Operating Instructions
Radar sensor for continuous level
measurement of liquids
VEGAPULS 62
HART and accumulator pack
Document ID: 40793
Contents
Contents
About this document
1.1 Function ........................................................................................................................... 4
1.2 Target group ..................................................................................................................... 4
1.3 Symbols used................................................................................................................... 4
2
For your safety
2.1 Authorised personnel ....................................................................................................... 5
2.2 Appropriate use ................................................................................................................ 5
2.3 Warning about incorrect use............................................................................................. 5
2.4 General safety instructions ............................................................................................... 5
2.5 CE conformity................................................................................................................... 6
2.6 NAMUR recommendations .............................................................................................. 6
2.7 Radio license for Europe .................................................................................................. 6
2.8 Radio license for USA/Canada ......................................................................................... 6
2.9 Environmental instructions ............................................................................................... 6
3
Product description
3.1 Configuration .................................................................................................................... 8
3.2 Principle of operation........................................................................................................ 9
3.3 Packaging, transport and storage ................................................................................... 10
3.4 Accessories and replacement parts ............................................................................... 10
4
Mounting
4.1 General instructions ....................................................................................................... 12
4.2 Mounting preparations ................................................................................................... 12
4.3 Mounting instructions ..................................................................................................... 14
4.4 Measurement setup - Pipes ........................................................................................... 20
4.5 Measurement setup - Flow ............................................................................................. 25
5
Connecting to power supply
5.1 Connection of the battery charger .................................................................................. 27
5.2 Wiring plan ..................................................................................................................... 27
5.3 Switch-on phase............................................................................................................. 28
6
Set up with the display and adjustment module
6.1 Insert display and adjustment module ............................................................................ 30
6.2 Adjustment system ......................................................................................................... 31
6.3 Parameter adjustment .................................................................................................... 31
6.4 Saving the parameter adjustment data ........................................................................... 45
7
Setup with PACTware
7.1 Connect the PC .............................................................................................................. 46
7.2 Parameter adjustment .................................................................................................... 46
7.3 Saving the parameter adjustment data ........................................................................... 47
8
Set up with other systems
8.1 DD adjustment programs ............................................................................................... 48
8.2 Field Communicator 375, 475 ........................................................................................ 48
9
Diagnosis, asset management and service
9.1 Maintenance .................................................................................................................. 49
9.2 Measured value and event memory ............................................................................... 49
9.3 Asset Management function ........................................................................................... 50
2
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
1
Contents
9.4
9.5
9.6
9.7
Rectify faults ................................................................................................................... 53
Exchanging the electronics module ................................................................................ 56
Software update ............................................................................................................. 57
How to proceed if a repair is needed .............................................................................. 57
10 Dismount
10.1 Dismounting steps.......................................................................................................... 58
10.2 Disposal ......................................................................................................................... 58
40793-EN-140922
11 Supplement
11.1 Technical data ................................................................................................................ 59
11.2 Dimensions .................................................................................................................... 66
Safety instructions for Ex areas
PleasenotetheEx-specificsafetyinformationforinstallationandoperation in Ex areas. These safety instructions are part of the operating
instructions manual and come with the Ex-approved instruments.
Editing status: 2014-09-04
VEGAPULS 62 • HART and accumulator pack
3
1 About this document
1
About this document
1.1
Function
1.2
Target group
1.3
Symbols used
This operating instructions manual provides all the information you
need for mounting, connection and setup as well as important instructionsformaintenanceandfaultrectification.Pleasereadthisinformation before putting the instrument into operation and keep this manual
accessible in the immediate vicinity of the device.
This operating instructions manual is directed to trained specialist
personnel. The contents of this manual should be made available to
these personnel and put into practice by them.
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
•
→
1
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Action
This arrow indicates a single action.
Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of batteries and accumulators.
40793-EN-140922
4
VEGAPULS 62 • HART and accumulator pack
2 For your safety
2
2.1
For your safety
Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2
Appropriate use
The VEGAPULS 62 is a sensor for continuous level measurement.
Due to the integrated accumulator the instrument is particularly
suitable as a portable measuring system or test sensor for special
applications.
Youcanfinddetailedinformationabouttheareaofapplicationin
chapter "Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecificationsintheoperatinginstructions
manual as well as possible supplementary instructions.
2.3
Warning about incorrect use
2.4
General safety instructions
Inappropriate or incorrect use of the instrument can give rise to
application-specifichazards,e.g.vesseloverfillordamagetosystem
components through incorrect mounting or adjustment.
This is a state-of-the-art instrument complying with all prevailing
regulations and guidelines. The instrument must only be operated in a
technicallyflawlessandreliablecondition.Theoperatorisresponsible
for the trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regulations.
The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and
accident prevention rules must be observed by the user.
40793-EN-140922
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbitraryconversionsormodificationsareexplicitlyforbidden.
The safety approval markings and safety tips on the device must also
be observed.
Depending on the instrument version, the emitting frequencies are in
the C or K band range. The low emitting frequencies are far below the
internationally approved limit values. When used correctly, there is no
danger to health.
VEGAPULS 62 • HART and accumulator pack
5
2 For your safety
2.5
CE conformity
ThedevicefulfillsthelegalrequirementsoftheapplicableECguidelines.ByaffixingtheCEmarking,weconfirmsuccessfultestingofthe
product.
YoucanfindtheCECertificateofConformityinthedownloadsection
of our homepage.
2.6
NAMUR recommendations
NAMUR is the automation technology user association in the process
industry in Germany. The published NAMUR recommendations are
acceptedasthestandardinfieldinstrumentation.
ThedevicefulfillstherequirementsofthefollowingNAMURrecommendations:
•
•
•
•
NE 21 – Electromagnetic compatibility of equipment
NE 43 – Signal level for malfunction information from measuring
transducers
NE53–Compatibilityoffielddevicesanddisplay/adjustment
components
NE107–Self-monitoringanddiagnosisoffielddevices
For further information see www.namur.de.
2.7
Radio license for Europe
2.8
Radio license for USA/Canada
The instrument is approved according to EN 302372-1/2 (2006-04)
for use in closed vessels.
The instrument is in conformity with part 15 of the FCC regulations.
Take note of the following two regulations:
•
•
The instrument must not cause any interfering emissions
The device must be insensitive to interfering immissions, including
those that may cause undesirable operating conditions
Modificationsnotexpresslyapprovedbythemanufacturerwillleadto
expiry of the operating licence according to FCC/IC.
The instrument is in conformity with RSS-210 of the IC regulations.
The instrument may only be used in closed vessels made of metal,
concrete,orfibre-reinforcedplastic.
2.9
Environmental instructions
Pleasehelpusfulfillthisobligationbyobservingtheenvironmental
instructions in this manual:
•
6
Chapter "Packaging, transport and storage"
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental protection.Theenvironmentmanagementsystemiscertifiedaccording
to DIN EN ISO 14001.
2 For your safety
Chapter "Disposal"
40793-EN-140922
•
VEGAPULS 62 • HART and accumulator pack
7
3 Product description
3
Type label
Product description
3.1 Configuration
Thetypelabelcontainsthemostimportantdataforidentificationand
use of the instrument:
1
17
16
2
3
15
4
5
6
7
8
9
13
10
11
14
12
Fig. 1: Layout of the type label (example)
1 Instrument type
2 Product code
3 Approvals
4 Power supply and signal output, electronics
5 Protection rating
6 Measuring range
7 Process and ambient temperature, process pressure
8 Material, wetted parts
9 Hardware and software version
10 Order number
11 Serial number of the instrument
12 Data-Matrix-Code for Smartphone-App
13 Symbol of the device protection class
14 ID numbers, instrument documentation
15 Reminder to observe the instrument documentation
16 NotifiedauthorityforCEmarking
17 Approval directive
Serial number - Instrument search
The type label contains the serial number of the instrument. With it
youcanfindthefollowinginstrumentdataonourhomepage:
•
•
•
•
Go to www.vega.com, "VEGATools" and "Instrument search". Enter
the serial number.
Alternatively, you can access the data via your smartphone:
8
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
•
•
Product code (HTML)
Delivery date (HTML)
Order-specificinstrumentfeatures(HTML)
Operating instructions and quick setup guide at the time of shipment (PDF)
Order-specificsensordataforanelectronicsexchange(XML)
Testcertificate(PDF)-optional
3 Product description
•
•
•
Download the smartphone app "VEGATools" from the "Apple App
Store" or the "GooglePlayStore"
Scan the Data Matrix code on the type label of the instrument or
Enter the serial number manually in the app
Scope of this operating
instructions manual
This operating instructions manual applies to the following instrument
versions:
Versions
Theinstrumentisavailableintwodifferentelectronicsversions.Each
versioncanbeidentifiedviatheproductcodeonthetypelabelas
well as on the electronics.
•
•
•
•
Hardware from 2.1.0
Software from 4.5.1
Standard electronics type PS60HK.Electronics with increased sensitivity type PS60HS.-
Scope of delivery
The scope of delivery encompasses:
Application area
The VEGAPULS 62 radar sensor can be used in a wide variety of applications for continuous level measurement of liquids. It is suitable for
applications in storage vessels, reactors and process vessels, even
underextremelydifficultprocessconditions.
•
•
•
Sensor with integrated accumulator
Battery charger
Documentation
– Quick setup guide VEGAPULS 62
– Testcertificatemeasuringaccuracy(optional)
– Operating instructions manual "Display and adjustment module" (optional)
– Ex-specific"Safety instructions" (with Ex versions)
– ifnecessary,furthercertificates
3.2
Principle of operation
Dependentontheapplicationrange,differentversionsareused:
•
40793-EN-140922
•
Antenna
– Small tanks and process vessels, measurement of virtually all
products: Horn antenna ø 40 mm
– Storage tanks and process vessels, measurement of products
such as solvents, hydrocarbons and fuels under extremely difficultprocessconditions:Horn antenna ø 48 … 95 mm
– Productswithlowεr value with large measuring distances:
Parabolic antenna
Electronics
– Productswithanεrvalue≥1.8:Standard electronics
– Productswithanεrvalue<1.8,≥1.5;applicationswithverybad
reflectiveproperties:Electronics with increased sensitivity
The actual values that can be reached depend on the measurement
conditions, the antenna system or the standpipe or bypass.
VEGAPULS 62 • HART and accumulator pack
9
3 Product description
Functional principle
The antenna of the radar sensor emits short radar pulses with a
durationofapprox.1ns.Thesepulsesarereflectedbytheproduct
and received by the antenna as echoes. The transit time of the radar
pulses from emission to reception is proportional to the distance and
hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
Voltage supply
The instrument is powered via an integrated accumulator. This allows
operation of the instrument independently of the mains or a control
system. To achieve a longer battery lifetime, the instrument is preset
to HART multidrop. This puts a load of only 4 mA current on the accumulator.
Packaging
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
based on ISO 4180.
3.3
Packaging, transport and storage
The packaging of standard instruments consists of environmentfriendly, recyclable cardboard. For special versions, PE foam or PE
foil is also used. Dispose of the packaging material via specialised
recycling companies.
Transport
Transport must be carried out in due consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
Transport inspection
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Storage
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
Storage and transport
temperature
10
•
Not in the open
Dry and dust free
Not exposed to corrosive media
Protected against solar radiation
Avoiding mechanical shock and vibration
Storage and transport temperature see chapter "Supplement Technicaldata-Ambientconditions"
Relative humidity 20 … 85 %
3.4
Accessories and replacement parts
The display and adjustment module PLICSCOM is used for measured
value indication, adjustment and diagnosis. It can be inserted into the
sensor or the external display and adjustment unit and removed at
any time.
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
PLICSCOM
•
•
•
•
•
•
3 Product description
Youcanfindfurtherinformationintheoperatinginstructions"Display
and adjustment module PLICSCOM" (Document-ID 27835).
VEGACONNECT
The interface adapter VEGACONNECT enables the connection of
communication-capable instruments to the USB interface of a PC. For
parameter adjustment of these instruments, the adjustment software
PACTware with VEGA-DTM is required.
Youcanfindfurtherinformationintheoperatinginstructions"Interface
adapterVEGACONNECT" (Document-ID 32628).
Protective cap
The protective cover protects the sensor housing against soiling and
intense heat from solar radiation.
Youwillfindadditionalinformationinthesupplementaryinstructions
manual "Protective cover" (Document-ID 34296).
Flanges
Screwedflangesareavailableindifferentversionsaccordingtothe
following standards: DIN 2501, EN 1092-1, BS 10, ANSI B 16.5,
JIS B 2210-1984, GOST 12821-80.
Youcanfindadditionalinformationinthesupplementaryinstructions
manual "FlangesaccordingtoDIN-EN-ASME-JIS" (Document-ID
31088).
Electronics module
Electronics module "VEGAPULS series 60" is a replacement part for
radarsensorsofVEGAPULSseries60.Adifferentversionisavailable
for each type of signal output.
Youcanfindfurtherinformationintheoperatinginstructions"ElectronicsmoduleVEGAPULSseries60" (Document-ID 36801).
Supplementary electronics power pack
The supplementary electronics "Power pack" is a replacement part for
sensors with integrated accumulator.
Youcanfindfurtherinformationintheoperatinginstructions"Supplementaryelectronicsfor4…20mA/HARTandpowerpack"
(Document-ID 41033).
Antenna impedance cone The antenna impedance cone is a replacement part used for optimum
transmission of microwaves and for sealing against the process.
40793-EN-140922
Youfindfurtherinformationintheoperatinginstructions"Antenna
impedanceconeVEGAPULS62and68" (Document-ID 31381).
VEGAPULS 62 • HART and accumulator pack
11
4 Mounting
4
Screwing in
Mounting
4.1
General instructions
Oninstrumentswithprocessfittingthread,thehexagonmustbetightenedwithasuitablewrench.Fortheproperwrenchsizeseechapter
"Dimensions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Protection against moisture
Protect your instrument against moisture ingress through the following
measures:
•
•
•
•
Use the recommended cable (see chapter "Connecting to power
supply")
Tighten the cable gland
Whenmountinghorizontally,turnthehousingsothatthecable
gland points downward
Loop the connection cable downward in front of the cable gland
This applies particularly to:
•
•
•
Outdoor mounting
Installations in areas where high humidity is expected (e.g. through
cleaning processes)
Installations on cooled or heated vessels
Suitability for the process Make sure that all parts of the instrument exposed to the process are
conditions
suitable for the existing process conditions.
These are mainly:
•
•
•
Active measuring component
Processfitting
Process seal
•
•
•
•
Process pressure
Process temperature
Chemical properties of the medium
Abrasionandmechanicalinfluences
Process conditions are particularly:
Youcanfinddetailedinformationontheprocessconditionsinchapter
"Technicaldata" as well as on the type label.
4.2
Mounting preparations
Horn antenna
12
Proceed as follows:
1. Loosen the hexagon socket screws (3) on the antenna socket
withanAllenwrench(size3)
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
The instrument is also available in versions with an antenna whose
diameterislargerthantheprocessfitting(thread,flange).Insuch
casestheantennamustbedisconnectedfromtheprocessfitting
before mounting.
4 Mounting
2. Remove the antenna (4)
Note:
The plastic cone may not be pulled out of the antenna socket.
3. Insert the antenna from below into the vessel socket and secure it
againstfallingoff
4. Retighten the antenna with hexagon screws to the antenna
socket;torquemax.2.5Nm(1.8lbfft)
Note:
The radar sensor with rinsing air connection or antenna extension
is provided with a notch on the antenna socket. This notch must be
alignedwiththemarkingontheprocessfitting(themarkingspecifies
the position of the polarisation of the radar signal).
1
2
3
4
Fig. 2: Dismounting of the horn antenna
1
2
3
4
Parabolic antenna
Polarisation marking
Marking at the antenna socket
Hexagon screws on the antenna socket
Antenna
Proceed as follows:
1. ClampVEGAPULS62withtheflange,e.g.inabenchvice
2. Holdtheconnectionpiece(1)withawrenchontheflatsurfaces
(widthacrossflats22mm)
3. Loosen counter nut (3) completely with a wrench (width across
flats36mm)inthedirectionoftheantenna
4. Loosen compression nut (2) completely with a wrench (width
acrossflats41mm)inthedirectionoftheantenna
40793-EN-140922
5. Remove the parabolic antenna (4) axially
6. Mountsensorflangeontheadapterflangeandfastenittightly
7. Check if the O-ring seal is present on the connection piece and
make sure it is not damaged.
VEGAPULS 62 • HART and accumulator pack
13
4 Mounting
Note:
A damaged O-ring seal must be replaced: FKM (SHS FPM 70C3
GLT),FFKM(Kalrez6375)
8. Remount the parabolic antenna (4)
9. Fastencompressionnut(2)withawrench(widthacrossflats41),
torque max. 50 Nm
10. Fastencounternut(3)withawrench(widthacrossflats36),
torque max. 40 Nm
Note:
On the version with rinsing air connection, make sure that the holes
intheantennaandintheprocessfittingcoincide.Thisensuresasufficientairflow(theairisledthroughtheholestothefeedsystem.A
rinsing of the whole parabolic antenna is not intended).
1
2
3
4
Fig. 3: Dismounting, parabolic antenna
1
2
3
4
Connection piece
Compression nut
Locknut
Parabolic antenna
4.3
Mounting instructions
Horn and parabolic
antenna
The illustrations with the following mounting instructions show a radar
sensor with horn antenna. The mounting instructions apply analogously also to the version with parabolic antenna.
Polarisation
The emitted radar impulses of the radar sensor are electromagnetic
waves. The polarisation is the direction of the electrical wave component.Byturningtheinstrumentintheconnectionflangeormounting
boss,thepolarisationcanbeusedtoreducetheeffectsoffalse
echoes.
Thepositionofthepolarisationismarkedontheprocessfittingofthe
instrument.
40793-EN-140922
14
VEGAPULS 62 • HART and accumulator pack
4 Mounting
1
2
Fig. 4: Position of the polarisation
1 Marking with screwed version
2 Markingwithflangeversion
Installation position
When mounting the sensor, keep a distance of at least 200 mm
(7.874 in) from the vessel wall. If the sensor is installed in the center
of dished or round vessel tops, multiple echoes can arise. However,
these can be suppressed by an appropriate adjustment (see chapter
"Setup").
If you cannot maintain this distance, you should carry out a false
signal storage during setup. This applies particularly if buildup on the
vessel wall is expected. In such cases, we recommend repeating the
false signal storage at a later date with existing buildup.
> 200 mm
(7.87")
Fig. 5: Mounting of the radar sensor on round vessel tops
40793-EN-140922
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.
VEGAPULS 62 • HART and accumulator pack
15
4 Mounting
Fig. 6: Mounting of the radar sensor on vessels with conical bottom
Inflowingmedium
Donotmounttheinstrumentsinorabovethefillingstream.Makesure
thatyoudetecttheproductsurface,nottheinflowingproduct.
Fig.7:Mountingoftheradarsensorwithinflowingmedium
The socket piece should be dimensioned in such a way that the
antenna end protrudes slightly out of the socket.
Fig. 8: Recommended socket mounting with horn antenna
16
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
ca. 10 mm
Socket
> 10 mm
(0.39")
4 Mounting
Fig. 9: Recommended socket mounting with parabolic antenna
When using a swivelling holder, keep in mind that the distance
between antenna and socket gets smaller as the inclination of the
sensorincreases.Additionalfalsereflectionsmaybegeneratedwhich
caninfluencethemeasuringresultatcloserange.
Fig. 10: Distance between antenna and socket with horn antenna
Fig. 11: Distance between antenna and socket with parabolic antenna
40793-EN-140922
Ifthemediumhasgoodreflectiveproperties,VEGAPULS62with
horn antenna can also be mounted on a longer socket piece. Recommendedvaluesforsocketheightsarespecifiedinthefollowing
illustration. You must carry out a false echo storage afterwards.
VEGAPULS 62 • HART and accumulator pack
17
h max.
4 Mounting
d
Fig. 12: Deviating socket dimensions
Socket diameter d
Socket length h
Recommended antenna diameter
40 mm
≤100mm
40 mm
50 mm
≤150mm
48 mm
80 mm
≤250mm
75 mm
100 mm
≤500mm
95 mm
150 mm
≤800mm
95 mm
Socket diameter d
Socket length h
Recommended antenna diameter
1½"
≤3.9in
1½"
2"
≤5.9in
2"
3"
≤9.8in
3"
4"
≤19.7in
4"
6"
≤31.5in
4"
Tip:
The instrument is also optionally available with an antenna extension.
The antenna length can be selected (either ex works or later) to allow
the antenna to protrude slightly out of the end of the mounting socket.
Duetotheantennaextensionhowever,disturbingreflectionsare
generated in the close-up range. This can lead to an increase in the
requiredminimumdistance,especiallywithpoorlyreflectingmedia
such as plastic powder. In practice, a cleanly constructed mounting
socket, if necessary with rounded edges, introduces fewer disturbing
influencesthananantennaextension.
Sensor orientation
In liquids, direct the sensor as perpendicular as possible to the product surface to achieve optimum measurement results.
18
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Fig. 13: Alignment in liquids
4 Mounting
Vessel installations
The mounting location of the radar sensor should be a place where no
otherequipmentorfixturescrossthepathofthemicrowavesignals.
Vessel installations, such as e.g. ladders, limit switches, heating spirals, struts, etc., can cause false echoes and impair the useful echo.
Make sure when planning your measuring point that the radar sensor
has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be
carried out during setup.
If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small,inclinedsheetmetalbafflesabovetheinstallationsscatterthe
radarsignalsandpreventdirectinterferingreflections.
Fig.14:Coverflat,large-areaprofileswithdeflectors
Agitators
If there are agitators in the vessel, a false signal suppression should
be carried out with the agitators in motion. This ensures that the
interferingreflectionsfromtheagitatorsaresavedwiththebladesin
differentpositions.
Fig. 15: Agitators
40793-EN-140922
Foam generation
Throughtheactionoffilling,stirringandotherprocessesinthevessel,
compact foams that considerably damp the emitted signals may form
on the product surface.
If foams are causing measurement errors, the biggest possible radar
antennas, the electronics with increased sensitivity or low frequency
radar sensors (C band) should be used.
VEGAPULS 62 • HART and accumulator pack
19
4 Mounting
As an alternative, sensors with guided microwave can be used. These
areunaffectedbyfoamgenerationandarebestsuitedforsuchapplications.
Mounting in the vessel
insulation
Instruments for a temperature range up to 250 °C or up to 450 °C
haveadistancepiecebetweenprocessfittingandelectronicshousing. Ths distance piece is used for thermal decoupling of the electronics against high process temperatures.
Information:
The spacer may only be incorporated up to a maximum of 50 mm into
the vessel insulation. Only then is a reliable temperature decoupling
guaranteed.
max. 50 mm
(1.97")
1
2
3
Fig. 16: Mounting the instrument on insulated vessels.
1 Electronicshousing
2 Spacer
3 Vessel insulation
Measurement in a surge
pipe
4.4
Measurement setup - Pipes
Byusingasurgepipeinthevessel,theinfluenceofvesselinstallations and turbulence can be excluded. Under these prerequisites, the
measurementofproductswithlowdielectricvalues(εrvalue≤1.6)is
possible.
Note the following illustrations and instructions for measurement in a
surge pipe.
Information:
Measurement in a surge pipe is not recommended for extremely
adhesive products.
40793-EN-140922
20
VEGAPULS 62 • HART and accumulator pack
4 Mounting
Configurationsurgepipe
1
1
2
2
3
3
4
100%
5
6
7
45°
0%
15°
9
8
9
10
9
Fig.17:ConfigurationsurgepipeVEGAPULS62
Radar sensor
Polarisation marking
Threadorflangeontheinstrument
Vent hole
Holes
WeldingconnectionthroughU-profile
Ball valve with complete opening
Surge pipe end
Reflectorsheet
Fastening of the surge pipe
40793-EN-140922
1
2
3
4
5
6
7
8
9
10
VEGAPULS 62 • HART and accumulator pack
21
4 Mounting
Surge pipe extension
ø 114,3 mm
(4.5")
°
75
4 mm
(0.16")
4 mm
(0.16")
4 mm
(0.16")
30,5 mm
(1.20")
26 mm
(1.02")
1
m
m
ø 88,9
(3.5")
2 mm
(0.08")
1
mm
14,3
ø 1 4.5")
(
5 mm
(0.20")
100 mm
(3.94")
2 mm
(0.08")
80 mm
(3.15")
mm
ø 60,3 )
(2.37"
80 mm
(3.15")
15 mm
(0.59")
2 mm
(0.08")
1
75°
dx2
8 mm
(0.32")
dx2
8 mm
(0.32")
4 mm
(0.16")
dx2
°
75
8 mm
(0.32")
ø 88,9 mm
(3.5")
ø 60,3 mm
(2.37")
5 mm
(0.20")
Fig.18:Weldingconnectionwithsurgepipeextensionfordifferentexample
diameters
1
Instructions and requirements, surge pipe
Position of the welded joint with longitudinally welded pipes
Instructions of orientation of the polarisation:
• Note marking of the polarisation on the sensor
• Withthreadedversions,themarkingisonthehexagon,withflange
versionsbetweentwoflangeholes
• The marking must be in one plane with the holes in the surge pipe
Instructions for the measurement:
The 100 % point must be below the upper vent hole and the
antenna edge
• The 0 % point is the end of the surge pipe
• During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
• A false signal suppression with the installed sensor is recommended but not mandatory
• The measurement through a ball valve with unrestricted channel
is possible
•
22
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Constructive requirements:
Material metal, smooth inner surface
Preferably pultruded or straight beaded stainless steel tube
Welded joint should be straight and lie in one axis with the holes
Flanges are welded to the tube according to the orientation of the
polarisation
•
•
•
•
4 Mounting
•
•
•
•
•
•
Whenusingaballvalves,alignthetransitionsontheinsideandfix
accurately
Gapsizewithjunctions≤0.1mm
Surge pipes must extend all the way down to the requested min.
level, as measurement is only possible within the tube
Diameterofholes≤5mm,anynumberOK,ononesideorcompletely through
The antenna diameter of the sensor should correspond to the
inner diameter of the tube
Diameter should be constant over the complete length
Instructions for surge pipe extension:
The ends of the extension tubes must be bevelled and exactly
aligned
• WeldedconnectionviaexternalUprofilesaccordingtoillustration
above.LengthoftheUprofilesshouldbeatleastdoublethetube
diameter
• Do not weld through the pipe wall. The surge pipe must remain
smooth inside. Roughness and beads on the inside caused by
unintentional penetration should be removed since they cause
strong false echoes and encourage buildup
• Anextensionviaweldingneckflangesorpipecollarsisnotrecommended.
•
An alternative to measurement in a surge pipe is measurement in a
bypass tube outside of the vessel.
40793-EN-140922
Measurement in the
bypass tube
VEGAPULS 62 • HART and accumulator pack
23
4 Mounting
Configurationbypass
1
2
3
4
100 %
6
5
0%
Fig.19:Configurationbypass
1
2
3
4
5
6
Instructions and requirements, bypass
Radar sensor
Polarisation marking
Instrumentflange
Distance sensor reference plane to upper tube connection
Distance of the tube connections
Ball valve with complete opening
Instructions of orientation of the polarisation:
• Note marking of the polarisation on the sensor
• Withthreadedversions,themarkingisonthehexagon,withflange
versionsbetweentwoflangeholes
• The marking must be in one plane with the tube connections to the
vessel
Instructions for the measurement:
The 100 % point may not be above the upper tube connection to
the vessel
• The 0 % point may not be below the lower tube connection to the
vessel
• Min. distance, sensor reference plane to upper edge of upper tube
connection > 300 mm
• During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
• A false signal suppression with the installed sensor is recommended but not mandatory
• The measurement through a ball valve with unrestricted channel
is possible
•
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
24
4 Mounting
Constructional requirements on the bypass pipe:
• Material metal, smooth inner surface
• In case of an extremely rough tube inner surface, use an inserted
tube (tube in tube) or a radar sensor with tube antenna
• Flanges are welded to the tube according to the orientation of the
polarisation
• Gapsizewithjunctions≤0.1mm,forexample,whenusingaball
valveorintermediateflangeswithsinglepipesections
• The antenna diameter of the sensor should correspond to the
inner diameter of the tube
• Diameter should be constant over the complete length
4.5
Measurement setup - Flow
Theshortexamplesgiveyouintroductoryinformationontheflow
measurement.Detailedplanninginformationisavailablefromflume
manufacturers and in special literature.
1
dmin
3 ... 4 hmax
90°
≥ 50 mm
2 2
33
90°
≥ 2 mm x hmax hmax
Flow measurement with
rectangularflume
4
Fig.20:Flowmeasurementwithrectangularflume:dmin. = min. distance of the
sensor(seechapter"Technicaldata");hmax.=max.fillingoftherectangular
flume
1
2
3
4
Overfloworifice(sideview)
Headwater
Tailwater
Overfallorifice(viewfrombottomwater)
In general, the following points must be observed:
40793-EN-140922
•
•
•
•
•
•
Install the sensor on the headwater side
Installationinthecentreoftheflumeandverticaltotheliquid
surface
Distancetotheoverfallorifice
Distanceoforificeopeningaboveground
Min.distanceoftheorificeopeningtobottomwater
Min. distance of the sensor to max. storage level
VEGAPULS 62 • HART and accumulator pack
25
4 Mounting
Flow measurement with
KhafagiVenturiflume
3 ... 4 x hmax
d
90°
hmax
1
B
2
Fig.21:FlowmeasurementwithKhafagi-Venturiflume:d=Min.distancetosensor;hmax.=max.fillingoftheflume;B=tightestconstrictionintheflume
1 Position sensor
2 Venturiflume
In general, the following points must be observed:
•
•
•
•
Installation of the sensor at the input side
Installationinthecentreoftheflumeandverticaltotheliquid
surface
DistancetotheVenturiflume
Min. distance of the sensor to max. storage level
40793-EN-140922
26
VEGAPULS 62 • HART and accumulator pack
5 Connecting to power supply
5
Connecting to power supply
5.1
Connection of the battery charger
We recommended charging the integrated accumulator completely
beforesettinguptheinstrument.Youcanfindthechargingtimein
chapter "Technicaldata".
The battery charger is plugged into a socket in the supply room, see
chapter "Wiring plan".
The LEDs in the supply room show the charging process and condition of the accumulator, see chapter "Wiring plan".
Overview
5.2
Wiring plan
2
1
Fig. 22: Position of the power supply and electronics compartment
1 Supply room (accumulator)
2 Electronicscompartment
Electronics compartment
2
4...20mA
(+)1
2(-)
5
6
7 8
1
Fig.23:Electronicscompartment,doublechamberhousing
Internal connection to the terminal compartment
Contact pins for the display and adjustment module
40793-EN-140922
1
2
VEGAPULS 62 • HART and accumulator pack
27
5 Connecting to power supply
Supply room
2
78
23
901
1,2 OFF
3 ON/OFF 1h
4 ON/OFF
5..9 auto cycle
Charge
modes
45 6
( +)1
3
Accu
2(-)
4
5
1
Fig. 24: Supply room
1
2
3
4
5
Internal connection of the socket for the battery charger
Mode switch
LEDgreen,chargingprocess
LEDyellow,chargingstatus
Socket for the battery charger
The mode switch enables the selection of the following modes:
•
•
•
•
•
•
•
•
•
0=sensoroff,LEDsshowtheaccumulatorstatus
1,2=sensoroff,LEDsoff
3 = sensor on for 1 hour after pressing a key (delivery status)
4=sensorpermanentlyon,switchingon/offviabutton
5 = sensor is switched on every 30 min. for 3 min.
6 = sensor is switched on every hour for 3 min.
7 = sensor is switched on every 6 hours for 3 min.
8 = sensor is switched on every 12 hours for 3 min.
9 = sensor is switched on every 24 hours for 3 min.
•
•
LEDflashes=Accumulatorischarging
LED lights = accumulator is full, battery charger should be
unplugged (accumulator life time)
ThegreenLEDcharacterizesthechargingprocess:
After pressing the key or changing the mode the yellow LED shows
the accumulator status for approximately 10 s as follows:
•
•
•
LED lights = accumulator is full
LEDflashes=accumulatorshouldbecharged
LEDoff=accumulatorisempty
5.3
Switch-on phase
Theinstrumentisswitchedonandoffbymeansofabuttonoutside
on the housing.
40793-EN-140922
28
VEGAPULS 62 • HART and accumulator pack
5 Connecting to power supply
1
Fig.25:Switchon/offbuttonoutsideonthehousing
1 On/Offbutton
After switching on, the instrument carries out a self-check for approximately 30 s:
•
•
•
Internal check of the electronics
Indication of the instrument type, hardware and software version,
measurement loop name on the display or PC
Indication of the status message "F 105 Determine measured
value" on the display or PC
40793-EN-140922
As soon as a plausible measured value is found, it is displayed. The
value corresponds to the actual level as well as the settings already
carried out, e.g. factory settings.
VEGAPULS 62 • HART and accumulator pack
29
6 Set up with the display and adjustment module
6
6.1
Set up with the display and adjustment
module
Insert display and adjustment module
The display and adjustment module can be inserted into the sensor
andremovedagainatanytime.Youcanchooseanyoneoffourdifferent positions - each displaced by 90°. It is not necessary to interrupt
the power supply.
Proceed as follows:
1. Unscrew the housing cover
2. Place the display and adjustment module on the electronics in the
desired position and turn it to the right until it snaps in.
3. Screw housing cover with inspection window tightly back on
Disassembly is carried out in reverse order.
The display and adjustment module is powered by the sensor, an additional connection is not necessary.
Fig. 26: Insertion of the display and adjustment module
Note:
Ifyouintendtoretrofittheinstrumentwithadisplayandadjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.
40793-EN-140922
30
VEGAPULS 62 • HART and accumulator pack
6 Set up with the display and adjustment module
6.2
Adjustment system
1
2
Fig. 27: Display and adjustment elements
Key functions
1
2
LC display
Adjustment keys
•
[OK] key:
– Move to the menu overview
– Confirmselectedmenu
– Edit parameter
– Save value
•
•
•
40793-EN-140922
Adjustment system
[->] key:
– Presentation, change measured value
– Select list entry
– Select editing position
[+] key:
– Change value of the parameter
[ESC] key:
– Interrupt input
– Jump to next higher menu
The instrument is adjusted via the four keys of the display and adjustment module. The LC display indicates the individual menu items. The
functions of the individual keys are shown in the above illustration.
Approx. 60 minutes after the last pressing of a key, an automatic reset
tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmed
with [OK] will not be saved.
6.3
Parameter adjustment
The instrument is adapted to the application conditions via the parameter adjustment. The parameter adjustment is carried out with an
adjustment menu.
VEGAPULS 62 • HART and accumulator pack
31
6 Set up with the display and adjustment module
Main menu
Themainmenuisdividedintofivesectionswiththefollowingfunctions:
Setup: Settings, e.g., for measurement loop name, medium, application, vessel, adjustment, signal output
Display: Settings, e.g., for language, measured value display, lighting
Diagnosis: Information, e.g. on instrument status, pointer, measurement reliability, simulation, echo curve
Further settings: Instrument unit, false signal suppression, linearisation curve, reset, date/time, reset, copy function
Info: Instrument name, hardware and software version, date of manufacture, instrument features
Information:
Inthisoperatinginstructionsmanual,theinstrument-specificparameters in the menu sections "Setup", "Diagnosis" and "Additional settings" are described. The general parameters in these menu section
are described in the operating instructions manual "Indicating and
adjustment module".
Youcanfindintheoperatinginstructionsmanual"Display and adjustment module" also the description of the menu sections "Display" and
"Info".
In the main menu point "Setup", the individual submenu points
should be selected one after the other and provided with the correct
parameters to ensure optimum adjustment of the measurement. The
procedure is described in the following.
Setup - Medium
Eachmediumhasdifferentreflectionproperties.Withliquids,further
interferingfactorsarefluctuationproductsurfaceandfoamgeneration. With bulk solids, these are dust generation, material cone and
additional echoes from the vessel wall.
Toadaptthesensortothesedifferentmeasuringconditions,the
selection "Liquid" or "Bulk solid" should be made in this menu item.
32
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Through this selection, the sensor is adapted perfectly to the product
andmeasurementreliability,particularlyinproductswithpoorreflective properties, is considerably increased.
6 Set up with the display and adjustment module
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Application
In addition to the medium, also the application, i.e. the measuring site,
caninfluencethemeasurement.
With this menu item, the sensor can be adapted to the applications.
The adjustment possibilities depend on the selection "Liquid" or "Bulk
solid" under "Medium".
The following options are available when "Liquid" is selected:
The selection "Standpipe" opens a new window in which the inner
diameter of the applied standpipe is entered.
The following features form the basis of the applications:
Storage tank:
• Setup: large-volumed, upright cylindrical, spherical
• Productspeed:slowfillingandemptying
• Process/measurement conditions:
– Condensation
– Smooth product surface
– High requirements to the measurement accuracy
• Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values through averaging
– High accuracy
– Short reaction time of the sensor not required
Storage tank with product circulation:
Setup: large-volumed, upright cylindrical, spherical
Productspeed:slowfillingandemptying
Installations: small laterally mounted or large top mounted stirrer
Process/measurement conditions:
– Relatively smooth product surface
– High requirements to the measurement accuracy
– Condensation
– Slight foam generation
– Overfillingpossible
• Properties, sensor:
40793-EN-140922
•
•
•
•
VEGAPULS 62 • HART and accumulator pack
33
6 Set up with the display and adjustment module
–
–
–
–
Slight sensitivity against sporadic false echoes
Stable and reliable measured values through averaging
High accuracy because not adjusted for max. speed
False signal suppression recommended
Storage tank on ships (Cargo Tank):
Productspeed:slowfillingandemptying
Vessel:
– Installations in the bottom section (bracers, heating spirals)
– High sockets 200 … 500 mm, also with large diameters
• Process/measurement conditions:
– Condensation, buildup by movement
– Max. requirement on measurement accuracy from 95 %
• Properties, sensor:
– Slight sensitivity against sporadic false echoes
– Stable and reliable measured values through averaging
– High accuracy
– False signal suppression required
•
•
Stirrer vessel (reactor):
Setup:allvesselsizespossible
Product speed:
– Fasttoslowfillingpossible
– Vesselisveryoftenfilledandemptied
• Vessel:
– Socket available
– Large agitator blades of metal
– Vortex breakers, heating spirals
• Process/measurement conditions:
– Condensation, buildup by movement
– Strong spout generation
– Very agitated surface, foam generation
• Properties, sensor:
– Higher measurement speed through lower averaging
– Sporadic false echoes are suppressed
•
•
Dosing vessel:
Setup:allvesselsizespossible
Product speed:
– Fastfillingandemptying
– Vesselisveryoftenfilledandemptied
• Vessel: narrow installation situation
• Process/measurement conditions:
– Condensation, buildup on the antenna
– Foam generation
• Properties, sensor:
– Measurementspeedoptimizedbyvirtuallynoaveraging
– Sporadic false echoes are suppressed
– False signal suppression recommended
•
•
34
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Standpipe:
Productspeed:veryfastfillingandemptying
Vessel:
•
•
6 Set up with the display and adjustment module
•
•
– Vent hole
– Joinslikeflanges,weldjoints
– Shifting of the running time in the tube
Process/measurement conditions:
– Condensation
– Buildup
Properties, sensor:
– Measurementspeedoptimizedthroughlittleaveraging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
Bypass:
Product speed:
– Fastuptoslowfillingwithshortuptolongbypasstubepossible
– Often the level is hold via a control facility
• Vessel:
– Lateral outlets and inlets
– Joinslikeflanges,weldjoints
– Shifting of the running time in the tube
• Process/measurement conditions:
– Condensation
– Buildup
– Separation of oil and water possible
– Overfillingintotheantennapossible
• Properties, sensor:
– Measurementspeedoptimizedthroughlittleaveraging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
– False signal suppression recommended
•
Plastic tank:
Vessel:
– Measurementfixmountedorintegrated
– Measurement depending on the application through the vessel
top
– With empty vessel, the measurement can be carried out
through the bottom
• Process/measurement conditions:
– Condensation on the plastic ceiling
– In outside facilities water and snow on the vessel top possible
• Properties, sensor:
– False signals outside the vessel are not taken into consideration
– False signal suppression recommended
40793-EN-140922
•
Transportable plastic tank:
Vessel:
– Materialandthicknessdifferent
– Measurement through the vessel top
• Process/measurement conditions:
– Measured value jump with vessel change
• Properties, sensor:
•
VEGAPULS 62 • HART and accumulator pack
35
6 Set up with the display and adjustment module
– Quickadaptationtochangingreflectionconditionsthrough
vessel change
– False signal suppression required
Open water (gauge measurement):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Distance sensor to water surface to big
– Extreme damping of output signal due to wave generation
– Ice and condensation on the antenna possible
– Spiders and insect nestle in the antennas
– Floating material and animals sporadically on the water surface
• Properties, sensor:
– Stable and reliable measured values through high averaging
– Insensitive in the close range
•
•
Openflume(flowmeasurement):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Ice and condensation on the antenna possible
– Spiders and insect nestle in the antennas
– Smooth water surface
– Exact measurement result required
– Distance to the water surface normally relatively high
• Properties, sensor:
– Stable and reliable measured values through high averaging
– Insensitive in the close range
•
•
Rain water overfall (weir):
Gauge rate of change: slow gauge change
Process/measurement conditions:
– Ice and condensation on the antenna possible
– Spiders and insect nestle in the antennas
– Turbulent water surface
– Sensorfloodingpossible
• Properties, sensor:
– Stable and reliable measured values through high averaging
– Insensitive in the close range
•
•
Demonstration:
Adjustment for all applications which are not typically level measurement
– Instrument demonstration
– Object recognition/monitoring (additional settings required)
• Properties, sensor:
– Sensor accepts all measured value changes within the measuring range immediately
– High sensitivity against interferences, because virtually no
averaging
•
36
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Caution:
Ifliquidswithdifferentdielectricconstantsseparateinthevessel,for
example through condensation, the radar sensor can detect under
6 Set up with the display and adjustment module
certain circumstances only the medium with the higher dielectric
constant. Keep in mind that layer interfaces can cause faulty measurements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially designed for interface measurement.
The following options are available when "Bulk solid" is selected:
The following features form the basis of the applications:
Silo (slender and high):
• Vessel of metal: weld joints
• Process/measurement conditions:
– Filling aperture too close to the sensor
– System noise in completely empty silo increased
• Properties, sensor:
– Stable measured values through higher averaging
– False signal suppression during setup recommended, required
for automatic false signal suppression
– Automaticfalsesignalsuppressionwithpartlyfilledvessel
Bunker (large-volume):
Vessel of concrete or metal:
– Structured vessel walls
– Installations present
• Process/measurement conditions:
– Large distance to the medium
– Large angles of repose
• Properties, sensor:
– Mean averaging
– High measured value jumps are accepted
•
Bunkerwithfastfilling:
Vessel of concrete or metal, also multiple chamber silo:
– Structured vessel walls
– Installations present
• Process/measurement conditions:
– Measured value jumps, e.g. through truck loading
– Large distance to the medium
– Large angles of repose
• Properties, sensor:
– Lower averaging
– Very high measured value jumps are accepted
40793-EN-140922
•
Heap:
Sensor mounting on movable conveyor belts
Detectionoftheheapprofile
Heightdetectionduringfilling
Process/measurement conditions:
•
•
•
•
VEGAPULS 62 • HART and accumulator pack
37
6 Set up with the display and adjustment module
•
– Measuredvaluejumps,e.g.bytheprofileoftheheaportraverses
– Large angles of repose
– Measurementnearthefillingstream
Properties, sensor:
– Mean averaging
– High measured value jumps are accepted
Crusher:
Vessel: installations, wear and protective facilities available
Process/measurement conditions:
– Measured value jumps, e.g. through truck loading
– Fast reaction time
– Large distance to the medium
• Properties, sensor:
– Little averaging
– Max. reaction speed, very high measured value jumps are
accepted
•
•
Demonstration:
Adjustment for all applications which are not typically level measurement
– Instrument demonstration
– Object recognition/monitoring (additional settings required)
• Properties, sensor:
– Sensor accepts all measured value changes within the measuring range immediately
– High sensitivity against interferences, because virtually no
averaging
•
Through this selection, the sensor is adapted optimally to the application or the location and measurement reliability under the various
basic conditions is increased considerably.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Vessel form
Alsothevesselformcaninfluencethemeasurementapartfromthe
medium and the application. To adapt the sensor to these measurementconditions,thismenuitemoffersyoudifferentoptionsforvessel
bottom and ceiling in case of certain applications.
Setup - Vessel height,
measuring range
38
With this selection, the operating range of the sensor is adapted to
thevesselheightandthereliabilitywithdifferentframeconditionsis
increased considerably.
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
6 Set up with the display and adjustment module
The min. adjustment must be carried out independently of this.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Setup - Adjustment
Since the radar sensor is a distance measuring instrument, the
distance from the sensor to the product surface is measured. For
indication of the real level, an allocation of the measured distance to
the percentage height must be carried out.
3
100%
2
5m
(196.9")
0,5 m
(19.68")
To perform the adjustment, enter the distance with full and empty vessel, see the following example:
0%
1
Fig. 28: Parameter adjustment example min./max. adjustment
1
2
3
Min. level = max. meas. distance
Max. level = min. meas. distance
Reference plane
40793-EN-140922
If these values are not known, an adjustment with the distances of for
example 10 % and 90 % is possible. Starting point for these distance
specificationsisalwaysthesealsurfaceofthethreadorflange.You
canfindspecificationsofthereferenceplaneinchapter"Technical
data". By means of these settings, the real level will be calculated.
The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Setup - Min. adjustment
Proceed as follows:
VEGAPULS 62 • HART and accumulator pack
39
6 Set up with the display and adjustment module
1. Select the menu item "Setup" with [->]andconfirmwith[OK].
Now select with [->] the menu item "Min. adjustment"andconfirm
with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Setup - Max. adjustment
Proceed as follows:
1. Select with [->]themenuitem"Max.adjustment"andconfirm
with [OK].
2. Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
40
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
6 Set up with the display and adjustment module
5. Save settings with [OK]
Diagnosis - Peak value
The respective min. and max. measured value is saved in the sensor.
The values are displayed in the menu item "Peak values".
Diagnosis - Measurement When non-contact level sensors are used, the measurement can be
reliability
influencedbytherespectiveprocessconditions.Inthismenuitem,
the measurement reliability of the level echo is displayed as dB value.
The measurement reliability equals signal strength minus noise. The
higher the value, the more reliable the measurement. With a functioning measurement, the values are > 10 dB.
Diagnoses - Curve indica- The "Echocurve" shows the signal strength of the echoes over the
tion
measuring range in dB. The signal strength enables an evaluation of
the quality of the measurement.
The "False signal suppression" displays the saved false echoes (see
menu "Additional settings") of the empty vessel with signal strength in
"dB" over the measuring range.
A comparison of echo curve and false signal suppression allows a
more detailed statement of the reliability.
Theselectedcurveiscontinuouslyupdated.Asubmenuwithzoom
functions is opened with the [OK] key:
40793-EN-140922
•
•
•
Diagnostics - Echo curve
memory
"X-Zoom":Zoomfunctionforthemeas.distance
"Y-Zoom":1,2,5and10xsignalmagnificationin"dB"
"Unzoom":Resetthepresentationtothenominalmeasuringrange
withoutmagnification
With the function "Echocurvememory" the echo curve can be saved
atthetimeofsetup.Thisisgenerallyrecommended;forusingtheAsset Management functions it is absolutely necessary. If possible, the
curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolutionechocurvecanbedisplayedandusedtorecognizesignal
VEGAPULS 62 • HART and accumulator pack
41
6 Set up with the display and adjustment module
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Additional adjustments False signal suppression
Thefollowingcircumstancescauseinterferingreflectionsandcan
influencethemeasurement:
•
•
•
•
High sockets
Vessel installations such as struts
Agitators
Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account in the level
measurement.
This should be done with a low level so that all potential interfering
reflectionscanbedetected.
Proceed as follows:
1. Select with [->] the menu item "False signal suppression" and
confirmwith[OK].
2. Confirmagainwith[OK].
3. Confirmagainwith[OK].
4. Confirmagainwith[OK] and enter the actual distance from the
sensor to the product surface.
42
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
5. All interfering signals in this section are detected by the sensor
andstoredafterconfirmingwith[OK].
6 Set up with the display and adjustment module
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
signal. The level would then no longer be detectable in this area.
If a false signal suppression has already been saved in the sensor,
the following menu window appears when selecting "False signal
suppression":
Delete: An already created false signal suppression will be completely deleted. This is useful if the saved false signal suppression no
longer matches the metrological conditions in the vessel.
Extend: is used to extend an already created false signal suppression. This is useful if a false signal suppression was carried out with
a too high level and not all false signals could be detected. When
selecting "Extend", the distance to the product surface of the created
false signal suppression is displayed. This value can now be changed
and the false signal suppression can be extended to this range.
Additional adjustments Linearization curve
A linearisation is necessary for all vessels in which the vessel volume
doesnotincreaselinearlywiththelevel-e.g.ahorizontalcylindrical or spherical tank - and the indication or output of the volume is
required. Corresponding linearisation curves are preprogrammed
for these vessels. They represent the correlation between the level
percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the
vessel is displayed correctly. If the volume should not be displayed in
percent but e.g. in l or kg, a scaling can be also set in the menu item
"Display".
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [ESC] and [->] key.
40793-EN-140922
Caution:
Note the following if instruments with appropriate approval are used
aspartofanoverfillprotectionsystemaccordingtoWHG:
If a linearisation curve is selected, the measuring signal is no longer
necessarilylineartothefillingheight.Thismustbeconsideredbythe
user especially when adjusting the switching point on the limit signal
transmitter.
Additional adjustments
- Reset
When a reset is carried out, all settings (with only a few exceptions)
are reset. The exceptions are: PIN, language, lighting, SIL and HART
mode.
VEGAPULS 62 • HART and accumulator pack
43
6 Set up with the display and adjustment module
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of shipmentfromthefactoryincl.theorder-specificsettings.Acreatedfalse
signalsuppression,user-programmablelinearizationcurveaswellas
the measured value memory will be deleted.
Basic settings: Resetting of the parameter settings, incl. special
parameters, to the default values of the respective instrument. Any
stored false signal suppression or user programmable linearisation
curve, as well as the measured value memory, is deleted.
Setup: Resetting of the parameter settings to the default values of the
respective instrument in the menu item Setup. User-generated false
signal suppression, user-programmed linearisation curve, measured
value memory as well as event memory remain untouched. The
linearisation is set to linear.
False signal suppression: Deleting a previously created false signal
suppression. The false signal suppression created in the factory
remains active.
Peak values distance: Resetting the measured min. and max. distances to the actual measured value.
The following table shows the default values of the instrument. Depending on the instrument version, not all menu items are available or
somemaybedifferentlyassigned:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Dependent on the sensor:
Liquid/Water
Bulk solids/Crushed stones, gravel
Demonstration
Vessel form
Vessel bottom, dished boiler end
Vessel height/
Measuring range
Recommended measuring range, see
"Technicaldata" in the supplement
Min. adjustment
Recommended measuring range, see
"Technicaldata" in the supplement
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output
mode
4 … 20 mA, < 3.6 mA
Current output
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Lock adjustment
Released
Vessel top, dished boiler end
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
44
Application
6 Set up with the display and adjustment module
Menu
Menu item
Default value
Display
Language
Like order
Displayed value
Distance
Display unit
m
Scalingsize
Volume
Scaling
0.00 lin %, 0 l
Additional adjustments
6.4
l
100.00 lin %, 100 l
Backlight
Switchedoff
Distance unit
m
Temperature unit
°C
Probe length
Length of the standpipe Ex factory
Linearisation
curve
Linear
HART mode
Multidrop
Address 1
Saving the parameter adjustment data
We recommended noting the adjusted data, e.g. in this operating
instructions manual, and archiving them afterwards. They are thus
available for multiple use or service purposes.
If the instrument is equipped with a display and adjustment module,
the data in the sensor can be saved in the display and adjustment
module. The procedure is described in the operating instructions
manual "Display and adjustment module" in the menu item "Copy
sensor data". The data remain there permanently even if the sensor
power supply fails.
The following data or settings for adjustment of the display and adjustment module are saved:
•
•
•
All data of the menu "Setup" and "Display"
In the menu "Additional adjustments" the items "Sensor-specific
units, temperature unit and linearization"
Thevaluesoftheuserprogrammablelinearizationcurve
40793-EN-140922
The function can also be used to transfer settings from one instrument to another instrument of the same type. If it is necessary to
exchange a sensor, the display and adjustment module is inserted
into the replacement instrument and the data are likewise written into
the sensor via the menu item "Copy sensor data".
VEGAPULS 62 • HART and accumulator pack
45
7 Setup with PACTware
7
7.1
Setup with PACTware
Connect the PC
Via the interface adapter
directly on the sensor
2
1
3
Fig. 29: Connection of the PC directly to the sensor via the interface adapter
1 USBcabletothePC
2 InterfaceadapterVEGACONNECT
3 Sensor
Prerequisites
7.2
Parameter adjustment
For parameter adjustment of the instrument via a Windows PC, the
configurationsoftwarePACTwareandasuitableinstrumentdriver
(DTM) according to FDT standard are required. The latest PACTware
version as well as all available DTMs are compiled in a DTM Collection. The DTMs can also be integrated into other frame applications
according to FDT standard.
Note:
To ensure that all instrument functions are supported, you should
always use the latest DTM Collection. Furthermore, not all described
functionsareincludedinolderfirmwareversions.Youcandownload
the latest instrument software from our homepage. A description of
the update procedure is also available in the Internet.
Further setup steps are described in the operating instructions manual "DTMCollection/PACTware" attached to each DTM Collection and
which can also be downloaded from the Internet. Detailed descriptions are available in the online help of PACTware and the DTMs.
40793-EN-140922
46
VEGAPULS 62 • HART and accumulator pack
7 Setup with PACTware
Fig.30:ExampleofaDTMview
Standard/Full version
All device DTMs are available as a free-of-charge standard version
and as a full version that must be purchased. In the standard version,
all functions for complete setup are already included. An assistant for
simpleprojectconfigurationsimplifiestheadjustmentconsiderably.
Saving/printing the project as well as import/export functions are also
part of the standard version.
In the full version there is also an extended print function for complete
project documentation as well as a save function for measured value
and echo curves. In addition, there is a tank calculation program as
well as a multiviewer for display and analysis of the saved measured
value and echo curves.
The standard version is available as a download under
www.vega.com/downloads and "Software". The full version is available on CD from the agency serving you.
7.3
Saving the parameter adjustment data
40793-EN-140922
We recommend documenting or saving the parameter adjustment
data via PACTware. That way the data are available for multiple use or
service purposes.
VEGAPULS 62 • HART and accumulator pack
47
8 Set up with other systems
8
8.1
Set up with other systems
DD adjustment programs
Device descriptions as Enhanced Device Description (EDD) are
available for DD adjustment programs such as, for example, AMS™
and PDM.
Thefilescanbedownloadedatwww.vega.com/downloads under
"Software".
8.2
Field Communicator 375, 475
Device descriptions for the instrument are available as EDD for parameter adjustment with the Field Communicator 375 or 475.
For the integration of the EDD in the Field Communicator 375 or 475,
the software "Easy Upgrade Utility" is required which is available from
the manufacturer. This software is updated via the Internet and new
EDDs are automatically taken over into the device catalogue of this
software after they are released by the manufacturer. They can then
be transferred to a Field Communicator.
40793-EN-140922
48
VEGAPULS 62 • HART and accumulator pack
9 Diagnosis, asset management and service
9
Diagnosis, asset management and service
9.1
Maintenance
9.2
Measured value and event memory
If the device is used correctly, no maintenance is required in normal
operation.
The instrument has several memories which are available for diagnosis purposes. The data remain even with voltage interruption.
Measured value memory
Up to 100,000 measured values can be stored in the sensor in a ring
memory. Each entry contains date/time as well as the respective
measured value. Storable values are for example:
•
•
•
•
•
•
•
•
Distance
Filling height
Percentage value
Lin. percent
Scaled
Current value
Meas. reliability
Electronics temperature
When the instrument is shipped, the measured value memory is
active and stores distance, measurement reliability and electronics
temperature every 3 minutes.
The requested values and recording conditions are set via a PC with
PACTware/DTM or the control system with EDD. Data are thus read
out and also reset.
Event memory
Up to 500 events are automatically stored with a time stamp in the
sensor (non-deletable). Each entry contains date/time, event type,
event description and value. Event types are for example:
•
•
•
•
Modificationofaparameter
Switch-onandswitch-offtimes
Status messages (according to NE 107)
Error messages (according to NE 107)
The data are read out via a PC with PACTware/DTM or the control
system with EDD.
40793-EN-140922
Echo curve memory
The echo curves are stored with date and time and the corresponding
echo data. The memory is divided into two sections:
Echo curve of the setup: This is used as reference echo curve for
the measurement conditions during setup. Changes in the measurement conditions during operation or buildup on the sensor can thus
berecognized.Theechocurveofthesetupisstoredvia:
•
•
•
PC with PACTware/DTM
Control system with EDD
Display and adjustment module
VEGAPULS 62 • HART and accumulator pack
49
9 Diagnosis, asset management and service
Further echo curves: Up to 10 echo curves can be stored in a ring
bufferinthismemorysection.Furtherechocurvesarestoredvia:
•
•
PC with PACTware/DTM
Control system with EDD
9.3
Asset Management function
The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item "Diagnostics" via the display and adjustment
module, PACTware/DTM and EDD.
Status messages
The status messages are divided into the following categories:
•
•
•
•
Failure
Function check
Outofspecification
Maintenance requirement
and explained by pictographs:
1
2
3
4
Fig. 31: Pictographs of the status messages
1
2
3
4
Failure - red
Outofspecification-yellow
Function check - orange
Maintenance - blue
Failure: Due to a malfunction in the instrument, a failure message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is in operation, the measured value
is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Outofspecification: The measured value is unstable because the
instrumentspecificationisexceeded(e.g.electronicstemperature).
Maintenance:Duetoexternalinfluences,theinstrumentfunction
islimited.Themeasurementisaffected,butthemeasuredvalueis
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
50
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
9 Diagnosis, asset management and service
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Failure
The following table shows the error codes in the status message
"Failure"andgivesinformationonthereasonandrectification.Keep
in mind that some information is only valid with four-wire instruments.
Code
Cause
Rectification
F013
– Sensor does not detect an
echo during operation
– Antenna system dirty or
defective
– Check or correct installation
and/or parameter adjustment
– Clean or exchange process
component or antenna
F017
– Adjustment not within
specification
– Change adjustment according to the limit values (difference between min. and
max.≥10mm)
F025
– Index markers are not con- – Checklinearizationtable
tinuously rising, for example – Delete table/Create new
illogical value pairs
F036
– Failed or interrupted software update
–
–
–
–
F040
– Hardware defect
– Exchanging the electronics
– Send instrument for repair
F080
– General software error
– Disconnect operating voltagebriefly
F105
– The instrument is still in the
start phase, the measured
value could not yet be
determined
– Wait for the end of the
switch-on phase
– Duration depending on
the version and parameter
adjustment up to approximately 3 min.
F113
– EMC interference
– Transmission error with the
external communication
with 4-wire power supply
unit
– RemoveEMCinfluences
– Exchange 4-wire power
supply unit or electronics
F125
– Temperature of the elec– Check ambient temperature
tronicsinthenon-specified – Isolate electronics
range
– Use instrument with higher
temperature range
F260
– Error in the calibration carried out in the factory
– Error in the EEPROM
Text message
no measured
value available
Adjustment
span too small
Error in the
linearization
table
No operable
software
Error in the
electronics
General software error
Determine
measured
value
40793-EN-140922
Communication error
Impermissible electronics
temperature
Error in the
calibration
VEGAPULS 62 • HART and accumulator pack
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
– Exchanging the electronics
– Send instrument for repair
51
9 Diagnosis, asset management and service
Code
Cause
Rectification
F261
– Error during setup
– False signal suppression
faulty
– Error when carrying out a
reset
– Repeat setup
– Carry out a reset
F264
– Adjustment not within the
– Check or correct installation
vessel height/measuring
and/or parameter adjustrange
ment
– Max. measuring range of
– Use an instrument with bigtheinstrumentnotsufficient
ger measuring range
Text message
Error in the
instrument
settings
Installation/
Setup error
F265
– Sensor no longer carries
out a measurement
Measurement
– Operating voltage too low
function disturbed
Function check
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Code
Cause
Rectification
C700
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
Text message
Simulation active
Outofspecification
The following table shows the error codes and text messages in the
status message "Outofspecification" and provides information on
causes as well as corrective measures.
Cause
S600
Impermissible electronics
temperature
– Temperature of the elec– Check ambient temperature
tronicsinthenon-specified – Isolate electronics
range
– Use instrument with higher
temperature range
S601
– Dangerofvesseloverfilling
– Make sure that there is no
furtherfilling
– Check level in the vessel
S603
– Operating voltage below
specifiedrange
– Check electrical connection
– if necessary, increase
operating voltage
Overfilling
Impermissible operating
voltage
52
Rectification
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Code
Text message
Maintenance
– Check operating voltage
– Carry out a reset
– Disconnect operating voltagebriefly
9 Diagnosis, asset management and service
Code
Cause
Rectification
M500
– With the reset to delivery
status, the data could not
be restored
– Repeat reset
– LoadXMLfilewithsensor
data into the sensor
M501
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M502
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M503
Meas. reliability too low
– The echo/noise ratio is too
small for reliable measurement
– Check installation and
process conditions
– Clean the antenna
– Change polarisation direction
– Use instrument with higher
sensitivity
M504
– Hardware defect
– Check connections
– Exchanging the electronics
– Send instrument for repair
M505
– Level echo can no longer
be detected
– Clean the antenna
– Use a more suitable
antenna/sensor
– Remove possible false
echoes
– Optimizesensorposition
and orientation
Text message
Error with the
reset delivery
status
Error in the
non-active
linearization
table
Error in the
diagnosis
memory
Error on an
device interface
40793-EN-140922
No echo available
9.4
Rectify faults
Reaction when malfunctions occur
The operator of the system is responsible for taking suitable measures to rectify faults.
Procedure for fault rectification
Thefirstmeasuresare:
•
•
•
Evaluation of fault messages, for example via the display and
adjustment module
Checking the output signal
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
bedeterminedinthiswayandfaultsrectified.
VEGAPULS 62 • HART and accumulator pack
53
9 Diagnosis, asset management and service
Treatment of measurement errors with liquids
The below tables show typical examples of application-related measurementerrorswithliquids.Themeasurementerrorsaredifferentiated
according to the following:
•
•
•
Constant level
Filling
Emptying
Level
The images in column "Errorpattern" show the real level with a broken line and the level displayed by the sensor as a continuous line.
1
2
0
1
2
time
Real level
Level displayed by the sensor
Notes:
• Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
• If the level indication is too low, the reason could be a line resistance that is too high
Measurement error with constant level
1. Measured value
shows a too low or too
high level
Error pattern
Level
Fault description
2. Measured value
jumps towards 0 %
time
Level
0
3. Measured value
jumps towards 100 %
time
Level
0
time
Rectification
– Adapt min./max. adjustment
– Incorrectlinearizationcurve
– Adaptlinearizationcurve
– Installation in a bypass tube or – Check parameter "Application"
standpipe, hence running time
with respect to vessel form,
error (small measurement error
adapt if necessary (bypass,
close to 100 %/large error close
standpipe, diameter)
to 0 %)
– Multiple echo (vessel top,
– Check parameter "Application",
product surface) with amplitude
especially vessel top, type of
higher than the level echo
medium, dished bottom, high
dielectric constant, and adapt if
necessary
– Due to the process, the amplitude of the level echo sinks
– A false signal suppression was
not carried out
– Carry out a false signal suppression
– Amplitude or position of a false – Determine the reason for the
signal has changed (e.g. conchanged false signals, carry out
densation,buildup);falsesignal
false signal suppression, e.g.
suppression no longer matches
with condensation
actual conditions
54
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
0
Cause
– Min./max. adjustment not
correct
9 Diagnosis, asset management and service
Measurementerrorduringfilling
4. Measured value remains unchanged
duringfilling
Error pattern
0
time
Level
5. Measured value remains in the bottom
sectionduringfilling
0
7. Measured value
jumps towards 0 %
duringfilling
Level
time
0
Rectification
– Echo from the tank bottom
larger than the level echo, for
example, with products with
εr < 2.5 oil-based, solvents
– Check parameters Medium,
Vessel height and Floor form,
adapt if necessary
– Turbulence on the product
surface,quickfilling
– Check parameters, change if
necessary, e.g. in dosing vessel, reactor
time
– Amplitude of a multiple echo
– Check parameter "Application",
(vessel top - product surface) is
especially vessel top, type of
larger than the level echo
medium, dished bottom, high
dielectric constant, and adapt if
necessary
Level
6. Measured value remains momentarily
unchangedduringfilling and then jumps to
the correct level
Cause
– False signals in the close range – Eliminate false signals in the
close range
too big or level echo too small
– Check measurement situation:
– Strong foam or spout generaAntenna must protrude out of
tion
the socket, installations
– Max. adjustment not correct
– Remove contamination on the
antenna
– In case of interferences due to
installations in the close range:
Change polarisation direction
– Create a new false signal suppression
– Adapt max. adjustment
Level
Fault description
0
time
– The level echo cannot be distin- – In case of interferences due to
guished from the false signal at
installations in the close range:
a false signal position (jumps to
Change polarisation direction
multiple echo)
– Chose a more suitable installation position
0
time
– Varying condensation or contamination on the antenna
Level
9. Measured value
jumps sporadically to
100%duringfilling
40793-EN-140922
0
time
Level
10. Measured value
jumpsto≥100%or
0 m distance
– Due to strong turbulence and
– Carry out a false signal supfoamgenerationduringfilling,
pression
the amplitude of the level echo
sinks. Measured value jumps to
the false signal
Level
8. Measured value
jumps towards 100 %
duringfilling
0
time
– Carry out a false signal suppression or increase false
signal suppression with condensation/contamination in the
close range by editing
– Level echo is no longer
detected in the close range
– Check measuring site: Antenna
due to foam generation or false
must protrude out of the socket
signals in the close range. The
– Remove contamination on the
sensorgoesintooverfillprotecantenna
tion mode. The max. level (0 m
distance) as well as the status – Use a sensor with a more suitable antenna
message"Overfillprotection"
are outputted.
VEGAPULS 62 • HART and accumulator pack
55
9 Diagnosis, asset management and service
Measurement error during emptying
12. Measured value
jumps towards 0 %
during emptying
Error pattern
Level
11. Measured value remains unchanged in
the close range during
emptying
0
0
time
Level
13. Measured value
jumps sporadically towards 100 % during
emptying
Cause
Rectification
– False signal larger than the
level echo
– Level echo too small
– Eliminate false signal in the
close range. Check: Antenna
must protrude from the socket
– Remove contamination on the
antenna
– In case of interferences due to
installations in the close range:
Change polarisation direction
– After removing the false signals,
the false signal suppression
must be deleted. Carry out a
new false signal suppression
– Echo from the tank bottom
larger than the level echo, for
example, with products with
εr < 2.5 oil-based, solvents
– Check parameters Type of
medium, Vessel height and
Floor form, adapt if necessary
– Varying condensation or contamination on the antenna
– Carry out false signal suppression or increase false signal
suppression in the close range
by editing
– With bulk solids, use radar sensor with purging air connection
time
Level
Fault description
0
time
Reaction after fault rectification
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
24 hour service hotline
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside normal working hours, seven
days a week around the clock.
Sinceweofferthisserviceworldwide,thesupportisprovidedin
English. The service itself is free of charge, the only costs involved are
the normal call charges.
9.5
Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with appropriate Ex approval may be used.
The new electronics module must be loaded with the default settings
of the sensor. These are the options:
•
•
56
In the factory
Or on site by the user
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
If there is no electronics module available on site, the electronics
module can be ordered through the agency serving you. The electronicsmodulesareadaptedtotherespectivesensoranddifferinsignal
output or voltage supply.
9 Diagnosis, asset management and service
In both cases, the serial number of the sensor is needed. The serial
numbers are stated on the type label of the instrument, on the inside
of the housing as well as on the delivery note.
Whenloadingonsite,firstofalltheorderdatamustbedownloaded
from the Internet (see operating instructions manual "Electronics
module").
Caution:
Alluser-specificsettingsmustbeenteredagain.Hence,youhaveto
carry out a new setup after the electronics exchange.
If you have stored the data of the parameter adjustment during the
firstsetupofthesensor,youcantransferthesetothereplacement
electronics module. A new setup is no more necessary.
9.6
Software update
The following components are required to update the instrument
software:
•
•
•
•
•
Instrument
Voltage supply
Interface adapter VEGACONNECT
PC with PACTware
Currentinstrumentsoftwareasfile
Youcanfindthecurrentinstrumentsoftwareaswellasdetailed
information on the procedure under "www.vega.com/downloads" and
"Software".
Caution:
Instruments with approvals can be bound to certain software versions.
Thereforemakesurethattheapprovalisstilleffectiveafterasoftware
update is carried out.
Youcanfinddetailedinformationatwww.vega.com/downloads and
"Approvals".
9.7
How to proceed if a repair is needed
Youcanfindarepairformaswellasdetailedinformationonhowto
proceed at www.vega.com/downloads and "Formsandcertificates".
By doing this you help us carry out the repair quickly and without having to call back for needed information.
If a repair is necessary, please proceed as follows:
40793-EN-140922
•
•
•
•
Printandfilloutoneformperinstrument
Clean the instrument and pack it damage-proof
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
Please contact the agency serving you to get the address for
thereturnshipment.Youcanfindtheagencyonourhomepage
www.vega.com.
VEGAPULS 62 • HART and accumulator pack
57
10 Dismount
10 Dismount
10.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel or pipeline, high temperatures, corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.
10.2 Disposal
The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have
designed the electronics to be easily separable.
Materials: see chapter "Technicaldata"
For disposal or recycling within the European Union proceed according to the "Electronicsrecycling" and "Battery/Accumulator recycling"
below. Outside the European Union you should take note of the valid
national regulations.
Electronics recycling
This instrument is not subject to the WEEE directive 2002/96/EG and
the respective national laws. Therefore pass the instrument directly
on to a specialised recycling company and do not use the municipal
collecting points. These may be used only for privately used products
according to the WEEE directive.
Battery/accumulator recycling
Note:
The disposal is subject to the directive 2006/66/EG on batteries and
accumulators.
Batteries and accumulators contain some environmentally harmful but also some valuable raw materials that can be recycled. For
that reason batteries and accumulators must not be disposed of in
household waste.
All users are legally obligated to bring batteries to a suitable collection
point, e.g. public collection points. You can also return the batteries
and accumulators to us for correct disposal. Due to the very strict
transport regulations for lithium-based batteries/accumulators, this is
normally not a good idea because shipment is very expensive.
Proceed as follows to dismount the accumulator:
Unscrew the cover of the supply room
Loosen the plug connector
Loosenthefixingscrews
Pull out the complete insert by means of the plastic strap
Correctdisposalavoidsnegativeeffectsonhumansandtheenvironment and ensures recycling of useful raw materials.
58
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
•
•
•
•
11 Supplement
11 Supplement
11.1 Technical data
General data
316L corresponds to 1.4404 or 1.4435
Materials, wetted parts
Ʋ Processfitting
Ʋ Process seal
Ʋ Antenna
Ʋ Antenna impedance cone
Ʋ seal, antenna system
Materials, non-wetted parts
316L, Alloy C22, Alloy 400
On site (instruments with thread: Klingersil C-4400 is
attached)
316L,Alloy C22, Tantalum, 316L electropolished, stainless steel investment casting 1.4848, Alloy 400, 316L
Safecoat coated
PTFE, PP, PEEK, ceramic (99.7 % Al2O3)
FKM(SHSFPM70C3GLT),FFKM(Kalrez6375),FFKM
(Kalrez6230-FDA),graphite(99.9%)
Ʋ Plastic housing
plastic PBT (Polyester)
Ʋ Stainless steel housing
316L
Ʋ Aluminium die-casting housing
Ʋ Seal between housing and housing
cover
Ʋ Inspection window in housing cover
(optional)
Ʋ Ground terminal
Ohmic contact
Processfittings
Aluminium die-casting AlSi10Mg, powder-coated - basis:
Polyester
NBR (stainless steel housing, precision casting), silicone
(aluminium/plastichousing;stainlesssteelhousing,
electropolished)
Polycarbonate
316L
Betweengroundterminal,processfittingandantenna
Ʋ Pipe thread, cylindrical (ISO 228 T1)
G1½ according to DIN 3852-A
Ʋ Flanges
DIN from DN 25, ASME from 1"
Ʋ American pipe thread, conically
Weights
Ʋ Instrument (depending on housing,
processfittingandantenna)
Ʋ Antenna extension
Length antenna extension max.
1½ NPT, 2 NPT
approx. 2 … 17.2 kg (4.409 … 37.92 lbs)
1.6 kg/m (1.157 lbs/ft)
5.85 m (19.19 ft)
Torque for NPT cable glands and Conduit tubes
40793-EN-140922
Ʋ Plastic housing
Ʋ Aluminium/Stainless steel housing
max. 10 Nm (7.376 lbf ft)
max. 50 Nm (36.88 lbf ft)
VEGAPULS 62 • HART and accumulator pack
59
11 Supplement
Input variable
Measured variable
The measured quantity is the distance between process
fittingofthesensorandproductsurface.Thereference
plane is the seal surface on the hexagon or the lower
sideoftheflange.
1
3
4
2
Fig. 46: Data of the input variable
1
2
3
4
Reference plane
Measured variable, max. measuring range
Antenna length
Usefulmeasuringrange
Standard electronics
Max. measuring range
Recommended measuring range
Ʋ Antenna ø 40 mm (1.575 in)
Ʋ Antenna ø 48 mm (1.89 in)
35 m (114.83 ft)
up to 15 m (49.21 ft)
up to 20 m (65.62 ft)
Ʋ Antenna ø 75 mm (2.953 in), ø 95 mm up to 35 m (114.83 ft)
(3.74 in), parabolic antenna
Electronics with increased sensitivity
Max. measuring range
Recommended measuring range
75 m (246.1 ft)
up to 15 m (49.21 ft)
Ʋ Antenna ø 75 mm (2.953 in)
up to 40 m (131.23 ft)
Ʋ Antenna ø 48 mm (1.89 in)
Ʋ Antenna ø 95 mm (3.74 in)
60
up to 20 m (65.62 ft)
up to 50 m (164 ft)
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Ʋ Antenna ø 40 mm (1.575 in)
11 Supplement
Ʋ Parabolic antenna
up to 75 m (246.1 ft)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Ʋ Min. distance to internal installations
> 200 mm (7.874 in)
Ʋ Falsereflections
Biggest false signal, 20 dB smaller than the useful signal
Installation reference conditions
Ʋ Reflector
Deviation with liquids
Flatplatereflector
See following diagrams
10 mm (0.394 in)
2 mm (0.079 in)
0
- 2 mm (- 0.079 in)
0,5 m (1.6 ft)
- 10 mm (- 0.394 in)
1 2
3
Fig. 47: Deviation under reference conditions
1
2
3
Reference plane
Antenna edge
Recommended measuring range
Repeatability
≤±1mm
Deviation with bulk solids
The values depend to a great extent on the application.
Bindingspecificationsarethusnotpossible.
Influenceofthesuperimposedgasandpressuretotheaccuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by
highpressure.Thiseffectdependsonthesuperimposedgasorvapourandisespeciallylargeat
low temperatures.
Thefollowingtableshowstheresultingdeviationforsometypicalgasesandvapours.Thespecified
values refer to the distance. Positive values mean that the measured distance is too large, negative
values that the measured distance is too small.
40793-EN-140922
Gas phase
Air
Temperature
Pressure
1 bar
(14.5 psig)
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
0.00 %
0.22 %
1.2 %
2.4 %
4.9 %
200 °C/392 °F -0.01 %
0.13 %
0.74 %
1.5 %
3.0 %
400 °C/752 °F -0.02 %
0.08 %
0.52 %
1.1 %
2.1 %
20 °C/68 °F
VEGAPULS 62 • HART and accumulator pack
61
11 Supplement
Gas phase
Hydrogen
Steam (saturated steam)
Temperature
Pressure
1 bar
(14.5 psig)
10 bar
(145 psig)
50 bar
(725 psig)
100 bar
(1450 psig)
200 bar
(2900 psig)
-0.01 %
0.10 %
0.61 %
1.2 %
2.5 %
200 °C/392 °F -0.02 %
0.05 %
0.37 %
0.76 %
1.6 %
400 °C/752 °F -0.02 %
0.03 %
0.25 %
0.53 %
1.1 %
100 °C/212 °F 0.26 %
-
-
-
-
180 °C/356 °F 0.17 %
2.1 %
-
-
-
264 °C/507 °F 0.12 %
1.44 %
9.2 %
-
-
366 °C/691 °F 0.07 %
1.01 %
5.7 %
13.2 %
76 %
20 °C/68 °F
Characteristics and performance data
Measuring frequency
K-band(26GHztechnology)
Measuring cycle time
Ʋ Standard electronics approx.
Ʋ Electronics with increased sensitivity
approx.
Step response time1)
Beam angle2)
Ʋ Horn antenna ø 40 mm (1.575 in)
Ʋ Horn antenna ø 48 mm (1.89 in)
Ʋ Horn antenna ø 75 mm (2.953 in)
Ʋ Horn antenna ø 95 mm (3.74 in)
450 ms
700 ms
≤3s
20°
15°
10°
8°
Ʋ Parabolic antenna
3°
Ʋ Average spectral transmission power
density
-14dBm/MHzEIRP
Emitted HF power (depending on the parameter adjustment)3)
Ʋ Max. spectral transmission power
density
Ʋ Max. power density at a distance of
1m
+43dBm/50MHzEIRP
< 1 µW/cm²
Ambient conditions
Ambient, storage and transport tempera- -40 … +80 °C (-40 … +176 °F)
ture
Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk
solids applications, until the output signal has taken for the first time 90 % of the final value (IEC 61298-2).
Outsidethespecifiedbeamangle,theenergyoftheradarsignalisreducedby50%(-3dB)
3)
EIRP: Equivalent Isotropic Radiated Power
1)
2)
62
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Process conditions
Fortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowestvalue
always applies.
11 Supplement
Seal
Antenna impedance
cone
Process temperature (measured on the process
fitting)
FKM (SHS FPM 70C3
GLT)
PTFE
-40 … +130 °C (-40 … +266 °F)
PTFE4)
-40 … +200 °C (-40 … +392 °F)
PEEK
-40 … +200 °C (-40 … +392 °F)
PTFE
-20 … +130 °C (-4 … +266 °F)
PEEK
-20 … +250 °C (-4 … +482 °F)
PTFE
-15 … +130 °C (5 … +266 °F)
5)
FFKM(Kalrez6375)
FFKM(Kalrez6230)
PEEK
-15 … +250 °C (5 … +482 °F)
Graphite
Ceramic
-196 … +450 °C (-321 … +842 °F)
Graphite(processfitting
Alloy C22)
Ceramic
-196 … +400 °C (-321 … +752 °F)
Vessel pressure - horn antenna
Ʋ Antenna impedance cone PTFE
-1 … 40 bar (-100 … 4000 kPa/-14.5 … 580 psig)
Ʋ Antenna impedance cone PP
-1 … 3 bar (-100 … 300 kPa/-14.5 … 43.5 psig)
Ʋ Antenna impedance cone PEEK
-1 … 100 bar (-100 … 10000 kPa/-14.5 … 1450 psig)
Ʋ Antenna impedance cone ceramic
-1 … 160 bar (-100 … 16000 kPa/-14.5 … 2320 psig)
Vessel pressure - parabolic antenna
-1 … 6 bar (-100 … 6000 kPa/-14.5 … 870 psig)
Vessel pressure with swivelling holder
-1 … 1 bar (-100 … 100 kPa/-14.5 … 14.5 psig)
Vesselpressurerelatingtotheflange
nominal pressure stage
see supplementary instructions manual "Flanges accordingtoDIN-EN-ASME-JIS"
Vibration resistance
Ʋ Horn antenna
4gat5…200HzaccordingtoEN60068-2-6(vibration
with resonance)
Ʋ Parabolic antenna
1gat5…200HzaccordingtoEN60068-2-6(vibration
with resonance)
Shock resistance
Ʋ Horn antenna
100 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Ʋ Parabolic antenna
25 g, 6 ms according to EN 60068-2-27 (mechanical
shock)
Data on rinsing air connection
Max. permissible pressure
6 bar (87.02 psig)
40793-EN-140922
Air volume with horn antenna, depending on pressure (recommended area)
Pressure
Withoutrefluxvalve
Withrefluxvalve
0.5 bar (7.25 psig)
3.3 m3/h
1.2 m3/h
0.6 bar (8.70 psig)
3.5 m3/h
1.4 m3/h
0.7 bar (10.15 psig)
3.7 m /h
1.7 m3/h
4)
5)
3
Not with steam
Not with steam
VEGAPULS 62 • HART and accumulator pack
63
11 Supplement
Pressure
Withoutrefluxvalve
Withrefluxvalve
0.8 bar (11.60 psig)
3.9 m3/h
1.8 m3/h
0.9 bar (13.05 psig)
4.0 m3/h
2.1 m3/h
1 bar (14.5 psig)
4.2 m /h
2.2 m3/h
1.5 bar (21.76 psig)
5.0 m /h
3.2 m3/h
2 bar (29.0 psig)
5.5 m3/h
4.5 m3/h
3
3
Air volume with parabolic antenna, depending on pressure (recommended area)
Pressure
Withoutrefluxvalve
Withrefluxvalve
0.5 bar (7.25 psig)
3.0 m3/h
1.2 m3/h
0.6 bar (8.70 psig)
3.2 m3/h
1.4 m3/h
0.7 bar (10.15 psig)
3.4 m3/h
1.7 m3/h
0.8 bar (11.60 psig)
3.5 m /h
1.9 m3/h
0.9 bar (13.05 psig)
3.6 m /h
2.0 m3/h
1 bar (14.5 psig)
3.8 m3/h
2.2 m3/h
1.5 bar (21.76 psig)
4.3 m3/h
3.5 m3/h
2 bar (29.0 psig)
4.8 m /h
4.0 m3/h
3
3
Thread
Closure with
Ʋ Non-Ex
Ʋ Ex
3
G⅛
Dust protection cover of PE
Threaded plug of 316Ti
Refluxvalve-unmounted(asoptionwithnon-Exversion,includedinthescopeofdeliverywithEx
version)
Ʋ Material
Ʋ Seal
Ʋ for tube diameter
Ʋ opening pressure
Ʋ Nominal pressure stage
Display and adjustment module
Display element
Measured value indication
Ʋ Number of digits
Ʋ Sizeofdigits
Adjustment elements
Ʋ unassembled
6 mm
0.5 bar (7.25 psig)
PN 250
Display with backlight
5
W x H = 7 x 13 mm
4 keys
IP 20
Ʋ mounted in the housing without lid
IP 40
Ʋ Housing
ABS
Materials
64
40793-EN-140922
Protection rating
316Ti
FKM(SHSFPM70C3GLT),FFKM(Kalrez6375)
VEGAPULS 62 • HART and accumulator pack
11 Supplement
Ʋ Inspection window
Display and adjustment elements
Display elements
Ʋ Green LED in the supply room
Polyester foil
Indication of the charging process
Ʋ Yellow LED in the supply room
Indication of the charging condition
Ʋ Rotary switch in the supply room
Selection of the mode
Adjustment elements
Ʋ Button outside on the housing
Switchingonandoff
Integrated clock
Date format
Day.Month.Year
TimezoneExfactory
CET
Time format
Rate deviation max.
12 h/24 h
10.5 min/year
Measurement electronics temerature
Resolution
0.1 °C (1.8 °F)
Accuracy
±1°C(1.8°F)
External battery charger
Mains voltage
100 … 240 V AC
Output current (shortcircuit proof) max.
500 mA
Permissible temperature range
Output voltage
Load current limitation
DC plug (inside plus, outside minus)
Integrated accumulator
Type
Voltage
Accumulator capacity
24 V DC
70 mA
2.1 mm
Lithium ions
14.8 V
4.7 Wh
Charging period from 0 % to 100 %
approx.
4h
Operating time in mode 4 (sensor permanently on) with completely charged
accumulator
> 60 h
Operating time after 10 min. charging of
0%
40793-EN-140922
-40 … +85 °C (-40 … +185 °F)
Temperature range
Ʋ Charge accumulator
Ʋ Accumulator operation
>3h
0 … +45° C (+32 … +167 °F)
-20 … +60° C (-4 … +140 °F)
VEGAPULS 62 • HART and accumulator pack
65
11 Supplement
Temperature derating accumulator capacity
Ʋ +25° C (+77 °F)
100 %
Ʋ -10° C (+14 °F)
50 %
Electrical protective measures
Protection, depending on housing version
Ʋ Plastic housing
Ʋ Aluminium housing, stainless steel
housing - investment casting, stainless steel housing - electro-polished
Overvoltage category
Protection class
IP66/IP67(NEMA4X)
IP 66/IP 68 (0.2 bar), NEMA 6P6)
III7)
III8)
11.2 Dimensions
The following dimensional drawings represent only an extract of all possible versions. Detailed
dimensional drawings can be downloaded at www.vega.com/downloads under "Drawings".
Housing
~ 87 mm
(3.43")
ø 79 mm
(3.11")
ø 84 mm
(3.31")
M16x1,5
112 mm
(4.41")
M16x1,5
120 mm
(4.72")
~ 84 mm
(3.31")
M20x1,5/
½ NPT
1
M20x1,5/
½ NPT
2
Fig. 48: Dimensions housing - with integrated display and adjustment module the housing is 9 mm/0.35 in higher
1
2
7)
8)
66
The prerequisites for maintaining the protection rating are a suitable cable as well as correct mounting.
IEC 61010-1
IEC 61010-1
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
6)
Plastic housing
Aluminium/Stainless steel housing
11 Supplement
144 mm (5.67")
2
G1½A / 1½ NPT
x
100
ø40
3"
216
ø75
2"
4"
x
y
1½"
inch
1½"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
ø48
ø95
x
ø1.58"
ø1.89"
ø2.95"
ø3.74"
y
y
mm
22 mm (0.87")
38 mm (1.50")
1
SW 46 mm
(1.81")
22 mm (0.87")
VEGAPULS 62, horn antenna in threaded version
x
Fig.49:VEGAPULS62,hornantennainthreadedversion
Standard
With temperature adapter up to 250 °C
40793-EN-140922
1
2
VEGAPULS 62 • HART and accumulator pack
67
11 Supplement
VEGAPULS62,hornantennainflangeversion
2
166 mm (6.54")
y
60 mm
(2.36")
1
x
mm
y
x
inch
ø48
2"
1½"
100
ø40
3"
216
ø75
2"
4"
120
430
ø95
1½"
3"
4"
y
3.94"
4.72"
8.50"
16.93"
x
ø1.58"
ø1.89"
ø2.95"
ø3.74"
Fig.50:VEGAPULS62,hornantennainflangeversion
1
2
Standard
With temperature adapter up to 250 °C
40793-EN-140922
68
VEGAPULS 62 • HART and accumulator pack
11 Supplement
260 mm (10.24")
VEGAPULS62,hornantennainflangeversion450°C
y
120
216
287
y
inch
4.72"
2"
3" 8.50"
4" 11.30"
x
ø 48
ø 75
ø 95
y
mm
2"
3"
4"
x
ø 1.89"
ø 2.95"
ø 3.74"
x
40793-EN-140922
Fig.51:VEGAPULS62,hornantennainflangeversionwithtemperatureadapterupto450°C
VEGAPULS 62 • HART and accumulator pack
69
11 Supplement
VEGAPULS 62, horn antenna and swivelling holder
max. 15
°
(0.59")
2
x
100
ø 40
3"
216
ø 75
2"
x
y
1½"
4"
inch
1½"
2"
3"
4"
120
430
y
3.94"
4.72"
8.50"
16.93"
ø 48
ø 95
20 m
m
(0.79
")
mm
x
ø 1.58"
ø 1.89"
ø 2.95"
ø 3.74"
y
y
20 m
m
(0.79
")
146 m
m (5.7
5")
40 m
m
(1.58
")
1
x
Fig.52:VEGAPULS62,hornantennaandswivellingholder
1
2
Standard
With temperature adapter up to 250 °C
40793-EN-140922
70
VEGAPULS 62 • HART and accumulator pack
11 Supplement
VEGAPULS62,hornantennaandswivellingholder,threadedfitting
max. 10°
(0.39")
2
102,2 m
m
(4.02")
159,6 mm
(6.28")
53,6 mm
(2.11")
1
SW 70 mm
(2.76")
G2 / 2NPT
102,2 m
m
(4.02")
ø 40 / 4
8
(1.57" / mm
1.89")
ø 40 / 4
8
(1.57" / mm
1.89")
Fig.53:VEGAPULS62,hornantennaandswivellingholder,threadedfitting
Standard
With temperature adapter up to 250 °C
40793-EN-140922
1
2
VEGAPULS 62 • HART and accumulator pack
71
11 Supplement
VEGAPULS 62, parabolic antenna and swivelling holder
max. 15
°
(0.59")
2
130 m
m (5.1
2")
120 m
m (4.7
2")
40 m
m
(1.58
")
1
ø 243
mm (9
.57")
Fig.54:VEGAPULS62,parabolicantennaandswivellingholder
1
2
Standard
With temperature adapter up to 200 °C
40793-EN-140922
72
VEGAPULS 62 • HART and accumulator pack
11 Supplement
11.3 Industrial property rights
VEGA product lines are global protected by industrial property rights. Further information see
www.vega.com.
Only in U.S.A.: Further information see patent label at the sensor housing.
VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.
Nähere Informationen unter www.vega.com.
Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.
VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web www.vega.com.
Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную
собственность. Дальнейшую информацию смотрите на сайте www.vega.com.
VEGA系列产品在全球享有知识产权保护。
进一步信息请参见网站<www.vega.com>。
11.4 Trademark
40793-EN-140922
All the brands as well as trade and company names used are property of their lawful proprietor/
originator.
VEGAPULS 62 • HART and accumulator pack
73
INDEX
INDEX
A
Adjustment 39, 40
Agitator 19
Application
– Bulk solid 37
– Liquid 33
– Standpipe 33
Application area 9
C
Connecting
– To the PC 46
Curve indication
– Echo curve 41
– False signal suppression 41
D
Default values 44
Deviation 54
E
Echo curve memory 49
Echo curve of the setup 41
EDD (Enhanced Device Description) 48
Electronics compartment 27
Error codes 52
Event memory 49
F
False signal suppression 42
Faultrectification53
Flow measurement 25, 26
Foam generation 19
Functional principle 10
N
NAMUR NE 107 51, 52
O
Operation
– System 31
OverfillprotectionaccordingtoWHG43
P
Peak value indicator 41
Polarisation 14
R
Reflectionproperties32
Repair 57
Replacement parts
– Supplementary electronics power pack 11
Reset 43
S
Sensor orientation 18
Service hotline 56
Socket 16
Status messages - NAMUR NE 107 50
T
Type label 8
V
Vessel form 38
Vessel height 38
Vessel installations 19
Vessel insulation 20
Voltage supply 10
I
Inflowingmedium16
Installation position 15
L
Linearisation curve 43
M
74
40793-EN-140922
Main menu 32
Meas. reliability 41
Measured value memory 49
Measurement in a surge pipe 20
Measurement in the bypass tube 23
VEGAPULS 62 • HART and accumulator pack
40793-EN-140922
Notes
VEGAPULS 62 • HART and accumulator pack
75
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice
© VEGA Grieshaber KG, Schiltach/Germany 2014
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone +49 7836 50-0
Fax +49 7836 50-201
E-mail: [email protected]
www.vega.com
40793-EN-140922
Printing date: