44 Note: 1. Internal power supply circuit is not isolated. 2. Relay outputs are isolated. G9SX USER'S GUIDE 2. Functions, Wiring and Settings 2-1 Logical AND Connection When connecting two or more Units using a logical AND connection, the logical AND connection setting is performed on the Unit on the input side. Set the logical AND connection preset switch on the Unit that is on the input side (G9SX-AD322 in the below diagram) to AND. 1. When the G9SX-AD/-NS/-NSA/-GS Is on the Input Side Unit A AND L1 A2 T41 T42 OFF AND OFF G9SX-AD322 Wiring and Setup Unit B Unit C AND L1 OFF A2 L1 A2 OFF AND T41 T42 T51 T52 3 2. When the G9SX-ADA Is on the Input Side AND Section Note: 1. In the above diagram, a setting error will occur and G9SX-AD322 will set a lock out if the logical AND setting switch on G9SX-AD322 is set to OFF. Set the switch carefully. 2. Set the logical AND setting switch on Unit A to OFF. 3. A logical AND input cannot be input to the G9SX-BC. AND OFF OFF T51/T52 T41/T42 G9SX-ADA222 Note: 1. When not connecting Unit B, leave terminals T41 and T42 of the G9SX-ADA222 Unit open, and set the logical AND setting switch T41/T42 to OFF. 2. When not connecting Unit C, leave terminals T51 and T52 of the G9SX-ADA222 Unit open, and set the logical AND setting switch to OFF. When connecting multiple Units to the input side, follow the wiring example in the following diagram. Unit A Input a G9SX-BC202 or G9SX-AD322-T Output (a) L1 A2 Unit B T41 T42 Logical AND connection signal (1st stage) Input b G9SX-AD322-T Output (a&b) L1 A2 Next unit (4 unit max.) T41 T42 G9SX-AD322-T Logical AND connection signal (2nd stage) Next unit (4 unit max.) T41 T42 G9SX-AD322-T L1 A2 Next unit (5 layers max.) Note: When a logical AND connection is not used, keep the logical AND connection inputs (terminals T41, T42, T51, and T52) and logical AND connection outputs (terminals L1 and L2) open, and set the logical AND setting switch to OFF. G9SX USER'S GUIDE 57 2. Functions, Wiring and Settings 3. Logical AND Connection Combinations ( 1 ) One logical AND connection output from an Advanced Unit G9SX-AD can be logical AND connected to up to four Advanced Units. G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD ( 2 ) Two logical AND outputs from a Basic Unit G9SX-BC can be logical AND connected to up to eight Advanced Units. G9SX-BC Section G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD 3 G9SX-AD Wiring and Setup G9SX-AD ( 3 ) Two logical AND outputs from an Advanced Unit G9SX-ADA can be logical AND connected to up to eight Advanced Units. G9SX-ADA G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD G9SX-AD ( 4 ) Any Advanced Unit with logical AND input can be logical AND connected to Advanced Units on up to five tiers. Advanced Unit or Basic Unit G9SX-AD G9SX-AD G9SX-AD G9SX-AD 58 G9SX USER'S GUIDE 2. Functions, Wiring and Settings ( 5 ) Two logical AND connection outputs, each from different Advanced/Basic Units, can be logical AND connected to a single G9SX-ADA Unit. G9SX-BC G9SX-BC G9SX-ADA ( 6 ) The largest possible system configuration contains a total of 20 Advanced and Basic Units. In this configuration, each Advanced Unit can have up to five Expansion Units. Advanced Unit or Basic Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Advanced Unit Number of Units connected in series by logical AND: 5 Units max. Advanced Unit Wiring and Setup Advanced Unit 3 Advanced Unit Section Advanced Unit Note 1: Basic Unit = G9SX-BC Advanced Unit = G9SX-AD or G9SX-ADA Note 2: The G9SX-AD322-T-@ has only one logical AND output. Number of Units connected per logical AND output: 4 Units max. Advanced Unit Advanced Unit Total number of Units connected by logical AND: 20 Units max. Note: The section on Advanced Units, above, can also be replaced with G9SX-NS/-NSA/-GS. G9SX USER'S GUIDE 59 2. Functions, Wiring and Settings 2-2 Response Time and Operation Time (1) G9SX-BC Safety input Max. response time (excluding Expansion Units) (See note 1.) Max. operating time (excluding Expansion Units) (See note 2.) 15 ms 50 ms Max. response time (excluding Expansion Units) (See note 1.) Max. operating time (excluding Expansion Units) (See note 2.) Safety input 15 ms 50 ms Logical AND connection input 15 ms 100 ms Max. response time (excluding Expansion Units) (See note 1.) Max. operating time (excluding Expansion Units) (See note 2.) Non-contact Door Switch input 20 ms 100 ms Logical AND connection input 15 ms 100 ms Max. response time (excluding Expansion Units) (See note 1.) Max. operating time (excluding Expansion Units) (See note 2.) Non-contact Door Switch input 20 ms 100 ms Safety input 15 ms 50 ms Logical AND connection input 15 ms 100 ms Safety input (2) G9SX-AD/ADA Section Safety input D4NS 3 Logical AND connection input Wiring and Setup (3) G9SX-NS Non-contact Door Switch input D40A Logical AND connection input (4) G9SX-NSA Non-contact Door Switch input D40A Logical AND connection input Safety Input D4NS Note: 1. The maximum response time is the time it takes the output to turn OFF after the input turns OFF. 2. The maximum operating time is the time it takes the output to turn ON after the input turn ON. 60 G9SX USER'S GUIDE 2. Functions, Wiring and Settings (5) G9SX-GS Safety Input A D4NS Safety Input B D4NS Logical AND connection input Max. response time (excluding Expansion Units) (See note 1.) Max. operating time (excluding Expansion Units) (See note 2.) Safety input A 15 ms (See note 3.) 50 ms Safety input B 15 ms (See note 3.) 50 ms 15 ms 100 ms Logical AND connection input Note: 1. The maximum response time is the time it takes the output to turn OFF after the input turns OFF. 2. The maximum operating time is the time it takes the output to turn ON after the input turn ON. 3. The maximum response time exists when safety input A or safety input B is enabled. Case 1 Safety Input A22E 3 Response Time from When A22E Turns OFF until Safety Output 2 Section (6) When two or more Units are connected using a logical AND connection. Turns OFF + 15 ms (Logical AND = Wiring and Setup 15 ms (A22E) 30 ms Connection (1)) Safety Output (1) Case 2 D40A Safety Input D4NS (1) Logical AND Connection (1) Response Time from When D40A Turns OFF until Safety Output 3 Turns OFF 20 ms (D40A) + 15 ms (Logical AND = 35 ms Connection (2)) Case 3 Safety Output (2) Logical AND Connection (2) Safety Input D4NS (2) Response Time from When A22E Turns OFF until Safety Output 3 Turns OFF 15 ms (A22E) + 15 ms (Logical AND Connection (1)) + 15 ms (Logical AND = 45 ms Connection (2)) Note: The operation time is calculated in a similar fashion. Safety Output (3) G9SX USER'S GUIDE 61 2. Functions, Wiring and Settings 2-3 Reset Mode Set the reset mode using feedback/reset input terminals T31, T32, and T33. Reset mode Wiring Function summary Feedback Loop KM1 KM2 The signal to terminal T33 must be ON for the safety output to turn ON. If terminal T33 is not ON, the safety output will not turn ON. KM3 Auto reset mode KM4 +24 V KM5 Section T31 T32 T33 3 Feedback Loop Wiring and Setup KM1 Reset switch KM2 KM3 Manual reset mode KM4 KM5 T31 62 The signal to terminal T32 must turn ON and then OFF for the safety output to turn ON. If terminal T32 does not turn ON and then OFF, the safety output will not turn ON. G9SX USER'S GUIDE T32 +24 V T33 2. Functions, Wiring and Settings 2-4 Cross Fault Detection The cross fault detection setting for the safety input is made using the cross fault detection input (terminals Y1 and Y2). Cross fault detection mode Cross fault detection input ON Open OFF Connect to +24 V Cross fault detection input Safety input to be monitored Function summary Terminal Y1 Terminals T11-T12 and T21-T22 Detects cross faults across T11-T12 and T21-T22 Terminal Y2 Terminals T61-T62 and T71-T72 Detect cross faults in T61-T62 and T71-T72 If a fault is detected, the following will occur. Section 1. The safety outputs and logical AND outputs will be locked out. 2. The LED error indicator will be lit. 3 3. The error output (auxiliary output) will turn ON. Wiring and Setup For wiring, refer to the following description. ( 1 ) Cross Fault between T11-T12 and T21-T22 Cross fault detection Wiring +24 V S1 Corresponds to Safety Category 2 +24 V T11 T12 T21 T22 Y1 OFF +24 V +24 V S1 Corresponds to Safety Category 3 +24 V T11 T12 T21 T22 Y1 T11 T12 T21 T22 NC Y1 S1 ON Corresponds to Safety Category 4 G9SX USER'S GUIDE 63 2. Functions, Wiring and Settings 2-5 Connecting Safety Sensors and the G9SX ( 1 ) When connecting safety sensors to the G9SX, the Y1 terminal must be connected to 24 VDC. The G9SX will detect a connection error, if the Y1 terminal is open. ( 2 ) In many cases, safety sensor outputs include an OFF-shot pulse for self diagnosis. The following condition of test pulse is applicable as safety inputs for the G9SX. • OFF-shot pulse width of the sensor, during the ON-state: 340 μs max. 340 µs max. Section 3 Wiring and Setup 64 G9SX USER'S GUIDE 2. Functions, Wiring and Settings 2-6 OFF-delay Time The safety output preset time is set using the OFF-delay time preset switch (1 each on the front and back of the Unit). Note: 1. Normal operation will occur only if both switches are set to the same setting. An error will occur if both switches are not identically set. 2. If the preset time is set to 0 seconds, the output function as an instantaneous safety output. Front Back Switch Section Switch 3 Wiring and Setup Refer to the following illustration for details on setting switch positions. 1. G9SX-AD322-T15 0.7 0.6 0.5 0.4 0.3 0.2 1 1.5 2 0 15 3 0.7 0.6 0.5 0.4 0.3 0.2 4 5 7 10 OFF-DELAY Notch Example 1: 0-second OFF-delay setting 1 1.5 2 0 15 3 4 5 7 10 OFF-DELAY Example 2: 1-second OFF-delay setting 2. G9SX-AD322-T150 60 50 40 30 20 10 70 80 90 100 110 120 130 140 0 150 OFF-DELAY Example 1: 0-second OFF-delay setting 60 50 40 30 20 10 Notch 70 80 90 100 110 120 130 140 0 150 OFF-DELAY Example 2: 70-second OFF-delay setting G9SX USER'S GUIDE 65 2. Functions, Wiring and Settings 2-7 Non-contact Door Switch Example: Wiring a Single Switch Yellow Blue Brown Black White D40A-1C@ D1 D2 D3 D4 Auxiliary output load (See note.) A2 Blue Brown Black Brown Black White Blue Brown Black Wiring and Setup Connect Up to 30 Non-contact Door Switches. White 3 Example: Wiring Multiple Switches White Note: The auxiliary output load current must be 10 mA max. Blue Section G9SX-NS202-@ G9SX-NSA222-T03-@ D1 D2 D3 D4 G9SX-NS202-@ G9SX-NSA222-T03-@ Wiring of Inputs and Outputs Signal name 66 Wire color Description of operation Non-contact Door Switch power supply input Brown Non-contact Door Switch input White Inputs signals from the G9SX-NS@. The Non-contact Door Switch input must be ON as a required condition for the Non-contact Door Switch output to be ON. Non-contact Door Switch output Black Turns ON and OFF according to actuator detection and the status of the Noncontact Door Switch input. Auxiliary output Yellow Turns ON when actuator is detected. G9SX USER'S GUIDE Blue Supplies power to the D40A. Connect to the D3 and D4 terminals of the G9SX-NS@. 2. Functions, Wiring and Settings 2-8 Switching Mode The switching mode is set by using the Switching Function setting switch on the bottom of the G9SX Unit. Set the switch to Auto for auto switching and Manual for manual switching. For manual switching, connect the mode selector as shown in the following table. Switching Mode Auto switching Switching Function setting switch Mode selector connection Manual NC NC M1 M2 Auto +24V Manual Auto Maintenance mode M1 M2 Section Manual switching Normal operating mode 3 Wiring and Setup M1 ON, M2 OFF: Normal operating mode M1 OFF, M2 ON: Maintenance mode G9SX USER'S GUIDE 67 2. Functions, Wiring and Settings 2-9 External Indicator Fault Diagnosis Diagnostic checks of external indicators connected to the G9SX-GS's external indicator outputs UA and UB can be switched with Y3 and Y4, respectively. Note: 1. If there is no indicator connected to external indicator output UA, connect Y3 to 24 V. If there is no indicator connected to external indicator output UB, connect Y4 to 24 V. If they are not connected to 24 V, the G9SX-GS will detect an error. 2. Diagnostic checks cannot be made for LED indicators. Disable the diagnostic check if using LED indicators. External indicator output Diagnostic check enabled Diagnostic check disabled +24V NC Y3 Y3 UA UA Indicator Indicator UA Section 3 Wiring and Setup 68 +24V NC Y4 Y4 UB UB Indicator Indicator UB G9SX USER'S GUIDE 2. Functions, Wiring and Settings 2-10 Connecting Expansion Units • G9SX-EX/G9SX-EX-T Expansion Units can be connected to the G9SX-AD/-ADA Advanced Unit, G9SX-NSA Non-contact Door Switch Controller, or G9SX-GS Safety Guard Switching Unit to increase the number of safety outputs. (Expansion Units cannot be connected to the G9SX-BC or to the G9SX-NS Non-contact Door Switch Controller.) • A maximum of five Expansion Units can be connected to one Advanced Unit. This may be a combination of G9SX-EX Instantaneous types and G9SX-EX-T OFF-delayed types. • Remove the end connector from the Unit (G9SX-AD, G9SX-ADA, G9SX-NSA, or G9SX-GS) and insert the connector on the Connecting Cable from the first Expansion Unit. Place the end connector that was removed from the Unit on the last Expansion Unit (i.e., the rightmost Expansion Unit). • When Expansion Units are connected to an Advanced Unit, make sure that power is supplied to every Expansion Unit. (Refer to the following diagram for actual Expansion Unit connection.) Section 3 Advanced Unit G9SX-AD/-ADA/-NSA/-GS Wiring and Setup Terminating connector Expansion Unit G9SX USER'S GUIDE 69 2-11 Confirming Settings Settings for the G9SX can be checked by the orange indicators for approx. 3 seconds after the power is turned ON. During this settings indication period, the ERR indicator will light, however the auxiliary error output will remain OFF. G9SX-AD/-ADA/-BC/-NS/-NSA Indicator Setting position T1 Cross fault detection mode Y1 terminal FB Reset mode T33 or T32 terminal Logical AND connection input mode (See note.) Logical AND connection preset switch AND (AND1, AND2) Indicator status Lit Setting mode Setting status Detection mode Y1 = open Not lit Non-detection mode Y1 = 24 VDC Lit Manual reset mode T33 = 24 VDC Auto reset mode T32 = 24 VDC Not lit Lit Enable logical AND input "AND" Not lit Disable logical AND input "OFF" Section Note: Except for the G9SX-BC and G9SX-NS. G9SX-GS 3 Wiring and Setup Indicator Item T1 Cross fault detection mode for safety input A Y1 terminal T6 Cross fault detection mode for safety input B Y2 terminal FB Reset mode T33 or T32 terminal Logical AND connection input mode Logical AND connection preset switch Switching Function Switching Function setting switch AND UA, UB 70 Item G9SX USER'S GUIDE Setting position Indicator status Setting mode Setting status Lit Enabled Y1 = open Not lit Disabled Y1 = 24 VDC Lit Enabled Y2 = open Not lit Disabled Y2 = 24 VDC Manual reset mode T33 = 24 VDC Auto reset mode T32 = 24 VDC Lit Not lit Lit Enabled "AND" Not lit Disabled "OFF" Lit Not lit Manual switching Auto switching "Manual" "Auto" Section 4 Ratings and Specifications 1. Ratings 72 1-2 Non-contact Door Switch Controller 73 1-3 Safety Guard Switching Unit 74 1-4 Expansion Unit 75 76 2-1 Advanced Unit/Basic Unit 76 2-2 Non-contact Door Switch Controller 77 2-3 Safety Guard Switching Unit 78 2-4 Expansion Unit 79 3. Dimensions and Terminal arrangements Ratings and Specifications 2. Characteristics 4 72 Section 1-1 Advanced Unit/Basic Unit 80 3-1 Advanced Unit 80 3-2 Basic Unit 80 3-3 Non-contact Door Switch Controller 81 3-4 Safety Guard Switching Unit 81 3-5 Expansion Unit 82 G9SX USER'S GUIDE 71 1. Ratings 1-1 Advanced Unit/Basic Unit Power input Item Model G9SX-AD322-@/ADA222-@ Rated supply voltage 24 VDC Operating voltage range −15% to 10% of rated supply voltage Rated power consumption (See note.) 4 W max. G9SX-BC202-@ 3 W max. Note: Power consumption of loads not included. Inputs Item Model G9SX-AD322-@/ADA222-@ G9SX-BC202-@ Safety input Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kΩ (See note.) Feedback/reset input Note: Provide a current equal to or higher than that of the minimum applicable load of the connected input control device. Outputs Item Section 4 Ratings and Specifications 72 Model G9SX-AD322-@/ADA222-@ G9SX-BC202-@ Instantaneous safety output (See note 1.) OFF-delayed safety output (See note 1.) P channel MOS FET transistor output P channel MOS FET transistor output Load current: Load current: Using 2 outputs or less: 1 A DC max. (See note 2.) Using 1 output: 1 A DC max. (See note 2.) Using 3 outputs or more: 0.8 A DC max. Using 2 outputs: 0.8 A DC max. Auxiliary output PNP transistor output Load current: 100 mA max. Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis. When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below. Approx. 100 ms ON OFF 360 µs max. 2. The following derating is required when Units are mounted side-by-side. G9SX-AD322-@/G9SX-ADA222-@/G9SX-BC202-@: 0.4 A DC max. load current G9SX USER'S GUIDE 1. Ratings 1-2 Non-contact Door Switch Controller Power input Item Model G9SX-NS202-@ Rated supply voltage 24 VDC Operating voltage range −15% to 10% of rated supply voltage Rated power consumption (See note.) 3 W max. G9SX-NSA222-T03-@ 4 W max. Note: Power consumption of loads not included. Inputs Item Model G9SX-NS202-@/G9SX-NSA222-T03-@ Safety input (See note 1.) Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8kΩ (See note 2.) Feedback/reset input Note: 1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Door Switch. 2. Provide a current equal to or higher than that of the minimum applicable load of the connected input control device. Outputs Item Model G9SX-NS202-@/G9SX-NSA222-T03-@ Auxiliary output PNP transistor output Load current: 100 mA max. 4 P channel MOS FET transistor output Load current: 0.8 A DC max. (See note 2 and 3.) Section Instantaneous safety output (See note 1.) OFF-delayed safety output (See note 1.) Approx.100 ms ON OFF 360 µs max. 2. The following derating is required when Units are mounted side-by-side. G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A DC max. load current 3. Apply the following rated load conditions for inductive loads. IEC/EN 60947-5-1 DC13: 0.8 A UL508 Pilot Duty: 0.5 A G9SX USER'S GUIDE Ratings and Specifications Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis. When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below. 73 1. Ratings 1-3 Safety Guard Switching Unit Power Input Item Model G9SX-GS226-T15-@ Rated supply voltage 24 VDC Operating voltage range −15% to 10% of rated supply voltage Rated power consumption (See note.) 5 W max. Note: Power consumption of loads not included. Inputs Item Model G9SX-GS226-T15-@ Safety inputs Mode selector input Operating voltage: 20.4 VDC to 26.4 VDC, Internal impedance: Approx. 2.8 kΩ (See note.) Feedback/reset input Note: Provide a current equal to or higher than that of the minimum applicable load of the connected input control device. Outputs Item Model Section Instantaneous safety outputs (See note 1.) OFF-delayed safety outputs (See note 1.) P channel MOS FET transistor outputs Load current: 0.8 A DC max. (See note 2 and 3.) Auxiliary outputs PNP transistor outputs (for input, output, and error monitoring) Load current: 100 mA max. 4 External indicator outputs Ratings and Specifications 74 G9SX-GS226-T15-@ P channel MOS FET transistor outputs Connectable indicators • Incandescent lamp: 24 VDC, 3 to 7 W • LED lamp: 10 to 300 mA DC Note: 1. While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis. When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below. Approx.100 ms ON OFF 360 µs max. 2. The following derating is required when Units are mounted side-by-side. G9SX-GS226-T15-@: 0.4 A DC max. load current 3. Apply the following rated load conditions for inductive loads. IEC/EN 60947-5-1 DC13: 0.8 A UL508 Pilot Duty: 0.5 A G9SX USER'S GUIDE 1. Ratings 1-4 Expansion Unit Power Input Item Model G9SX-EX-@ Rated supply voltage 24 VDC Operating voltage range −15% to 10% of rated supply voltage Rated power consumption (See note.) 2 W max. Note: Power consumption of loads not included. Outputs Item Model G9SX-EX-@ Rated load 250 VAC, 3 A / 30 VDC, 3 A (resistive load) Rated carry current 3A Maximum switching voltage 250 VAC, 125 VDC Section 4 Ratings and Specifications G9SX USER'S GUIDE 75 2. Characteristics 2-1 Advanced Unit/Basic Unit Item Model G9SX-AD322-@/ADA222-@ G9SX-BC202-@ Over-voltage category (IEC/EN 60664-1) II Operating time (OFF to ON state) (See note 1.) 50 ms max. (Safety input: ON) (See note 2.) 100 ms max. (Logical AND connection input: ON) (See note 3.) Response time (ON to OFF state) (See note 1.) 15 ms max. ON-state residual voltage 3.0 V max. (safety output, auxiliary output) OFF-state leakage current 0.1 mA max. (safety output, auxiliary output) Maximum wiring length of safety input and logical AND input 100 m max. (External connection impedance: 100 Ω max. and 10 nF max.) Reset input time (Reset button pressing time) 100 ms min. Accuracy of OFF-delay time Within ± 5% of the set value Insulation resistance 4 Ratings and Specifications Section Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected 500 VAC for 1 min together Vibration resistance --- 20 MΩ min. (at 100 VDC) Between all terminals connected together and DIN rail Shock resistance --- Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected 20 MΩ min. (at 100 VDC) together Between all terminals connected together and DIN rail Dielectric strength 50 ms max. (Safety input: ON) --- 500 VAC for 1 min Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) Destruction 300 m/s2 Malfunction 100 m/s2 Ambient temperature −10 to 55°C (no icing or condensation) Ambient humidity 25% to 85% Terminal tightening torque (See note 4.) 0.5 N·m Weight Approx. 200 g Approx. 125 g Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response times, respectively, of all the Units connected by logical AND. 2. Represents the operating time when the safety input turns ON with all other conditions set. 3. Represents the operating time when the logical AND input turns ON with all other conditions set. 4. For the G9SX-@-RT (with screw terminals) only. 76 G9SX USER'S GUIDE 2. Characteristics 2-2 Non-contact Door Switch Controller Item Model Over-voltage category (IEC/EN 60664-1) Operating time (OFF to ON state) (See note 1.) Response time (ON to OFF state) (See note 1.) G9SX-NS202-@ G9SX-NSA222-T03-@ 100 ms max. (Logical AND connection input ON and Non-contact Door Switch input ON) 50 ms max. (Safety input: ON) (See note 2.) 100 ms max. (Logical AND connection input ON and Non-contact Door Switch input ON) (See note 3.) 15 ms max. (Logical AND connection input: OFF) 15 ms max. (Safety input OFF and logical AND connection input OFF) 20 ms max. (Non-contact Door Switch input OFF) 20 ms max. (Non-contact Door Switch input: OFF) (See note 4.) (See note 4.) II ON-state residual voltage 3.0 V max. (safety output, auxiliary output) OFF-state leakage current 0.1 mA max. (safety output, auxiliary output) Maximum wiring length of safety input, logical AND connection input, and Noncontact Door Switch input 100 m max. (External connection impedance: 100 Ω max. and 10 nF max.) Reset input time (Reset button pressing time) 100 ms min. Accuracy of OFF-delay time Within ±5% of the set value Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected 20 MΩ min. (at 100 VDC) together Section 4 Insulation resistance --- Ratings and Specifications Between all terminals connected together and DIN rail Dielectric strength Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected 500 VAC for 1 min. together Between all terminals connected together and DIN rail Vibration resistance Shock resistance 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) Destruction 300 m/s2 Malfunction 100 m/s2 Ambient operating temperature −10 to 55°C (no icing or condensation) Ambient operating humidity 25% to 85% Terminal tightening torque (See note 5.) 0.5 N·m Weight Approx. 125 g Approx. 200 g Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response times, respectively, of all the Units connected by logical AND. 2. Represents the operating time when the safety input turns ON with all other conditions set. 3. Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set. 4. The fault detection time for 24-V short-circuit faults on the non-contact door switch input is 35 ms max. When calculating the safe distance for applications other than as door switches, use a fault detection time of 35 ms. 5. For the G9SX-@-RT (with screw terminals) only. G9SX USER'S GUIDE 77 2. Characteristics 2-3 Safety Guard Switching Unit Item Model G9SX-GS226-T15-@ Overvoltage category (IEC/EN 60664-1) II Operating time (OFF to ON state) (See note 1.) 50 ms max. (Safety input: ON) (See note 2.) 100 ms max. (Logical AND connection input: ON) (See note 3.) Response time (ON to OFF state) (See note 1.) 15 ms max. Allowable switching time for mode selector input (See notes 4 and 6.) 450 ms max. Response time for switching operating modes (See notes 5 and 6.) 50 ms max. ON-state residual voltage 3.0 V max. for safety outputs, auxiliary outputs, and external indicator outputs OFF-state leakage current 0.1 mA max. for safety outputs and auxiliary outputs, 1 mA max. for external indicator outputs Maximum wiring length of safety input and logical AND input 100 m max. (External connection impedance: 100 Ω max. and 10 nF max.) Reset input time (Reset button pressing time) 100 ms min. Accuracy of OFF-delay time Within ± 5% of the set value Section Insulation resistance Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together 20 MΩ min. (at 100 VDC) 4 Between all terminals connected together and DIN rail Ratings and Specifications Dielectric strength Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together 500 VAC for 1 min Between all terminals connected together and DIN rail Vibration resistance Shock resistance Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) Destruction 300 m/s2 Malfunction 100 m/s2 Ambient operating temperature −10 to 55°C (with no icing or condensation) Ambient operating humidity 25% to 85% Terminal tightening torque (See note 7.) 0.5 N·m Weight Approx. 240 g Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response times, respectively, of all the Units connected by logical AND. 2. Represents the operating time when the safety input turns ON with all other conditions set. 3. Represents the operating time when the logical AND input turns ON with all other conditions set. 4. This is the allowable switching time for the operating mode selector. If switching takes more than 450 ms, the G9SX-GS@ will detect an error. 5. This is the time required for the safety input to actually switch to an activated condition after the mode selector input is switched. <When M2 Is Turned ON after M1 Is Turned OFF> <When M1 Is Turned OFF after M2 Is Turned ON> 450 ms max. M1 450 ms max. M1 M2 M2 50 ms max. UA UA Safety input B is activated UB Safety input A is activated 6. Only when the G9SX-GS@ is used with manual switching. 7. For the G9SX-@-RT (with screw terminals) only. 78 G9SX USER'S GUIDE 50 ms max. UB Safety input B is activated Safety input A is activated 2. Characteristics 2-4 Expansion Unit Item Model G9SX-EX-@ Overvoltage category (IEC/EN 60664-1) II (Safety relay outputs 13 to 43 and 14 to 44: III) Operating time (OFF to ON state) (See note 1.) 30 ms max. (See note 2.) Response time (ON to OFF state) (See note 1.) 10 ms max. (See note 2.) ON-state residual voltage 3.0 V max. for safety outputs and auxiliary outputs OFF-state leakage current 0.1 mA max. for safety outputs and auxiliary outputs Maximum wiring length of safety input and logical AND input 100 m max. (External connection impedance: 100 Ω max. and 10 nF max.) Reset input time (Reset button pressing time) 100 ms min. Accuracy of OFF-delay time (See note 3.) Within ± 5% of the set value Insulation resistance Between all terminals connected together and DIN rail Between all terminals connected together and DIN rail 1,200 VAC for 1 min Between different poles of outputs Section Dielectric strength 100 MΩ min. (at 500 VDC) Shock resistance Frequency: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) Destruction 300 m/s2 Malfunction 100 m/s2 Electrical 100,000 cycles min. (rated load, switching frequency: 1,800 cycles/hour) Mechanical 5,000,000 cycles min. (switching frequency: 7,200 cycles/hour) Durability Ambient operating temperature −10 to 55°C (with no icing or condensation) Ambient operating humidity 25% to 85% Terminal tightening torque (See note 4.) 0.5 N·m Weight Approx. 165 g Ratings and Specifications Vibration resistance 4 Between safety relay outputs connected together and 2,200 VAC for 1 min other terminals connected together Note: 1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response times, respectively, of all the Units connected by logical AND. 2. This does not include the operating time or response time of Safety Guard Switching Units (G9SX-AD/-ADA/-NSA/-GS) that are connected. 3. This does not include the operating time or response time of internal relays in the G9SX-EX-@. 4. For the G9SX-@-RT (with screw terminals) only. G9SX USER'S GUIDE 79 3. Dimensions and Terminal arrangements Note: All units are in millimeters unless otherwise indicated. 3-1 Advanced Unit G9SX-AD322-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 T11 T12 Y1 X1 X2 A1 T31 T32 T33 T11 T12 Y1 X1 X2 A1 G9SX-AD322-T15 24VDC PWR FB T1 T2 100 max. AND EI 0.7 0.6 0.5 0.4 0.3 0.2 PWR FB T1 T2 AND ED 1 1.5 2 0 15 3 4 5 7 10 EI ERR ED ERR No. OFF-DELAY T21 T22 T41 T42 S14 S24 S34 S44 S54 A2 L1 T21 T22 T41 T42 A2 S14 S24 S34 S44 S54 L1 35.5 max. (35)* (10) * Typical dimension 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. G9SX-ADA222-@ Section (6) (See note 2.) Terminal arrangement T31 T32 T33 T51 T52 T11 T12 Y1 X1 X2 A1 4 Ratings and Specifications AND1 AND2 G9SX-ADA222-T150 T31 T32 T33 T51 T52 T11 T12 Y1 X1 X2 A1 G9SX-ADA222-T150 24VDC PWR FB T1 FB T1 T2 T2 100 max. AND1 AND2 EI 0.7 0.6 0.5 0.4 0.3 0.2 PWR ED 1 1.5 2 0 15 AND2 EI 3 4 5 7 10 AND1 ED ERR ERR No. OFF-DELAY T21 T22 T41 T42 S14 S24 S44 S54 L1 A2 L2 T21 T22 T41 T42 A2 S14 S24 S44 S54 L1 L2 35.5 max. (35)* * Typical dimension (10) 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. 3-2 Basic Unit G9SX-BC202-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 Y1 T11 T12 X1 A1 T31 T32 T33 Y1 T11 T12 X1 A1 G9SX-BC202 24VDC PWR FB T1 T2 EI ERR 100 max. PWR FB T1 T2 EI ERR No. T21 T22 X2 S14 S24 L1 A2 L2 T21 T22 X2 A2 S14 S24 L1 L2 23 max. (22.5)* * Typical dimension 80 G9SX USER'S GUIDE 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. 3. Dimensions and Terminal arrangements 3-3 Non-contact Door Switch Controller G9SX-NS202-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 D3 D1 D2 X1 A1 T31 T32 T33 D3 D1 D2 X1 A1 G9SX-NS202 24VDC PWR FB AND NS EI 100 max. PWR FB AND NS ERR EI ERR No. T41 T42 X2 S14 S24 L1 A2 D4 T41 T42 X2 A2 S14 S24 L1 D4 23 max. (22.5)* 115 max. * Typical dimension (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. G9SX-NSA222-T03-@ Terminal arrangement (6) (See note 2.) T11 T12 Y1 X1 X2 A1 D2 X2 D3 A1 FB T1 T2 AND NS EI ED 0.8 0.91.0 1.2 1.4 1.8 2.0 2.5 0 3.0 100 max. PWR FB T1 T2 AND NS EI ED ERR ERR No. OFF-DELAY T21 T22 T41 T42 S14 S24 S44 S54 L1 A2 D4 T21 T22 T41 T42 A2 S14 S24 S44 S54 L1 D4 35.5 max. (35)* * Typical dimension (10) 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. Ratings and Specifications 0.7 0.6 0.5 0.4 0.3 0.2 PWR 4 T31 T32 T33 D1 T11 T12 Y1 X1 G9SX-NSA222-T30 24VDC Section T31 T32 T33 D1 D2 D3 3-4 Safety Guard Switching Unit G9SX-GS226-T15-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 Y1 M1 M2 UA UB T11 T12 T61 T62 Y2 Y3 Y4 A1 T31 T32 T33 Y1 M1 M2 UA UB T11 T12 T61 T62 Y2 Y3 Y4 A1 G9SX-GS226-T15 PWR FB AND T1 UA T2 T6 UB T7 EI ED 24VDC PWR FB AND T1 UA T2 T6 UB T7 EI ED 1.5 2 3 0.7 1 4 0.6 5 0.5 7 0.4 10 0.3 0.2 0 15 100 max. ERR OFF-DELAY ERR No. T21 T22 T71 T72 T41 T42 L1 A2 X1 X2 X3 X4 S14 S24 S44 S54 T21 T22 T71 T72 T41 T42 L1 A2 X1 X2 X3 X4 S14 S24 S44 S54 45.5 max. (45)* * Typical dimension (10) 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. G9SX USER'S GUIDE 81 3. Dimensions and Terminal arrangements 3-5 Expansion Unit Expansion Unit G9SX-EX401-@ Expansion Unit (OFF-delayed Model) G9SX-EX041-T-@ Terminal arrangement G9SX-EX401-@ (Expansion Unit) G9SX-EX041-T-@ (Expansion Unit with OFF Delay) 13 23 33 43 13 23 33 43 PWR PWR EI ED ERR ERR (6) (See note 2.) G9SX-EX041-T 100 max. Section 23 max. (22.5)* * Typical dimension 4 Ratings and Specifications 82 G9SX USER'S GUIDE 115 max. (6) (See note 2.) Note: 1. Above outline drawing is for -RC terminal type. 2. For -RC terminal type only. A1 X2 A2 A1 X2 A2 14 24 34 44 14 24 34 44 Appendix 1. Troubleshooting 84 2. Logical AND Connections 91 3. Accessories and Related Products 93 Appendix G9SX USER'S GUIDE 83 1. Troubleshooting ■ Fault Detection When the G9SX detects a fault, the ERR indicator and/or other indicators light up or blink to inform the user about the fault. Check and take necessary measures referring to the following table, and then re-supply power to the G9SX. ■ Error Indications G9SX-BC202-@/G9SX-AD322-@/G9SX-ADA222-@ ERR indicator Other indicator --- Blinks T1 blinks T2 blinks Fault Check points and measures to take Page (1) Check the disturbance level around the G9SX and the related system. --- (2) Replace the G9SX. --- (1) Incorrect wiring of safety input 1. (For example, cross fault detection mode settings and safety input wiring do not match). (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input 1 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T11 and T12. --- Fault due to electro- (1) Affected by excessive electromagnetic disturbance. magnetic disturbance or of internal circuits (2) Failure of the G9SX internal circuit. Fault involved with safety input 1 Fault involved with safety input 2 (3) Check the wiring to T11, T12, T21 and (3) Short circuit between safety inputs (when cross fault detection mode is ON). T22. 63 (4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX. --- (1) Incorrect wiring of safety input 2. (For example, cross fault detection mode settings and safety input wiring do not match). (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input 2 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T21 and T22. --- (3) Short circuit between safety inputs (3) Check the wiring to T11, T12, T21 and (when cross fault detection mode is ON). T22. 63 Appendix (4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX. --- Fault involved with feedback/reset inputs (1) Incorrect feedback/reset input wiring. (1) Check the wiring to T31, T32 and T33. 62 Fault in Expansion Unit (2) Connecting cable to Expansion Unit or terminating connector disconnected. (2) Check the connecting cable to the Expansion Unit and the connection of the terminating connector. 69 (3) Voltage fluctuation caused by insufficient supply voltage current capacity. (3) Change to a power supply with a greater current capacity. --- (4) Supply voltage outside the rated value. (4) Connect to a supply voltage of 24 VDC -15% to +10%. --- (5) Failure in internal circuit for T31, T32 and T33. (5) Replace the G9SX. --- (6) Expansion Unit relay contact or internal circuit failed. (6) Replace the Expansion Unit. --- (1) Check the wiring to S14, S24 and S34. --- (2) Check the wiring to S14, S24 and S34. --- Lights FB blinks Expected causes of the fault Abnormal supply voltage to Expansion Unit Failure in internal circuit (1) Instantaneous safety outputs short circuited. Fault involved with instantaneous safety (2) Instantaneous safety outputs and 24 V, outputs 0 V, or another I/O terminal short circuited. EI blinks Fault involved with logical AND connection outputs (3) Logical AND connection outputs and 24 V, 0 V, or another I/O terminal short circuited. (3) Check the wiring to L1 and L2. --- Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 76 (5) Failure in internal circuit for S14, S24 and S34. (5) Replace the G9SX. --- (6) Failure in internal circuit for L1 and L2. (6) Replace the G9SX. --- Failure in internal circuit 84 G9SX USER'S GUIDE 1. Troubleshooting ERR indicator Other indicator Fault Expected causes of the fault Check points and measures to take (1) Safety OFF-delayed outputs short circuited. (1) Check the wiring to S44 and S54. --- (2) Wiring to the OFF-delayed safety contact outputs and 24 V, 0 V, or another I/O terminal short circuited. (2) Check the wiring to S44 and S54. --- Incorrect set values for OFF-delay time (3) Settings of two OFF-delay time preset switches are not the same. (3) Confirm the set values of the OFFdelay time preset switches on the front and back of the Unit. 65 Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 76 (5) Failure in internal circuit for S44 and S54. (5) Replace the G9SX. --- (6) OFF-delay time preset switch failed. (6) Replace the G9SX. --- Fault involved with OFF-delayed safety outputs ED blinks Failure in internal circuit (1) Logical AND connection input and 24 V, 0 V, or another I/O terminal short (1) Check the wiring to T41 and T51. circuited. Fault involved with logical AND connection input Lights Page AND blinks Incorrect setting for (AND1, logical AND AND2) connection setting switch Fault in internal circuit Supply voltage All indicators outside the rated except PWR value blink --- (2) Maximum cable length exceeded. (2) Make sure that the wiring length for the T41, T42, T51 and T52 terminals is less than 100 m. --- (3) Maximum number of connected Units exceeded. (3) Check the logical AND connection for the G9SX. 59 (4) The logical AND connection preset switch is set to OFF. (4) When using a logical AND connection, set the logical AND connection preset switch to AND. 57 (5) Failure in internal circuit for T41, T42, T51 and T52. (5) Replace the G9SX. --- (6) The logical AND connection preset switch failed. (6) Replace the G9SX. --- (1) Supply voltage outside the rated value. (1) Connect to a supply voltage of 24 VDC -15% to +10%. --- (2) Voltage fluctuation caused by insufficient supply voltage current capacity. (2) Change to a power supply with a greater current capacity. --- ERR indicator Other indicator Fault T1 Off T2 Blinks Mismatch between input 1 and input 2 Expected causes of the fault The input status between safety input 1 and safety input 2 is different due to a contact failure or short circuit of a safety input device or a wiring fault. Check points and measures to take Page Check the wiring from safety input devices to the G9SX. Or check the input sequence of safety input devices. After removing the fault, turn both safety input 1 and 2 to the OFF state. --- G9SX USER'S GUIDE Appendix When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table. 85 1. Troubleshooting G9SX-NS202-@/G9SX-NSA222-@ ERR indicator Other indicator --- Blinks T1 blinks T2 blinks Fault Fault involved with safety input 1 Fault involved with safety input 2 NS blinks Failure in internal circuit Appendix FB blinks Check points and measures to take Page (1) Check the disturbance level around the G9SX and the related system. --- (2) Replace the G9SX. --- (1) Incorrect wiring of safety input 1. (For example, cross fault detection mode settings and safety input wiring do not match). (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input 1 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T11 and T12. --- (3) Short circuit between safety inputs (when cross fault detection mode is ON). (3) Check the wiring to T11, T12, T21 and T22. 63 Fault due to electro- (1) Affected by excessive electromagnetic disturbance. magnetic disturbance or of internal circuits (2) Failure of the G9SX internal circuit. Fault in Non-contact Door Switch input Lights Expected causes of the fault (4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX. --- (1) Incorrect wiring of safety input 2. (For example, cross fault detection mode settings and safety input wiring do not match). (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input 2 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T21 and T22. --- (3) Short circuit between safety inputs (when cross fault detection mode is ON). (3) Check the wiring to T11, T12, T21 and T22. 63 (4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX. --- (1) Wiring to the Non-contact Door Switch input and 24 V or another I/O terminal short circuited. (1) Check the wiring to D1 and D2. 66 (2) Incorrect wiring of Non-contact Door Switch inputs in series connection. (2) Check the wiring to the D40A. 66 (3) Non-contact Door Switch failed. (3) Replace the D40A. --- (4) Failure in internal circuit for D1 and D2. (4) Replace the G9SX. --- Fault involved with feedback/reset inputs (1) Incorrect feedback/reset input wiring. (1) Check the wiring to T31, T32, and T33. 62 Fault in Expansion Unit (2) Connecting cable to Expansion Unit or terminating connector disconnected. (2) Check the connecting cable to the Expansion Unit and the connection of the terminating connector. 69 (3) Voltage fluctuation caused by insufficient supply voltage current capacity. (3) Change to a power supply with a greater current capacity. --- (4) Supply voltage outside the rated value. (4) Connect to a supply voltage of 24 VDC -15% to +10%. --- (5) Failure in internal circuit for T31, T32 and T33. (5) Replace the G9SX. --- (6) Expansion Unit relay contact or internal circuit failed. (6) Replace the Expansion Unit. --- (1) Check the wiring to S14 and S24. --- (2) Check the wiring to S14 and S24. --- Abnormal supply voltage to Expansion Unit Failure in internal circuit (1) Instantaneous safety outputs short circuited. Fault involved with instantaneous safety (2) Instantaneous safety outputs and 24 V, outputs 0 V, or another I/O terminal short circuited. EI blinks Fault involved with logical AND connection outputs (3) Logical AND connection outputs and 24 V, 0 V, or another I/O terminal short circuited. (3) Check the wiring to L1. --- Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 77 (5) Failure in internal circuit for S14 and S24. (5) Replace the G9SX. --- (6) Failure in internal circuit for L1. (6) Replace the G9SX. --- Failure in internal circuit 86 G9SX USER'S GUIDE 1. Troubleshooting ERR indicator Other indicator Fault Check points and measures to take Page (1) Safety OFF-delayed outputs short circuited. (1) Check the wiring to S44 and S54. --- (2) Wiring to the OFF-delayed safety contact outputs and 24 V, 0 V, or another I/O terminal short circuited. (2) Check the wiring to S44 and S54. --- Incorrect set values for OFF-delay time (3) Settings of two OFF-delay time preset switches are not the same. (3) Confirm the set values of the OFFdelay time preset switches on the front and back of the Unit. 65 Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 77 (5) Failure in internal circuit for S44 and S54. (5) Replace the G9SX. --- (6) OFF-delay time preset switch failed. (6) Replace the G9SX. --- Fault involved with OFF-delayed safety outputs ED blinks Failure in internal circuit Fault involved with logical AND connection input Lights Expected causes of the fault Incorrect setting for AND blinks logical AND connection setting switch Fault in internal circuit Supply voltage All indicators outside the rated except PWR value blink (1) Logical AND connection input and 24 V, 0 V, or another I/O terminal short (1) Check the wiring to T41. circuited. --- (2) Maximum cable length exceeded. (2) Make sure that the wiring length for the T41 and T42 terminals is less than 100 m. --- (3) Maximum number of connected Units exceeded. (3) Check the logical AND connection for the G9SX. 59 (4) The logical AND connection preset switch is set to OFF. (4) When using a logical AND connection, set the logical AND connection preset switch to AND. 57 (5) Failure in internal circuit for T41 and T42. (5) Replace the G9SX. --- (6) The logical AND connection preset switch failed. (6) Replace the G9SX. --- (1) Supply voltage outside the rated value. (1) Connect to a supply voltage of 24 VDC -15% to +10%. --- (2) Voltage fluctuation caused by insufficient supply voltage current capacity. (2) Change to a power supply with a greater current capacity. --- When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table. Other indicator Fault T1 Off T2 Blinks Mismatch between input 1 and input 2 Expected causes of the fault The input status between safety input 1 and safety input 2 is different due to a contact failure or short circuit of a safety input device or a wiring fault. Check points and measures to take Page Check the wiring from safety input devices to the G9SX. Or check the input sequence of safety input devices. After removing the fault, turn both safety input 1 and 2 to the OFF state. --- G9SX USER'S GUIDE Appendix ERR indicator 87 1. Troubleshooting G9SX-GS226-@ ERR indicator Other indicator --- Blinks T1 blinks T2 blinks T6 blinks Fault Fault due to electro- (1) Affected by excessive electromagnetic disturbance. magnetic disturbance or of internal circuits (2) Failure of the G9SX internal circuit. Fault involved with safety input A, channel 1 Fault involved with safety input A, channel 2 Fault involved with safety input B, channel 1 Lights Appendix T7 blinks FB blinks Fault involved with safety input B, channel 1 G9SX USER'S GUIDE Check points and measures to take Page (1) Check the disturbance level around the G9SX and the related system. --- (2) Replace the G9SX. --- (1) Incorrect wiring of safety input A channel 1. (For example, cross fault detection mode settings and safety input wiring do not match.) (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input A channel 1 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T11 and T12. --- (3) Short circuit between safety inputs (when cross fault detection mode is ON). (3) Check the wiring to T11, T12, T21 and T22. 63 (4) Failure in internal circuit for T11 and T12. (4) Replace the G9SX. --- (1) Incorrect wiring of safety input A channel 2. (For example, cross fault detection mode settings and safety input wiring do not match.) (1) Check the wiring to T11, T12, T21, T22 and Y1. 63 (2) Wiring to safety input A channel 2 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T21 and T22. --- (3) Check the wiring to T11, T12, T21 and (3) Short circuit between safety inputs (when cross fault detection mode is ON). T22. 63 (4) Failure in internal circuit for T21 and T22. (4) Replace the G9SX. --- (1) Incorrect wiring of safety input B channel 1. (For example, cross fault detection mode settings and safety input wiring do not match.) (1) Check the wiring to T61, T62, T71, T72 and Y2. 63 (2) Wiring to safety input B channel 1 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T61 and T62. --- (3) Check the wiring to T61, T62, T71 and (3) Short circuit between safety inputs (when cross fault detection mode is ON). T72. 63 (4) Failure in internal circuit for T61 and T62. (4) Replace the G9SX. --- (1) Incorrect wiring of safety input B channel 2. (For example, cross fault detection mode settings and safety input wiring do not match.) (1) Check the wiring to T61, T62, T71, T72 and Y2. 63 (2) Wiring to safety input B channel 2 and 24 V or another I/O terminal short circuited. (2) Check the wiring to T71 and T72. --- (3) Short circuit between safety inputs (3) Check the wiring to T61, T16, T71 and (when cross fault detection mode is ON). T72. 63 (4) Failure in internal circuit for T71 and T72. (4) Replace the G9SX. --- Fault involved with feedback/reset inputs (1) Incorrect feedback/reset input wiring. (1) Check the wiring to T31, T32, and T33. 62 Fault in Expansion Unit (2) Connecting cable to Expansion Unit or terminating connector disconnected. (2) Check the connecting cable to the Expansion Unit and the connection of the terminating connector. 69 (3) Voltage fluctuation caused by insufficient supply voltage current capacity. (3) Change to a power supply with a greater current capacity. --- (4) Supply voltage outside the rated value. (4) Connect to a supply voltage of 24 VDC -15% to +10%. --- (5) Failure in internal circuit for T31, T32 and T33. (5) Replace the G9SX. --- (6) Expansion Unit relay contact or internal circuit failed. (6) Replace the Expansion Unit. --- Abnormal supply voltage to Expansion Unit Failure in internal circuit 88 Expected causes of the fault 1. Troubleshooting ERR indicator Other indicator Fault Expected causes of the fault (1) Instantaneous safety outputs short circuited. Fault involved with instantaneous safety (2) Instantaneous safety outputs and 24 V, outputs 0 V, or another I/O terminal short circuited. EI blinks Page (1) Check the wiring to S14 and S24. --- (2) Check the wiring to S14 and S24. --- Fault involved with logical AND connection outputs (3) Logical AND connection outputs and 24 V, 0 V, or another I/O terminal short circuited. (3) Check the wiring to L1. --- Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 78 (5) Failure in internal circuit for S14 and S24. (5) Replace the G9SX. --- (6) Failure in internal circuit for L1. (6) Replace the G9SX. --- (1) Safety OFF-delayed outputs short circuited. (1) Check the wiring to S44 and S54. --- (2) Wiring to the OFF-delayed safety contact outputs and 24 V, 0 V, or another I/O terminal short circuited. (2) Check the wiring to S44 and S54. --- Incorrect set values for OFF-delay time (3) Settings of two OFF-delay time preset switches are not the same. (3) Confirm the set values of the OFFdelay time preset switches on the front and back of the Unit. 65 Abnormal ambient temperature (4) The environment exceeds the permissible ambient operating temperature. (4) Check the ambient temperature and spacing around the G9SX. 78 (5) Failure in internal circuit for S44 and S54. (5) Replace the G9SX. --- (6) OFF-delay time preset switch failed. (6) Replace the G9SX. --- Failure in internal circuit Fault involved with OFF-delayed safety outputs ED blinks Failure in internal circuit Lights Fault involved with logical AND connection input (1) Logical AND connection input and 24 V, 0 V, or another I/O terminal short (1) Check the wiring to T41. circuited. --- (2) Make sure that the wiring length for the T41 and T42 terminals is less than 100 m. --- (3) Maximum number of connected Units exceeded. (3) Check the logical AND connection for the G9SX. 59 (4) The logical AND connection preset switch is set to OFF. (4) When using a logical AND connection, set the logical AND connection preset switch to AND. 57 (5) Failure in internal circuit for T41 and T42. (5) Replace the G9SX. --- (6) The logical AND connection preset switch failed. (6) Replace the G9SX. --- (1) Wiring to the external indicator output and 24 V, 0 V, or another I/O terminal short circuited. (1) Check the wiring to UA. --- (2) External indicator output disconnected. (external indicator not connected) (2) Check the wiring to UA. 68 Failure of the external indicator (3) External indicator failed. (3) Replace the connected external indicator. --- Fault in the external indicator diagnosis switching input (4) Wiring for external indicator diagnosis switching input and 24 V disconnected. (when external indicator was not connected) (4) Check the wiring to Y3. 68 (5) Failure in internal circuit for UA. (5) Replace the G9SX. --- (6) Failure in internal circuit for Y3. (6) Replace the G9SX. --- Fault in internal circuit Fault in external indicator output Failure in internal circuit G9SX USER'S GUIDE Appendix (2) Maximum cable length exceeded. Incorrect setting for AND blinks logical AND connection setting switch UA blinks Check points and measures to take 89 1. Troubleshooting ERR indicator Other indicator Fault Page (1) Check the wiring to UB. --- (2) External indicator output disconnected. (external indicator not connected) (2) Check the wiring to UB. 68 Failure of the external indicator (3) External indicator failed. (3) Replace the external indicator. --- Fault in the external indicator diagnosis switching input (4) Wiring for external indicator diagnosis switching input and 24 V disconnected. (when external indicator was not connected) (4) Check the wiring to Y4. 68 Failure in internal circuit Fault involved with the Switching Function Lights Check points and measures to take (1) Wiring to the external indicator output and 24 V, 0 V, or another I/O terminal short circuited. Fault in external indicator output UB blinks Expected causes of the fault UA and UB alternately blink Mode selector error Failure in internal circuit Supply voltage All indicators outside the rated except PWR value blink (5) Failure in internal circuit for UB. (5) Replace the G9SX. --- (6) Failure in internal circuit for Y4. (6) Replace the G9SX. --- (1) Incorrect setting of the Switching Function setting switch or incorrect wiring to the mode selector input. (1) Check the wiring to the M1 and M2, and the setting of the Switching Function setting switch. 67 (2) Wiring to the mode selector input and 24 V, 0 V, or another I/O terminal short circuited. (2) Check the wiring to M1 and M2. 67 (3) Incorrect mode selector input switching time. (3) Check the mode selector input switching time. 78 (4) Mode selector failed. (4) Replace mode switch. --- (5) Internal circuit of the mode selector input failed. (5) Replace the G9SX. --- (1) Supply voltage outside the rated value. (1) Connect to a supply voltage of 24 VDC -15% to +10%. --- (2) Voltage fluctuation caused by insufficient supply voltage current capacity. (2) Change to a power supply with a greater current capacity. --- When indicators other than the ERR indicator blink, check and take necessary actions referring to the following table. ERR indicator Other indicator Fault Check points and measures to take Page Safety input A mismatch The input status between safety input A channel 1 and safety input A channel 2 is different due to contact failure or a short circuit of safety input device or a wiring fault. Check the wiring from safety input devices to the G9SX-GS@. Or check the input sequence of safety input devices. After removing the fault, turn both safety input A channels 1 and 2 to the OFF state. --- Safety input B mismatch The input status between safety input B channel 1 and safety input B channel 2 is different due to contact failure or a short circuit of safety input device or a wiring fault. Check the wiring from safety input devices to the G9SX-GS@. Or check the input sequence of safety input devices. After removing the fault, turn both safety input B channels 1 and 2 to the OFF state. --- Check points and measures to take Page T1 Appendix T2 Off Blinks T6 T7 Expected causes of the fault G9SX-EX401-@/G9SX-EX041-T-@ ERR indicator Other indicator --- Lights 90 G9SX USER'S GUIDE Fault Failure of the Expansion Unit Expected causes of the fault Internal safety relay contact is welded. Replace the G9SX-EX@. --- Internal circuit failed. Replace the G9SX-EX@. --- 2. Logical AND Connections The logical AND connection is used to build logic between multiple safety inputs and safety outputs. This technology is unique to the G9SX Series. ■ Logical AND Connection Signals Pulse signals are used in the G9SX logical AND connection and dynamic processing is used to monitor the signals. Information on safety between Units is passed by these pulse signals, which are also used to detect faults in the connection and short circuits. 24 VDC 24 VDC G9SX G9SX A1 A1 Internal circuit A2 Internal circuit L1 Logical AND connection signal A2 T41 T42 For this reason, up to safety category 4 can be achieved without redundant logical AND connection signal lines. ■ Insulation The logical AND connection input section of the G9SX is insulated. Therefore, even when the G9SX logical AND connection cable is configured across multiple devices, it is not necessary to use a shared power source. Device A Power supply A Appendix Unit A Device B Power supply B Unit B Logical AND connection Insulation provided here. G9SX USER'S GUIDE 91 2. Logical AND Connections ■ Simplifying Safety Circuits Safety circuits were traditionally built by combining relay contacts, but now the logical AND connections of the G9SX simplify building safety circuits. A safety system will be described in which the power is turned ON when safety input 1 and safety input 2 are simultaneously input. Previous Circuit with Relay Units Safety Input 1 Safety Input 2 (1) Internal circuit Unit 1 Feedback Input Internal circuit Unit 2 Feedback Input Motor controller KM1 KM2 M Robot Safety Circuit with G9SX Safety Input 1 Appendix Unit 1 Safety Input 2 Internal circuit Logical AND connection Internal circuit Unit 2 Feedback Input Section (1) in the above figure can be constructed with only 2 wires. Motor controller KM1 KM2 M Robot 92 G9SX USER'S GUIDE 3. Accessories and Related Products 3. Accessories and Related Products Accessories: Terminal Blocks Appearance (See note 1.) Specifications Applicable Units Terminal Block with screw terminals (3-pin) G9SX-AD-@-RT G9SX-ADA-@-RT G9SX-NSA-@-RT Terminal Block with screw terminals (4-pin) G9SX-BC-@-RT G9SX-EX-@-RT G9SX-NS-@-RT G9SX-GS-@-RT Terminal Block with Spring-cage Terminals (3-pin) G9SX-AD-@-RC G9SX-ADA-@-RC G9SX-NSA-@-RC Terminal Block with Spring-cage Terminals (4-pin) G9SX-BC-@-RC G9SX-EX-@-RC G9SX-NS-@-RC G9SX-GS-@-RC Model Remarks Y9S-03T1B-02A Set including two terminal blocks (black) with screw terminals and six code marks to prevent incorrect insertion. Y9S-04T1B-02A Set including two terminal blocks (black) with screw terminals and six code marks to prevent incorrect insertion. Y9S-03C1B-02A Set including two terminal blocks (black) with spring-cage terminals and six code marks to prevent incorrect insertion. Y9S-04C1B-02A Set including two terminal blocks (black) with spring-cage terminals and six code marks to prevent incorrect insertion. Note: 1. The illustrations show 3-pin models. 2. The G9SX comes with the terminal blocks attached. The accessories shown here can be ordered as replacements. Related Products Name Compact Safety Door Switch Compact Safety Limit Switch Compact Noncontact Door Switch/ Flexible Safety Unit Certified Body Safety Category D4NS • Lineup includes models with 3 contacts (DPST-NC + SPST-NO and TPST-NC models) in addition to the previous DPST-NC + SPST-NO and DPST-NC models. • Models with M12 connectors are available to save labor and simplify replacement work. • Standard-feature gold-clad contacts provide high contact reliability. Can be used with both standard loads and microloads. 4 D4NL • Built-in switches with four- or five-terminal contact construction are available. • Key holding force of 1,300 N minimum. • Can be used for either standard loads or microloads. • Lineup includes models with a conduit size of M20. • IP67 degree of protection. 4 D4N • Lineup includes models with 3 contacts (DPST-NC + SPST-NO and TPST-NC models) in addition to the previous DPST-NC + SPST-NO and DPST-NC models. • Models with M12 connectors are available to save labor and simplify replacement work. • Standard-feature gold-clad contacts provide high contact reliability. Can be used with both standard loads and microloads. 4 D40A/ G9SX-NS • Stable operation reduces Controller errors caused by unstable doors. • Connect up to 30 Non-contact Door Switches with LED indicators to one Controller. • Reversible switch provides flexibility in installation. • Two-color LED indicator enables easier maintenance by providing identification of door status and cable disconnections. • Both Non-contact Door Switches and conventional Key-type Safety-door Switches can be input to one Controller, saving space. 3 (EN954-1) SIL3 (IEC/EN 61508) Appearance G9SX USER'S GUIDE Appendix Compact Guard Lock Safety Door Switch Features Model 93 3. Accessories and Related Products Name Safety Light Curtain Emergency Stop Switch Emergency Stop Switch Appearance Features Safety Category F3SJ Ver.2 4 A165E • Same length as the 16-dia. Short-body A3B Switch and allows mounting or dismounting of the Switch Unit. • Operational Unit design remains the same as previous models. • Large terminals for easy wiring. • Switch Unit can be easily mounted or dismounted using a special tool. 4 A22E • Easy mounting or dismounting of the Switch Unit from the Operational Unit using a lever (provided). • Not only round or forked crimp terminals, but also solid wires can be connected to the Switch. • Safety lock mechanism provided for the first time for 22-dia. models. • Applicable to 22.3-dia. or 25-dia. panel cutouts. IP65 degree of protection. (However, also use A22Z-R25 for 25-dia. cutout) • Employs a three-tier terminal block (for lighted model) for easy wiring in narrow spaces. 4 • Sure click feel to ensure operation. • Easy configuration of safety circuits when combined with the G9SX-GS. 4 • For changing modes when using the manual switching function of the G9SX-GS. • Direct opening mechanism (NC contacts only). --- A4EG Key-type Selector Switch A22K G9SX USER'S GUIDE Certified Body • Conforms to EN and IEC standards and incorporates the highest level of safety design. • Can be front-mounted, top-mounted, or backmounted in series. • Finger, hand, or hand to body protection. • Sensing width of 245 to 2,500 mm. Enabling Grip Switch Appendix 94 Model Scheduled for release in autumn of 2007. Precautions Precautions G9SX USER'S GUIDE 95 Safety Precautions !WARNING <Precautions for All G9SX Models> Serious injury may possibly occur due to breakdown of safety outputs. Do not connect loads beyond the rated value to the safety outputs. Serious injury may possibly occur due to loss of required safety functions. Wire G9SX properly so that supply voltages or voltages for loads do NOT touch the safety inputs accidentally or unintentionally. Serious injury may possibly occur due to damages of safety inputs. Apply protection circuitry against back electromotive force in case connecting inductive loads to safety outputs. Serious injury may possibly occur due to loss of safety functions. Use devices appropriate for the application and the condition where G9SX is used. Control Devices Serious injury may possibly occur due to loss of safety functions. Construct an appropriate safety system as shown in the following table. Switching function Emergency Stop Switches Door interlocking switches or limit switches. Use approved devices with Direct Opening Mechanism complying with IEC/EN 609475-1 and capable of switching micro loads of 24VDC, 5mA. Safety Sensors Use approved devices complying with the relevant product standards, regulations and rules in the country where it is used. Consult a certification body to assess that the entire system satisfies the required safety category level. Precautions Relays with forcibly guided contacts Use approved devices with forcibly guided contacts complying with EN 50205. For feedback purpose use devices with contacts capable of switching micro loads of 24VDC, 5mA. Contactors Use contactors with forcibly guided mechanism to input the signal to Feedback/ Reset input of G9SX through the NC contact of the contactor. For feedback purpose use devices with contacts capable of switching micro loads of 24VDC, 5mA. Failure to open contacts of a contactor cannot be detected by monitoring its auxiliary NC contact without forcibly guided mechanism. Safety system configuration example G9SX USER'S GUIDE Safety Sensor A Area A Safety Sensor B Person Safety precautions (1) Select Safety Sensors that satisfy the following condition: 1. Diameter of the smallest detectable object < Diameter of the object to be detected. (2) Install the Safety Sensors so that they satisfy the following conditions: 1. Use Safety Sensor A to detect the entry of the machine into area A, and Safety Sensor B to detect the entry of a person into area A. 2. Make sure that the machine can reach area A only by passing through Safety Sensor A, and that a person can reach area A only by passing through Safety Sensor B. (3) Provide a protective structure to prevent a person from passing completely through Safety Sensor B and stepping into area A. If this is not possible, install a sensor that will detect the presence of a person inside area A and prevent the machine from being restarted while the person is inside area A. (4) Provide a sufficient safety distance (S1) considering the entry speed of a person and a sufficient safety distance (S2) considering the entry speed of the machine. For details, refer to Safety Distance on page 97. Switching function Manual switching Machine Safety system configuration example Safety Sensor Area A Mode selector Safety Door Switch Safety Limit Switch Person Evaluate whether devices used are appropriate to satisfy the requirements of safety category level. Safety precautions 96 Auto switching Machine Requirements Use approved devices with Direct Opening Mechanism complying with IEC/EN 609475-1. Do not connect an Emergency Stop Switch to the G9SX-GS@. Other devices <G9SX-GS@> (1) Select Safety Sensors that satisfy the following condition: 1. Diameter of the smallest detectable object < Diameter of the object to be detected. (2) Install the Safety Sensors so that they satisfy the following conditions: 1. Use the Safety Sensor to detect the entry of the machine into area A. 2. Make sure that the machine can reach area A only by passing through the Safety Sensor. (3) Provide a protective structure to prevent a person from stepping into area A when the door is opened. If this is not possible, install a sensor that will detect the presence of a person inside area A and prevent the machine from being restarted while the person is inside area A. (4) Provide a sufficient safety distance (S2) considering the entry speed of the machine. For details, refer to Safety Distance on page 97. (5) Position the mode selector in a location where it cannot be operated from inside area A. Safety Precautions Safety Distance The safety distance is the minimum distance that must be provided between the safety input device and a machine's hazardous part to stop the hazardous part before a person or object reaches it. The safety distance varies according to the standards of each country and the specifications of each machine. In addition, the calculation of the safety distance differs if the direction of approach is not perpendicular to the detection zone of the safety input device. Always refer to the relevant standards. Safety Distance Concepts ( 1 ) To determine the approach speed K1, consider all factors, including the operator's physical abilities. ( 2 ) To determine the maximum approach speed K2, consult with a notified body or other authoritative institutes. ( 3 ) The response time of a machine is the time from when the machine receives a stop signal to the time when the machine's hazardous part stops. Measure the response time on the actual system. Also, periodically check that the machine's response time has not changed. ( 4 ) For information on the response time of the G9SX system, refer to item 10 of Precautions for Correct Use on page 98. ■ Precautions for Safe Use Machine <Precautions for All G9SX Models> Safety Sensor A P1 When a person approaches a hazard (machine) Area A S1 Safety Sensor B Person • S1: Safety distance 1 • P1: The closest that a machine can come to a person while operating (the boundary of the machine's operating area) Machine Safety Sensor A When a hazard (machine) approaches a person S2 Area A P2 Safety Sensor B Person • S2: Safety distance 2 • P2: The closest that a part of a person can come to a machine. Safety Distance Calculation Examples (Reference) S1: S2: K1: K2: T: C: Safety distance 1 Safety distance 2 Approach speed of a person to the detection zone (area A) Maximum approach speed of a machine to the detection zone (area A) Total response time of the machine and G9SX system Additional distance calculated by the detection capability (the diameter of the smallest detectable object) of the Safety Sensor. If a person approaches the detection zone perpendicularly, calculate the safety distance as shown below. S1 = K1 × (Ts + Tc + Tr + Tbm) + Dpf S2 = K2 × (Ts + Tc + Tr + Tbm) + Dpf Calculating the safety distance specified by American standard ANSI B11.19 S1: S2: K1: Safety distance 1 Safety distance 2 Approach speed of a person to the detection zone (area A) K2: Maximum approach speed of a machine to the detection zone (area A) Ts: Machine's stop time (s) Tr: Response time of the G9SX system from ON to OFF (s) Tc: Machine control circuit's maximum response time required to activate its brake (s) Tbm: Additional time (s) Dpf: Additional distance G9SX USER'S GUIDE Precautions Calculating the safety distance specified by international standard ISO 138552002 (European standard EN 9991999) If a person approaches the detection zone perpendicularly, calculate the safety distance as shown below. S1 = K1 × T + C S2 = K2 × T + C ( 1 ) Use G9SX within an enclosure with IP54 protection or higher of IEC/EN60529. ( 2 ) Incorrect wiring may lead to loss of safety function. Wire conductors correctly and verify the operation of G9SX before commissioning the system in which G9SX is incorporated. ( 3 ) Do not apply DC voltages exceeding the rated voltages, or any AC voltages to the G9SX power supply input. ( 4 ) Use DC supply satisfying requirements below to prevent electric shock. • DC power supply with double or reinforced insulation, for example, according to IEC/EN60950 or EN50178 or a transformer according to IEC/EN61558. • DC supply satisfies the requirement for class 2 circuits or limited voltage/current circuit stated in UL 508. ( 5 ) Apply properly specified voltages to G9SX inputs. Applying inappropriate voltages cause G9SX to fail to perform its specified function, which leads to the loss of safety functions or damages to G9SX. ( 6 ) Auxiliary error outputs and auxiliary monitoring outputs are NOT safety outputs. Do not use auxiliary outputs as any safety output. Such incorrect use causes loss of safety function of G9SX and its relevant system. Also Logical AND connection outputs can only be used for logical AND connections between G9SXs. ( 7 ) After installation of G9SX, qualified personnel should confirm the installation, and should conduct test operations and maintenance. The qualified personnel should be qualified and authorized to secure the safety on each phases of design, installation, running, maintenance and disposal of system. ( 8 ) A person in charge, who is familiar to the machine in which G9SX is to be installed, should conduct and verify the installation. ( 9 ) Perform daily and 6-month inspections on the G9SX. Otherwise, the system may fail to work properly, resulting in serious injury. (10) Do not dismantle, repair, or modify G9SX. It may lead to loss of its safety functions. (11) Use only appropriate components or devices complying with relevant safety standards corresponding to the required level of safety categories. Conformity to requirements of safety category is determined as an entire system. It is recommended to consult a certification body regarding assessment of conformity to the required safety level. (12) OMRON shall not be responsible for conformity with any safety standards regarding to customer's entire system. (13) Disconnect G9SX from power supply when wiring, to prevent electric shock or unexpected operation. Doing so may lead to the loss of its safety functions. (14) Be cautious not to have your fingers caught when attaching terminal sockets to the plugs on G9SX. (15) Do not use in combustible gases or explosive gases. 97 Safety Precautions <G9SX-GS@> ( 1 ) Be sure to correctly connect safety input devices to safety input A and safety input B to ensure proper operation of the safety functions. ( 2 ) When setting the Switching Function, be sure to consider safety control requirements, safety level and safety category of the entire system. ( 3 ) A qualified personnel who has a thorough understanding of the installed machine must switch the mode selector input. For example, a Switching Unit with Key must be used for the mode selector, and the key must be managed and used in such a way that the machine cannot be operated by unauthorized persons. ( 5 ) Wiring 1. G9SX • Wire the G9SX as described below. <G9SX-EX@> ( 1 ) The durability of relays depend greatly on the switching condition. Confirm the actual conditions of operation in which the relay will be used in order to make sure of the permissible number of switching operations. (6) ■ Precautions for Correct Use <Precautions for All G9SX Models> Precautions ( 1 ) Handle with care Do not drop G9SX to the ground or expose to excessive vibration or mechanical shocks. G9SX may be damaged and may not function properly. ( 2 ) Conditions of storage Do not store in such conditions stated below. 1. In direct sunlight 2. At ambient temperatures out of the range of −10 to 55°C. 3. At relative humidity out of the range of 25% to 85% or under such temperature change that causes condensation. 4. In corrosive or combustible gases 5. With vibration or mechanical shocks out of the rated values. 6. Under splashing of water, oil, chemicals 7. In the atmosphere containing dust, saline or metal powder. G9SX may be damaged and may not function properly. ( 3 ) Mounting Mount G9SX to DIN track with attachments (PFP-M, not incorporated to this product), not to drop off the track by vibration or other force especially when the length of DIN track is short compared to the widths of G9SX. ( 4 ) Following spacing around G9SX should be available to apply rated current to outputs of G9SX and for enough ventilation and wiring: 1. At least 25 mm beside side faces of the G9SX. 2. At least 50 mm above top face of G9SX and below bottom face of G9SX. (7) (8) (9) (10) 50 mm min. T31 T32 T33 D1 D2 X1 D3 A1 G9SX-NS202 24VDC T31 T32 T33 Y1 M1 M2 UA UB T11 T12 T61 T62 Y2 Y3 Y4 A1 13 G9SX-GS226-T15 G9SX-EX401-T 24VDC 24VDC PWR PWB T1 FB AND NS EI ERR T6 EI 1.5 2 3 0.7 1 4 0.6 5 0.5 7 0.4 10 0.3 0.2 0 15 OFF-DELAY No. T41 T42 S14 S24 25 mm min. X2 L1 A2 D4 FB AND UA T2 UB T7 23 33 43 13 33 43 PWR ED ED ERR ED 23 G9SX-EX401-T 24VDC PWR ERR ERR No. T21 T22 T71 T72 T41 T42 L1 A2 X1 X2 X3 X4 S14 S24 S44 S54 No. 14 A1 24 X2 34 No. A2 44 14 A1 24 X2 34 A2 44 25 mm min. 50 mm min. (11) 98 G9SX USER'S GUIDE Solid wire 0.2 to 2.5 mm2 (AWG24 to AWG12) Stranded wire 0.2 to 2.5 mm2 (AWG24 to AWG12) • Strip no more than 7 mm of insulation from the end of the wire. • It is recommended that stranded wire be covered with insulated 0.25- to 2.5-mm2 ferrules before connecting it. 2. G9SX-@-RT (with Screw Terminals) • Tighten each screw to 0.5 to 0.6 N·m or the G9SX-@RT may malfunction or generate heat. 3. Wiring for a Logical AND Connection • Use a 2-conductor cabtire cable or shielded cable to wire a logical AND connection between Units. Connecting Expansion Units (G9SX-EX@-@): (Only G9SX-AD@/-ADA@/-NSA@/-GS@) 1. Remove the termination connector from the G9SX, and insert the connector of the Expansion Unit into the G9SX to connect it. 2. Insert the termination connector into the last Expansion Unit as viewed from the G9SX. When the G9SX is used without any Expansion Units, do not remove the termination connector from the G9SX. 3. Do not remove the termination connector while the system is operating. 4. Before applying the power supply voltage, confirm that the connecting sockets and plugs are locked. 5. Make sure that all connected Expansion Units are supplied with power within 10 s after the power to the G9SX is turned ON. Otherwise, the G9SX will detect a power supply error for the Expansion Units. Use cables with length less than 100m to connect to Safety Inputs, Feed-back/Reset inputs, or between Logical AND connection inputs and Logical AND connection outputs, respectively. Set the time duration of OFF-delay to an appropriate value that does not cause the loss of safety function of system. Logical AND connection between Units: 1. When using Logical AND connection inputs, set the Logical AND connection preset switch to 'AND' position for the units which the logical AND connection signal are input to. 2. Connect Logical AND connection outputs appropriately to Logical AND connection inputs of the relevant unit. Verify the operation of G9SX before commissioning the system. 3. When configuring the safety related system, be sure to consider that the delay of response time caused by logical AND connections do not degrade the safety function of the system. 4. Use 2-conductor cabtire cable or shielded cable for logical AND connections between Units. To determine the safety distance to hazards, take into account the delay of safety outputs caused by the following times: 1. Response time of safety inputs 2. Response time of logical AND connection input (Also consider the precaution in "Note" below) 3. Preset OFF-delay time 4. Accuracy of OFF-delay time Note: When connecting multiple Units with logical AND connections, the operating time and response time after logical AND connection inputs will be the sum of the operating times and response times of the Units that are connected in series by logical AND connections. Start entire system after more than 5s have passed since applying supply voltage to all G9SXs in the system. Safety Precautions (12) Power Supply 1. The G9SX may malfunction due to electromagnetic disturbances. Be sure to connect terminal A2 to ground. 2. When sharing a power supply with a Safety Light Curtain, use a power supply that will not fail for a momentary power interruption of 20 ms or less. (13) Devices connected to G9SX may operate unexpectedly. When replacing G9SX, disconnect it from power supply. (14) Adhesion of solvent such as alcohol, thinner, trichloroethane or gasoline on the product should be avoided. Such solvents make the marking on G9SX illegible and cause deterioration of parts. <G9SX-NS/-NSA, D40A> For details, refer to D40A/G9SX-NS catalog (Cat. No. C160). ( 1 ) Connection with Non-contact Door Switch Wire conductors between the G9SX-NS@ and the D40A Non-contact Door Switch correctly and verify operation, before using the system. ( 2 ) The D40A must be used with a designated actuator and G9SX-NS@ Controller. ( 3 ) Use cables with a length of less than 100 m total to connect D40A Switches. (11) Check that the machine is stopped whenever the interlocked guard door is open. (12) Do not mount the switch and actuator on magnetic materials, otherwise it may affect the operating distance. Below are reference values of the effect to the operating distance. Distance from surface of magnetic material Operating distance 0 to 5 mm Decrease to approx. 90% of rated value. > 5 mm No effect (13) Tighten all screws to the specified torque by using nonmagnetic M4 screws and washer for the installation of the switch and actuator. After installation and using, the actuator and switch fixing screws must be coated with tamper proof varnish or similar compound. Using anaerobic locking compounds can have a detrimental effect on the plastic switch case if the compounds come into contact with the switch case. Actuator Total wiring length 100 m max. D1 D2 D3 D4 G9SX-NS202-@ G9SX-NSA222-T03-@ Switch (14) Wiring 1. Use the following to wire to the product. Stranded wire (flexible wire): 0.2 to 2.5 mm2 (AWG24 to AWG12) Solid wire (steel wire): 0.2 to 2.5 mm2 (AWG24 to AWG12) 2. When an auxiliary output is not used, cut off the wiring and cover it with tape so that it does not contact other terminals. <G9SX-GS> ( 1 ) Use a mode selector that has an SPST-NO + SPST-NC contact form (e.g., OMRON's A22K-@-11). Precautions ( 4 ) Disconnect the G9SX-NS@ from the power supply when replacing the D40A. Devices connected to the G9SX-NS@ may operate unexpectedly. ( 5 ) Do not use the D40A in a magnetic field of 1.5 mT or higher. The D40A may not function properly. ( 6 ) Do not use the D40A in the water or in an environment continuously exposed to water. Water may penetrate into the D40A. (The IP67 degree of protection for this switch means that it has been checked for penetration of water after having been left in water for a fixed period of time.) ( 7 ) Be sure to mount a guard stopper and guide to prevent the D40A Non-contact Door Switch from being subjected to impact. ( 8 ) Do not use the switch or actuator as a stopper. Protect the switch and the actuator by installing a stopper. Separate the switch and the actuator to a distance of 1 mm or more. ( 9 ) Install the actuator and switch at an appropriate distance so that they do not create a gap that provides access to the hazard. (10) Where two or more Switches are mounted side-by-side, they must be no closer than 25 mm. 25 mm min. G9SX USER'S GUIDE 99 Safety Precautions ■ Category of EN 954-1 In the condition shown in Application Examples, G9SX can be used for the corresponding categories up to category 4. This does NOT mean that G9SX can always be used for required category under all the similar conditions and situations. Conformity to the categories must be assessed as a whole system. When using G9SX for safety categories, be sure to confirm the conformity as a whole system. To conform with Safety Category 4 (EN954-1) When using Non-contact Door Switch D40A/G9SX-NS@, the system can be used for the corresponding categories up to category 3. 1. Input the signals to both of the safety inputs (T11-T12, T21-T22, T61-T62 and T71-T72). 2. Input a signal to the safety inputs (T11-T12, T21-T22, T61-T62 and T71-T72) through switches with Direct Opening Mechanism. When using Limit Switches, at least one of them must have Direct Opening Mechanism. 3. When connecting Safety sensor with G9SX, use TYPE 4 safety sensor. 4. Input the signal through a NC contact of the contactor to Feedback/Reset input (T31-T32 for manual reset or T31-T33 for auto reset). (Refer to Application Examples) 5. Keep Cross fault detection mode input (Y1 and Y2) open. However, when connecting devices with self-diagnosis function, such as safety sensors, apply 24VDC to Y1 and Y2. 6. Be sure to Connect A2 to ground. 7. When using a G9SX-EX-@-@ Expansion Unit, connect fuses with a current rating of 3.15 A max. to the safety relay outputs to prevent the contacts from welding. ■ Compliance with International Standards Model G9SX-AD G9SX-ADA G9SX-NS G9SX-NSA G9SX-BC G9SX-GS G9SX-EX EN50178 ❍ ❍ ❍ ❍ ❍ IEC/EN60204-1 ❍ ❍ ❍ ❍ ❍ EN954-1 Cat.4 ❍ ❍ ❍ ❍ ❍ ❍ ❍ Item ❍ EN954-1 Cat.3 Approved by TÜV Product Service Precautions 100 Approved by UL IEC/EN61508 SIL3 ❍ ❍ IEC/EN62061 SIL3 IEC/EN61000-6-2 ❍ IEC/EN61000-6-4 ❍ IEC/EN60947-5-2 ❍ IEC/EN60947-5-3 PDF-M ❍ ❍ ❍ ❍ ❍ ❍ ❍ UL508 ❍ ❍ ❍ ❍ ❍ UL1998 ❍ ❍ ❍ ❍ ❍ NFPA79 ❍ ❍ ❍ ❍ ❍ IEC61508 ❍ ❍ ❍ ❍ ❍ CAN/CSA C22.2 No.142 ❍ ❍ ❍ ❍ ❍ ❍ ❍ ❍ Approved by KOSHA G9SX USER'S GUIDE ❍ ❍ MEMO G9SX USER'S GUIDE 101 MEMO 102 G9SX USER'S GUIDE READ AND UNDERSTAND THIS CATALOG Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the product. At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof. Copyright and Copy Permission COPYRIGHT AND COPY PERMISSION This document shall not be copied for sales or promotions without permission. This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or reproducing this document in any manner, for any other purpose. If copying or transmitting this document to another, please copy or transmit it in its entirety. OMRON Corporation Industrial Automation Company OMRON SCIENTIFIC TECHNOLOGIES INC. 6550 Dumbarton Circle, Fremont CA 94555-3605 U.S.A. Tel: (1) 510-608-3400/Fax: (1) 510-744-1442 Authorized Distributor: Safety Devices Division Shiokoji Horikawa, Shimogyo-ku, OMRON ASIA PACIFIC PTE. LTD. Kyoto, 600-8530 Japan Tel: (81) 75-344-7093/Fax: (81) 75-344-8197 No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 Regional Headquarters OMRON (CHINA) CO., LTD. OMRON EUROPE B.V. Room 2211, Bank of China Tower, Wegalaan 67-69, NL-2132 JD Hoofddorp 200 Yin Cheng Zhong Road, The Netherlands Pu Dong New Area, Shanghai, 200120, China Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Note: Specifications subject to change without notice. Cat. No. Z255-E1-01 Printed in Japan 0807-0.3M (0307) (M)