11 Supplement
Input variable
Measured variable
The measured quantity is the distance between process
fittingofthesensorandproductsurface.Thereference
plane is the seal surface on the hexagon or the lower
sideoftheflange.
1
3
4
2
Fig. 53: Data of the input variable
1
2
3
4
Reference plane
Measured variable, max. measuring range
Antenna length
Usefulmeasuringrange
Max. measuring range
75 m (246.1 ft)
Recommended meas. range depending on the antenna diameter
Ʋ ø 40 mm (1.575 in)
Ʋ ø 48 mm (1.89 in)
Ʋ ø 75 mm (2.953 in)
Ʋ ø 95 mm (3.74 in)
36535-EN-140209
Ʋ Parabolic antenna
up to 15 m (49.21 ft)
up to 20 m (65.62 ft)
up to 40 m (131.2 ft)
up to 50 m (164 ft)
up to 75 m (246.1 ft)
Output variable
Output signal
4 … 20 mA/HART
Signal resolution
0.3 µA
Range of the output signal
Resolution, digital
3.8 … 20.5 mA/HART (default setting)
< 1 mm (0.039 in)
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current
22 mA
VEGAPULS 68 • 4 … 20 mA/HART two-wire
69