Download SYSTEM 236 Installation Manual

Transcript
F3 750mA KYPO
F2 750mA AUX
F1 2.5A BELL
F4 3A BATTERY
SYSTEM 236 Installation Manual
WARNINGS:
- For continued protection against risk of fire,
replaces fuses only with fuses of same type
and rating
- Disconnect AC, battery, and phone cord
BEFORE Servicing.
Green
Black
Red
Capacity for
emergency standby
at least four hours
2.2k
2.2k
2.2k
AUDIBLE
16.5VAC
10.5-13.5 VCD
25-40VA Protected by
50/60Hz Fuse F1:
Fuse F4 3AG,2.5A
3AG,3 A
Battery
protection
12DVC 6.5AH
or 12VDC, 4.0 A-H
Sealed lead-acid
2.2k
2.2k
2.2k
GENERAL INFORMATION
- Protected by
Fuse F2:
3AG, 0.75A - Do not exceed 4
keypads or max AUX
- Shared with
POWER
keypads and - Protected by Fuse F3 :
3AG,0.75 A
CAUTION:
Total power from terminals bell, Aux
and Key+ Terminals NOT to exceed
800mA, combined (also see NOTE:
below)
POWER SUPPLY INFORMATION
- Use only 12VDC ,6.5AH or 4.0 A-H sealed lead-acid
battery. Replace battery every 4-6 years with Model 1265 or
Model 1240 6.5 A-H standby battery time with 1 keypad is 14
hours at 300 mA 4.0 A-H standby battery time with 1 keypad
is 7 hours at 400 mA
Power demand for AUX POWER, keypads, and sounders
not to exceed maximum ratings
-Install transformer on unswitched power receptacle
-Remove AC and battery power before replacing fuses
-Maximum battery charge current=350 mA
This equipment should be installed in accordance with the
National Fire Protection Association
Standard 72 Chapter
2 (National Fire Protection Association, Battery march Park,
Quincy, MA 02269). Printed information describing proper
installation, operation, testing maintenance, evacuation
planning and repair service is to be provided with the equipment.
- Connect ground wire from door hinge to earth
ground using 16 AWG, green jacketed,
solid-conductor wire
- All outputs are power limited
- If programmed for EOL or Supervised Loop, the
2.2K ohm EOL resistor (Model 9.X, 2.2K) must
be at end of circuit
- Loop voltages: 0.00-1.50 VDC=short
1.60-3.10 VDC=normal
3.20-5.00 VDC=open
-
Are electrically common
- When used as a fire warning system, use a 4-wire
smoke detector (Sentrol #ES-449C) with a Power
Supervisory EOL Relay Module (System Sensor
A77716 Series) at the end of the detector power
loop. Consider the maximum detector alarm load
when confirming that the total alarm load is less
than 800mA.
NOTE
Total power from terminals AUX and KEY+
NOT to exceed 400mA,combined.
SYSTEM 236 Installation Manual
Table of Contents
Recommended Setup (continued)
Subject
Page No.
System FC-236 Terminal Label
Residential Configuration (Recommended)
Installation
Wiring the Panel
System Start-Up
Keypad Setup
Addressing Keypads
Factory Default Settings
Programming Options (Alphabetical List)
Programming the Panel
Programming with the LED Keypad
Programming with the Alpha Keypad
Entering Hexadecimal Numbers
Programming the Alpha Keypad
Programming Letters & Numbers
Special Function Keys
Programming Options (Numerical Order)
Keypad Label Drawer
Telephone Line Problems
Watchdog Indicator
Keypad Operation Command Summary
Help with Common Problems (Troubleshooting)
Reducing False Alarms
Warranty information
Programming Worksheets
Front cover
2
2-3
3-4
4
4-5
5
5
5-6
6-7
6
6
7
7-8
7
8
9-23
24
24
25
25
26-27
28
28
29-32
11. The communicator should not be programmed for Delay
Before Dial.
12. The system must not be programmed to dial a police station.
13. Use screws (supplied ) to secure cover or install a lock on the
cabinet.
14. Loop Response Time should be set to 500ms.
Zone Programming
FIRE LOOP
No Delay Before Dial
24-hour arming
Pulsing audible
Supervised
-latching for heat
-resetting for smoke
-Not shuntable
Not shuntable
BURGLAR LOOP
No Delay Before Dial
NO/NC with EOL
Steady Audible
500ms Loop response Time
INSTALLATION
Mounting
The SYSTEM 236 should be mounted in a location which allows
convenient access to AC power, telephone connections, and earth
ground.
Remove the circuit board from the cabinet. This will prevent
possible damage to the circuit board when removing the
knock-outs.
Remove the knock-outs, as required.
Mark the screw mounting holes on the wall.
Mount the cabinet at the desired height and pass the cables
through the knock-outs.
Replace the circuit board, remembering to connect the ground
Scope of This Manual
lug to the lower left corner of the circuit board.
This manual contains basic installation and programming information
Reconnect the spade lug to the lower door hinge. This provides
for the SYSTEM FC-236 control/communicator. For detailed information
the earth ground connection for the door.
about remote programming, please refer to the Commander II/
Monitor II Operating Manual.
Earth Ground
To ensure the effectiveness of the lightning and transient protection
Accuracy
circuits, the control panel must be connected to
This manual has been carefully checked for accuracy. However,
Earth Ground .
Ideally, this should be a common ground to the power lines,
IntelliSense assumes no liability for inaccuracies or actions resulting
telephone system, and security system. This type of ground, called
from the use of this manual. In addition, IntelliSense reserves the
a
right to modify the SYSTEM FC-236 hardware, software, and
Unified Earth Ground, provides the best protection. The ground
connection, from a grounding rod, cold water pipe or other
manual s without prior notice.
established ground point, is made to the green jacketed wire
providing a ground to the panel housing.
Residential Configuration
Control
Panel
Power
Lines
The following list of options are recommended for a standa rd SYSTE M
FC-236 installation in a residential environment:
1. Program the audible to sound for at least four minutes before
silencing.
2. No zones should be programmed for silent alarm.
3. Fire zones should be programmed for pulsing audible alarm.
4. Burglar zones should be programmed for a steady audible.
5. Burglar loops should be programmed for EOL.
6. Entry delay should not be greater than 45 seconds.
7. Exit Delay should not be greater than 60 seconds.
8. The Dynamic Battery Test should be enabled.
9. The Unit Status Report should be enabled.
10. The 24- hour Check-in (Test Report) should be enabled.
Power Line
Earth Ground
Connecting to
Earth Ground
2
Telephone
Lines
Telephone
Earth Ground
Unified Earth Ground
with Bonded Ground Roots
SYSTEM 236 Installation Manual
Electromagnetic Interference
WIRING THE PANEL
Standby Battery
Vibrating horns can produce electromagnetic interference
(EMI) . While EMI will not damage the SYSTEM 236, it can
cause transmission errors and mis-dialing. To minimize
EMI, install a 0.01 mfd, 100V capacitor across the
terminals of the horn. The capacitor must be located in the
horn.
The SYSTEM 236 is designed to operate using a 12 v, 6.5A-H (Model
1265) or 12V, 4.0 A-H (Model 1240) sealed lead-acid battery. Do not
use non-rechargeable batteries or batteries other than sealed leadacid. It is recommended that you replace. The standby battery every
four to six years.
Install the battery with the terminals oriented toward the hinge side
of the case and the battery mounted as close to the hinge as possible.
Connect the red lead to the positive terminal of the battery and the
black lead to the negative battery terminal. The panel is electronically
protected against reverse battery polarity.
SWITCHED
AUXILIARY POWER
Terminal Labels:
AUX&c
C
AUX
The AUX(+) terminal provides positive 9.3-14.0 VDC
for auxiliary devices that require switched power for
resetting. Typical devices in glass-break and smoke
detectors.
WARNING:
Improper placement of the battery may result in ground trace
shorting on the PCB.
The terminal labelled C provides the power common.
AC POWER
Terminal Label:
AC
ARMING STATIONS
AC AC
AC power is supplied by a 16.5 VAC, 25-40VA
transformer at 50 or 60 Hz. A UL Listed Class 2
transformer must be used. Connect the secondary
of the transformer to the terminals labelled AC on the SYSTEM
236. Use at least 18 AWG (1.02 mm) wire to reduce voltage drops.
T h e p r i m a r y s i d e o f t h e t r a n s f o r m e r m u s t b e c o n n ec t e d t o a n
unswitched receptacle. Do not connect primary to Ground-FaultInterrup (GFI) circuits. Secure the transformer to the wall.
Terminal Labels:
KEY+,C& DATA
KEY+
+
C DATA
-
KEY(+) Terminal (red) provides 9.8-14.0
VDC keypad power.
C (-) Terminal (black) is common.
DATA Terminal (green) is for keypad data.
Maximum wire length for connecting any keypad is 500' (152m) of
22 AWG (0.643mm) copper wire.
AC Power Failure
Red
Black
Green
If an AC power failure lasts more than 15 minutes, the keypads
will display a system trouble and an AC failure report will be sent,
if programmed. When AC is restored for five minutes, the restoral
report will be sent.
Precautions
Do not share the secondary of the transformer with other devices.
A foreign ground can damage the power supply. Voiding the
warranty.
+
-
May not be loaded
on all systems
BAT CLK TAMPER
Do not use any transformer other than that specified in the AC
POWER section above.
ON
Available Power
236
OFF
The maximum total power available at the BELL(+), AUX (+), and
KEY (+) terminals is 800 mA. The switched auxiliary and keypads
share the same power bus. The combined power for the AUX(+)
and KEY(+) terminals is 400 mA. Do not exceed 400mA for all
Keypads and auxiliary devices.
AUDIBLE OUTPUT
7208
7216
Connect the keypad to the control panel as shown in the diagram
above. The Alpha Plus keypad also has a jumper, located near the
piezo, that must be installed when used with the System 236 control
panel.
The SYSTEM 236 is capable of addressing up to seven Alpha and
four LED keypads. Each LED keypad uses40mA of current. Each
Alpha II keypad uses 64 mA of current. See Available Power for current
limitations . See page 4-5 for additional information on keypad setup.
Terminal label:
BELL&C
BELL C
+
The BELL(+) terminal (Audible output)
provides up to 800mA at 9.5-14.0 VDC.
-
Fuse F1
Fuse F2
KEY+ Terminal is protected by a 3 AG, 0.5A, fast-blow fuse.
The BELL(+) Terminal is protected by a 3 AG, 1.0A ,slow-blow fuse
(F1). If any fuse opens, remove AC and DC power, remove the
short or overload condition, then replace the fuse before restoring
power. Do not substitute a higher rated fuse.
3
SYSTEM 236 Installation Manual
Tamper Switches installed in the SYSTEM 236 cabinet
LOOP INPUTS
Terminal Labels:
C
Z2
Z3
SYSTEM 236
Loop Terminals
EOL loop
N.C.
Alam
N.O
Alam
Z4
C
2.2K ohm EOL
Z1
Z1-Z6&C
Loops 1-6
0.00-1.50 VDC=SHORT
1.60-3.10 VDC=normal
3.20-5.00 VDC=open
Z5
C
PRINTED CIRCUIT
BOARD
Z6
Each loop is independently
configured through programming. Loops can be wired
with an open circuit switch, or
closed circuit switch, or with
a 2.2K ohm end-of-line (EOL)
resistor.
TB1
DOOR
TAMPER SWITCH
LEAD-ACID
BATTERY
WALL
TAMPER SWITCH
When programm ed as EOL, either an open or a short will
be reported as an alarm if the system is in an armed state.
TELEPHONE INTERFACE
Use the 9.X PCF cord to connect the SYSTEM
236 to the phone line. The cord has a modular
connector on one end to plug into the wall
outlet and flying leads on the other end to
connect to the panel. Wire the phone connector
as follows:
N.C.
Trouble
N.O
Alam
2.2K ohm EOL
SYSTEM 236
Loop Terminals
Supervised Loop
When operated as a
Supervised Loop, an
open will be reported
as a Trouble. Whether
the system is armed
or disarmed. A short on
a Supervised Loop will
be reported as an alarm
if the system is armed,
but will have no effect if
the system is disarmed.
9.X PCF
The 9.XPCF has eight flying leads on the end.
TAMPER SWITCH INSTALLATION
The cabinet is constructed in order to accommodate two
switches. One tamper for the cover and a second switch for
a wall tamper.To install the tamper switches:
1. Position the tamper switch inside the cabinet at the lower
right corner of the cabinet. For the wall tamper, the plunger
should go through the small hole in the back of the cabinet.
For the door tamper, the plunger should face out from the
cabinet. Refer to the drawing below.
2. Connect the tamper switches in series and wire the tamper
terminals to a dedicated zone of the control panel.
3.Program the dedicated zone as desired: NC, EOL, 24-hour,
etc.
Received a telephone
Received a telephone
outside line
Once the tamper switches are installed, opening the cabinet
door or removing the cabinet from the wall will result in a
tamper signal at the panel.
4
SYSTEM 236 Installation Manual
SYSTEM START-UP
Addressing LED Keypads
The LED keypad also requires an address. The address on the LED
keypad is set by two jumpers (W1 and W2) on the printed circuit
board.
Fifteen minutes after the panel is powered up, it will dynamic ally
test the standby battery by interrupting AC power for two minutes
and monitoring the battery under load.
W1 W2
The chart below shows how to set Jumpers W1 and W2 to
set the address of LED keypads. Any address from 8 to 11
can be used. The exact number is not important, As long
as each LED keypad in the system has a different address number.
In the event that two keypads are accidentally given the same
address, the system will fail to respond to keypad input. Refer to
page24 for assistance in correcting this problem.
Standby Battery Time with One LED Keypad
AUX POWER DRAIN*
STANDBY TIME
6.5 A-H
Battery
50mA
70 mA
150mA
300 mA
400mA
4.0 A-H
Battery
32hours
24 hours
24 hours
14 hours
12 hours
W1
W2
KEYPAD ADDRESS
7 hours
* Total power for all keypads and auxiliary
If you replace the battery after a SYSTEM TROUBLE-LOW BATTERY
message, you must re-test the battery under load conditions. Press
[*][6][4][#] to start the Dynamic Battery Test.
Voltage Variations
Output voltages will vary between9 and 14.4 VDC (worst case),
depending on the load battery condition.
Installed
Installed
8
Removed
Installed
9
Installed
Removed
10
Removed
Removed
11
FACTORY SETTINGS
DEFAULT PROGRAM SETUP
The default programming of the SYSTEM 236 will allow you to use
it as a local panel without any additional programming. The actual
d e f a u l t p r o g r a m m i n g v a l u e s a r e s h o w n o n t h e P ro g r a m mi n g
Worksheet .
KEYPAD SETUP
ALPHA KEYPAD INFORMATION
The Alpha keypad uses a top viewing display. This means the dis play
reads most clearly when viewed from a top angle rather than straight
on or from below. Mounting the keypad at the light switch level and
adjusting the viewing angle gives the best results.
Note: If you connect power before wiring the loops, install a 2.2K
EOL resistor across each loop.
Combinations
Installer combination: 012345
User #1 (Master) combination: 1234
Users #2-6: disabled
Default installer combination: yes
Combination required: no
Faulted Arming type: goof-proof
Opening/Closing: disabled
Adjusting the LCD Display
T o a d j u s t t h e v i e w i n g a n g l e , r e m o v e t h e k ey p a d f ro m t h e b a c k
mounting plate. Towards the bottom centre of the circuit board is
a small hole. Insert a small screwdriver into the hole and adjust
R23, while holding the keypad at its mounting height. Adjust the
potentiometer as necessary for optimu m viewing .
Reporting
Account #1 : 000000
Dialing type: pulse
RPS allowed: yes
Addressing Keypads
Each Alpha and LED keypad installed in the system must have an
address. Addresses must not be repeated. When replacing a
keypad, make sure the replacement has the same address as the
previous keypad. Once all keypads have been addressed, reset
t he p an el b y p r e s s i n g [ m a s t e r C o m b i n a t i o n ] [ * ] [ 6 ] [ 8 ] [ # ] o r
by temporarily removing both AC and DC power.
Zones
Zone 1= Entry/Exit delay-EOL circuit
Zone 2=interior-EOL circuit
Zone 3=doors or windows-EOL circuit
Zone 4=doors or windows-EOL circuit
Zone 5=doors or windows-EOL circuit
Zone 6=fire or smoke-supervised EOL circuit
Panic soft zone: pulsed audible, non-reporting
Addressing Alpha Keypads
The first time you power up the system, unaddressed Alpha keypads
will display KEYPAD ADDRESS? Press any number from 0 through
7 a t e ac h k ey p ad . Th e e xa c t n u m b e r y o u p r e s s i s n o t i m p o r t a n t
as l ong as e ach keypad has a different address number. The keypad
will not accept values outside of the specified range. Should you
accidentally use the same address for more than one keypad, the
system will fail to properly respond to the keypad input, Refer to
page 24 for assistance in correcting this problem.
Testing
Test report interval: 7 days and disabled
Timing
Entry time: 60 seconds and prewarn
Exit time: 30 seconds and prewarn
Bell time: 5 minutes.
Unit Control
Local system: yes
Dynamic battery test: off
5
SYSTEM 236 Installation Manual
Option
PROGRAMMING OPTIONS
The following is an alphabetical listing of all SYSTEM 236
programming options, including Command Locations and Digit
Positions. Digit Positions are inside parentheses ( ).
Option
AC Fail Report Code
AC Line Frequency
AC Restore Report Code
Account Number
Audible Time
Autohome Enable
Bell Fuse Fail Report Code
Bell Fuse Restore Report Code
Cancel Report Code
Closing Report code
Combination Command
Completed Programming Report Code
Daily Battery Test Enable
Default Installer Combination
Delay Before Dial by Enable
Delay Before Dial Time
Dial Attempts
Dial Type
Disable Instant/Home Exit Delay
Disable Loop LEDs
Door Chime Enable
Entry Delay Time
Event Report Receiver Select
Exit Delay Time
Failed To Communicate report Code
Faulted Arming Type
Installer Combination
Keypad RPS Enable
Local System Only
Loop Alarm Report Code
Loop Arming Type
Loop Audible Type
Loop Circuit Type
Loop Receiver Select
Loop Response Time
Loop Restore reporting Code
Loop Restore Type
Loop Shunting Enable
Loop Shunt Report Code
Low Battery Report Code
Low battery Restore Report Code
Master Code
Opening Report Code
Opening/Closing Report Receiver Select
Panic Audible Type
Panic Report Code
Panic Report Receiver Select
Phone Ring Type
Receiver #1 Message Format
Receiver #1 Phone Number
Receiver #1 Receive Format
Location
Receiver #2 Message Format
Receiver #2 Phone Number
Receiver #2 Receive Format
RPS Enable
RPS Phone Number
Set Test Report Countdown Timer
Test Report Code
Test Report interval
Test Report Receiver Select
Trouble Report Code
Trouble Restore Code
Unit Status Report Code
User Arming Type
User Combinations
Watchdog Reset Report Code
Location
18 (3)
08 (6)
18 (4)
0B (1-6)
1B (3)
1B (6)
18(1)
18(2)
15(3)
16(3)
08(5)
17(4)
08(4)
08 (3)
25(1-6)
1B(4)
09(2)
09(6)
1B(5)
08 (1)
23 (1-6)
1B (1)
15(1)
1B (2)
17(3)
08 (2)
00 (1-6)
09 (4)
09 (1)
1C(1-6)
1D-22(4)
1D-22 (5)
1D-22 (6)
1D-22 (2)
1D-2(1)
15(5)
1D-22 (3)
24(1-6)
15(2)
18(5)
18(6)
01 (1-4)
16 (2)
16 (1)
19 (4)
19(1-2)
19(3)
09(5)
0A (2)
0C-0E (1-6)
0A (1)
0A (4)
0F-11 (1-6)
0A (3)
09 (3)
12-14(1-6)
A0 (1)
1A (1-2)
1A (4)
1A (3)
15(4)
15(5)
17(1)
07 (1-6)
01-06 (1-4)
17(2)
PROGRAMMING THE PANEL
You can program the SYSTEM 236 from either the Alpha or LED
keypad, or remotely using the Commander II softwa re. This m anual
provides you with a brief description of each programming option
beginning on page 9. Remote programming information can be found
in the COMMANDER II/MONITOR II Operating Manual.
To Start Keypad Programming
Key in the [installer Combination][*][0][#]. The default Installer
Combination is: 012345. On the LED Keypad, the ARM, SERVICE,
AND AC LED s will flash to indicate programming mode. The Alpha
II keypad will display CMD DATA across the top of the LCD display
to indicate programming mode.
Programming with the LED Keypad
Programming with the LED keypad is a one-step process. Key in the
two-digit address (Command Location), followed by the desired
programming values (program data), then press the [#] key to store
the data. The LED keypad does not display programmed values.
If you are not sure that the correct programming values have been
entered, program the Command Location again.
System 236 LED Keypad Layout
1
2
3
4
5
6
0
7
8
9 PANIC
#
NOTE: To program Command Location A0 with an LED keypad,
remember to enter the Command Location, followed by
the program data, then press the [#] key.
Warning: If you enter a Command Location and then press
the [#] key without entering any data, the keypad will
b e e p 5 t i m e s , i n d i c a t i n g a n e r r o r. To c or r e ct t hi s
problem, simply re-enter the Command Location and
Data, then press the [#] key.
6
SYSTEM 236 Installation Manual
Programming With the Alpha Plus Keypad
PROGRAMMING the ALPHA Plus KEYPAD
Entering program data with an Alpha Plus keypad is a two-step
process. First, key in the two-digit address (Command Location) to
be programmed and press the [#] key. The Alpha keypad displays
the Command Location and the data previously stored. Enter the
new data you wish to store and press the [#] key to write the data.
You can also scroll through the Command Locations in numerical
order by alternately pressing and releasing the [#] key.
You must have the Alpha Plus keypad wired to the SYSTEM236.
Apply power to the panel. You can only program when the panel
is disarmed.
.
NOTE: Programming the Keypad is not the same as
Keypad Programming.
The Alpha Keypad
You can program the Alpha Plus keypads with labels for each of the
6 zones labels , Zone Labels display during the walktest and when
the [#] key is pressed during alarm memory or faults .The Service
Message is displayed during AC failure ,fuse failure, communication
failure , low battery, or watchdog reset. The Dealer Message displays
whenever the system is disarmed .
NOTE: Command Location A0 must be addressed directly. When
programming this Command Location with an Alpha II
keypad, the previously stored data is not displayed.
To program this location, enter the Command Location
followed by the [#] key. Then enter the data to be stored
and again press the [#] key.
These messages can be programmed directly from the Alpha Plus
keypad or remotely using the Commander II/Monitor II software
package. For detailed information about remote programming,
refer to the Commander II /Monitor II Operating Manual (PN 5-051-221-00).
Programming Hexadecimal Numbers
The Alpha keypad may be used to program the control panel. The
cursor is moved to the right using the Emergency (E ) key and to
the left using the Police (P) keys. The Fire (F) key enters a blank
space and moves the cursor one position to the right.
Keypad Message Programming
The Alpha keypad programming template is used to allow the
installer to program messages and zone descriptions into the
Alpha keypads. The template shown on the next page should be
used when programming the keypad.
Data is programmed into the panel using the hexadecimal number
system, which consists of the digits 0-9 and the letters A-F ,The
digits 0-9 are entered directly from the keypad. The chart below
shows how to enter the hexadecimal digits A through F.
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
To activate the keypad programming mode, enter the [Installer's
Code][*][0][1][#]. Information may be entered into the keypad in the
form of letters (upper and lower case ), numbers (0-9), and 22
special symbols. All characters are displayed in the order listed
above, i.e. Upper and lower case letters, numbers, and special
symbols. the [Space] character precedes the letter A .
Key Strokes
*0
*1
*2
*3
*4
*5
To enter a Message or Label, use the [2] key to scroll through
the characters until you reach the desired character, If you scroll
past the desired character, the [8] key may be used to scroll
backwards. When the desired character is display, press the [6]
key to move the cursor to the next character position, the [4] key
moves the cursor to the left , When all characters have been
entered, press the [#] key to write the message and move to the
next message position. Use the [0] key to move backward through
the messages.
The same procedure is used with both the LED and the Alpha
keypads.
End of Programming Segment
The last two Command Locations are CL 25 and CL A0. When you
press the [#] key at these locations, the program will advance you
to CL 26 or CL A1, These locations are not used in the SYSTEM
236. If you enter CL26 or CLA1, either press [*] [#] to exit
programming , or press the Command Location followed by the
[#] key, for the desired programming location.
The Alpha and Alpha Plus Templates, used for programming keypad
messages, are shown on the next page.
The Scrolling order of the Alpha Plus message is:
To Exit Panel Programming
When you have finished programming, press [*][#]. The panel will
also exit the programming mode if you do not press any key
within a five minute period.
SERVICE MESSAGE
DEALER MESSAGE
SOFT ZONE IDENTIFIERS C
HARDWIRED LOOP IDENTIFIERS
KEYPAD ADDRESS
For example to change the Keypad Address:
Enter keypad programming, as described previously, then press [*]
[BYPASS]. This will step backwards one step to Keypad Address. Enter
the [New Address] followed by the [#] key.
7
SYSTEM 236 Installation Manual
ALPHA PLUS Programming Template
ALPHA II Programming Template
PUSH AND HOLD ARROWS FOR FAST SCROLL
PUSH AND HOLD ARROWS FOR FAST SCROLL
CHARACTER
CURSOR
MESSAGES
CHARACTER
CURSOR
CURSOR
CHARACTER
CURSOR
CHARACTER
#
MESSAGES
MESSAGES
BYPASS
#
ENTER EXIT
MESSAGES
Both the Alpha and the Alpha Plus use the same procedure to
program messages.
ENTER EXIT
NOTE: If you do not press any key for 5 minutes,
the keypad will automatically exit the programming
mode.
To Exit Keypad Programming
When you have finished programming, press [*][#]. The keypad will
also exit the programming mode if you do not press any key within a
five minute period.
8
CL 00-07
SYSTEM 236 Installation Manual
Command location 00: Installer Combination
Default Values
Digit Position (1)-(6): Installer Combination
Combination must have 6 digits Valid entries are 0-9.
Command Locations 01-06: User Arming Combination (PIN)
01=User #1 (Master)
02=User #2
03=User #3
04=User #4
05=User #5
06=User #6
Default Values
Digit Position (1)-(4): Arming Combination
Combination must have 4 digits. Valid entries are 0-9.
Master Combination can be used to change other combinations.
To delete a PIN, enter 0 0 0 0.
Command Locations 07: User Opening/Closing Report Enable
0
7
Digit Position (1): User #1 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
Digit Position (2): User #2 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
Digit Position (3): User #3 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
Digit Position (4): User #4 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
Digit Position (5): User #5 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
Digit Position (6): User #6 O/C Report Enable
0=No Opening and No Closing Reports
1=Opening and Closing Reports
9
0
0
0
0
0
CL08 and 09
SYSTEM 236 Installation Manual
Command Locations 08 : Panel Control Options
Default values
8
Digit Position (1) : Disable Loop LEDs
0= No
1= Yes: shuts zone LEDs off after 5 minutes
Digit Position (2) : Faulted Arming Type
0= Goof-proof: zones must be normal or shunted to arm
1= Force Arm: faulted zones will be shunted at end of Exit delay
Digit Position (3) : Default Installer Combination
0= No: this enables the Pirate-GuardTM feature for added security
1= Yes: combination reverts to factory value on power loss
Digit Position (4) : Daily Battery Test Enable
0= No
1= Yes: tests battery under load every 24 hours
Digit Position (5) : Combination Command
0= No
1= Yes: requires combination for Bypass, Instant Arm, keypad-activated RPS, and Test (central station and bell)
Digit Position (6) : AC Line Frequency
0= 50HZ
1= 60Hz
Command Locations 09 : Telco Control Options
Default values
9
Digit Position (1) : Local System only
0= No
1= Yes: disables all communications except RPS
Digit Position (2) : Dialling Attempts
0= 4 attempts
1= 8 attempts
2= 14 attempts
Digit Position (3) : RPS Enable
0= No
1= Yes: allows remote programming to start from off00remise location
Digit Position (4) : Enable Keypad RPS
0= No
1= Yes: allows remote programming to start from on-site keypad command
Digit Position (5) : Phone Ring Type
0= Single ring; uniformly timed rings with long pauses between rings
1= Double ring; rings twice quickly followed by a long pause then rings twice again
Digit Position (6) : Dial Type
0= Touch Tone* DTMF
1= Pulse Dialing
* Touch Tone is a trademark of AT&T
10
CL0A and 0B
SYSTEM 236 Installation Manual
Command Locations 0A: Communications Fromat
Default values
A
Digit Position (1): Receiver #1 Receiver Format
1=Fast “A”, 2300Hz
2=Slow “B”, 1400 Hz
3=SumCheck, 1400Hz
4=SumCheck,2300 Hz
5=CFSK III
6=Ademco DTMF,1400 Hz
Digit Position (2): Receiver #1 Message Format
1=3/1 Extended
2=4/2 (2digit reporting code)
3=CFSK III
Digit Position (3): Receiver #2 Receiver Format
1=Fast “A”, 2300Hz
2=Slow “B”, 1400 Hz
3=SumCheck, 1400Hz
4=SumCheck,2300 Hz
5=CFSK III
6=Ademco DTMF,1400 Hz
Digit Position (4): Receiver #2 Message Format
1=3/1 Extended
2=4/2 (2-digit reporting code)
3=CFSK III
Valid combinations of Receiver Format and Message Format are listed below.
Message Format
Receiver Format(s)
3/1 Extended
All formats, except CFSK III and DTMF,1400 Hz
4/2(2-digit reporting)
All formats, except CFSK III
CFSK III
CFSK III only
Command Locations 0B: Account Number 1
Default avlues
B
Digit Positions (1)-(6): Account Number
Valid entries are 0-F.
The Account Number is right justified. The last digit must be in Position (6).
The SYSTEM 236 will read the account number using:
Digit Positions (4)- (6) in 3-digit accounts
Digit Positions (3)- (6) in 4-digit accounts
Digit Positions (1)- (6) in 6-digit accounts
Fill all unused Digit Positions with 0's.
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
11
Key Strokes
*0
*1
*2
*3
*4
*5
CL OC-0E
SYSTEM 236 Installation Manual
Command Locations OC-0E: Receiver #1 Phone Number
Order in which the numbers will be dialed
Command Locations OC
(1)
(2)
(3)
(4)
(5)
(6)
Command Locations OE
Command Locations OD
(1)
(2)
(3)
(4)
(5)
(6)
(1)
(2)
(3)
(4)
(5)
(6)
Command Location OC: Receiver #1 Phone Number (digits 1-6)
Default Values
E
0
0
0
0
0
C
Digit Positions (1) -(6):Receiver #1 Phone Number (digits 1-6)
0-9=dialing digits
*0=dial tone detect (use if more than one dial tone must be detected)
*2=* (DTMF dialing only, not used in pulse dialing)
*3=# (DTMF dialing only, not used in pulse dialing)
*4=end of number
*5=5 second delay
Digit (1) is dialed first.
You must place a * 4 (EON) after the last digit to be dialed.
Fill in remaining positions with 0 . Zeroes after EON
will not be dialed.
Command Location OD: Receiver #1 Phone Number (digits 7-12)
0
Default Values
0
0
0
0
0
0
0
0
D
Command Location 0E: Receiver #1 Phone Number (digits 13-18)
0
Default Values
0
0
E
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
12
Key Strokes
*0
*1
*2
*3
*4
*5
CL 0F-11
SYSTEM 236 Installation Manual
Command Locations 0F-11: Receiver #2 Phone Number
Order in which the numbers will be dialed
Command Location 0F
(1)
(2)
(3)
(4)
(5)
Command Location 11
Command Location 10
(6)
(1)
(2)
(3)
(4)
(5)
(6)
(1)
(2)
(3)
(4)
(5)
(6)
Command Locations 0F: Receiver #2 Phone Number (digits 1-6)
Default Values
E
0
0
0
0
0
0
F
Digit Positions (1) -(6):Receiver #2 Phone Number (digits 1-6)
0-9=dialing digits
*0=dial tone detect (use if more than one dial tone must be detected)
*2=* (DTMF dialing only, not used in pulse dialing)
*3=# (DTMF dialing only, not used in pulse dialing)
*4=end of number
*5=5 second delay
Digit (1) is dialed first.
You must place a * 4 (EON) after the last digit to be dialed.
Fill in remaining positions with 0 . Zeroes after EON
will not be dialed.
Command Location 10: Receiver #2 Phone Number (digits 7-12)
0
Default Values
1
0
0
0
0
0
0
0
0
0
Command Location 11: Receiver #2 Phone Number (digits 13-18)
0
Default Values
1
0
0
1
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
13
Key Strokes
*0
*1
*2
*3
*4
*5
CL 12-14
SYSTEM 236 Installation Manual
Command Locations 12-14: RPS Phone Number
Order in which the numbers will be dialed
Command Location 12
(1)
(2)
(3)
(4)
(5)
Command Location 14
Command Location 13
(6)
(1)
(2)
(3)
(4)
(5)
(6)
(1)
(2)
(3)
(4)
(5)
(6)
Command Locations 12: RPS Phone Number (digits 1-6)
Default Values
E
1
0
0
0
0
0
2
Digit Positions (1) -(6):RPS Phone Number (digits 1-6)
0-9=dialing digits
*0=dial tone detect (use if more than one dial tone must be detected)
*2=* (DTMF dialing only, not used in pulse dialing)
*3=# (DTMF dialing only, not used in pulse dialing)
*4=end of number
*5=5 second delay
Digit (1) is dialed first.
You must place a * 4 (EON) after the last digit to be dialed.
Fill in remaining positions with 0 . Zeroes after EON
will not be dialed.
Command Location 13: RPS Phone Number (digits 7-12)
0
Default Values
1
0
0
0
0
0
0
0
0
0
0
3
Command Location 14: RPS Phone Number (digits 13-18)
0
Default Values
1
4
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
14
Key Strokes
*0
*1
*2
*3
*4
*5
CL 15-16
SYSTEM 236 Installation Manual
Command Locations 15: Event Reports
1
Default Values
1
9
D
F
E
5
Digit Position (1): Event Report Receiver Select
Shunts, All restores, Status, Trouble, and Cancel
0=Receiver 1 with Receiver
2 as back-up 2=Receiver 2 only
1=Receiver 1 only
3=Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (2): Loop Shunt report Code
Valid entries are 1-F.
This ais a 1-digit reporting code used for all loops.
For 2-digit reporting formats, the loop number will be automatically added as an extension.
Programming a 0 in Position (2) disables shunt reporting for all loops.
Digit Position (3): Cancel Report code
Valid entries are 1-F.
This ais a 1-digit reporting code used for all loops.
For 2-digit reporting formats, the loop number will be automatically added as an extension.
Programming a 0 in Position (3) disables shunt reporting for all loops.
Digit Position (4): Trouble Report code
Valid entries are 1-F.
This ais a 1-digit reporting code used for all loops.
For 2-digit reporting formats, the loop number will be automatically added as an extension.
Programming a 0 in Position (4) disables shunt reporting for all loops.
Digit Position (5): Loop Restore Reporting Code
Restores are sent for alarm, shunt, and trouble.
Valid entries are 1-F.
This ais a 1-digit reporting code used for all loops.
For 2-digit reporting formats, the loop number will be automatically added as an extension.
Programming a 0 in Position (5) disables shunt reporting for all loops.
Command Locations 16: Opening/Closing Reports
Default Values
1
B
(1)
(2)
C
6
Digit Position (1): Opening/Closing Receiver Select
0=Receiver 1 with Receiver 2 as back-up 2=Receiver 2 only
1=Receiver 1 only
3=Receiver 1 and Receiver 2 (Dual Reporting)
Digit Position (2): Opening Receiver Select
Valid entries are 1-F
This is a 1-digit reporting code.
For 2-digit reporting formats, the User ID Number will be automatically added as an extension.
Programming a 0 in Position (2) disables opening reports.
Digit Position (3): Closing Report Code
Valid entries are 1-F
This is a 1-digit reporting code.
For 2-digit reporting formats, the User ID Number will be automatically added as an extension.
Programming a 0 in Position (3) disables closing reports.
15
1
#
(3)
CL 17-18
SYSTEM 236 Installation Manual
Command Locations 17: Status Events Reporting Codes-#1
Default Values
0
0
0
0
(1)
(2)
(3) (4)
7
1
Digit Position (1):Unit Status Report Code
This global command for CL17 and CL 18.
If Position (1) is programmed with a 0 , all status Reports in Cl18 AND cl 18 will be disabled.
If Position (1) is programmed with any value other than 0, all Status Reports in CL 17 and CL 18 which have
been enabled (not programmed with0) will send reports. Status Reporting Codes will be a 2-digit code. The first
digit is the contents of CL 17 (1) and the second digit is the respective Report
code programmed into the panel.
Digit Position (2): Watchdog Reset Report Code
0=No
1-F=Yes: this report code sent after each Watchdog reset
Digit Position (3): Falled To communicate Report code
0=No
1-F=Yes: this report code sent after each failure to communicate
Digit Position (4): Completed Programming Report Code
0=No
1-F=Yes: this report code sent on completion of panel programming
Command Location 18: Status Events Reporting Codes - #2
Default Values
1
0
0
(1)
(2)
0
0
0
0
(5)
(6)
8
(3) (4)
Digit Position (1): Bell Fuse Fall Report code
0=No
1-F=Yes: this report code sent at Bell fuse failure
Digit Position (2): Bell Fuse restore report code
0=No
1-F=Yes: this report code sent at bell Fuse restoral
Digit Position (3): AC Fail Report Code
0= No
1-F=Yes: this report code sent at AC failure
Digit Position (4): AC Restore Report Code
0= No
1-F=Yes: this report code sent at AC restoral
Digit Position (5): Low Battery Report Code
0= No
1-F=Yes: this report code sent at low battery voltage
PROGRAMMING CONVERSIONS
Hexadecimal Value
Digit Position (6): Low Battery restore Report Code
0= No
1-F=Yes: this report code sent when battery voltage returns to normal
16
A
B
C
D
E
F
Key Strokes
*0
*1
*2
*3
*4
*5
CL 19 and 1A
SYSTEM 236 Installation Manual
Command Location 19: Panic Report
Default Values
0
0
1
1
(1)
(2)
(3) (4)
0
0
1
(1)
(2)
(3) (4)
9
1
Digit Position (1)and (2): Panic Report code
Vaild entries are 0-F
Program a 00 to disable Panic Reports.
Digit Position (3): Panic Receiver Select
0=Receiver 1 with Receiver 2 as back-up 2=Receiver 2 only
1=receiver 1 only
3=Receiver 1 and Receiver 2(Dual Reporting)
Digit Position (4): Panic audible Type
1=Pulsing
3=Chirp
2=Steady
4=Silent
Command Location 1A: Test Report
Default Values
1
5
A
Digit Position (1) (2): Test Report code
Vaild entries are 0-F
Program a 00 to disable Test Reports.
Digit Position (3): Test Report Receiver Select
0=Receiver 1 with Receiver 2 as back-up 2=Receiver 2 only
1=receiver 1 only
3=Receiver 1 and Receiver 2(Dual Reporting)
Digit Position (4): Test report Interval
0=Manual (see NOTE)
4=24 hours
1=1 hour
5= 7 days
2=4 hours
6= 14 days
3=12 hours
7= 30 days
8=1 hour, if armed
9=4 hours , if armed
*0= 12 hours, if armed
*1=24 hours, if armed
NOTE: When the Test Report Interval is programmed with a 0 , automatic
Test reporting is disabled. To send a Manual test report to the central station,
refer to the System Test procedures outlined in the Keypad End User Manual
supplied with this System.
PROGRAMMING CONVERSIONS
Hexadecimal Value
A
B
C
D
E
F
17
Key Strokes
*0
*1
*2
*3
*4
*5
CL 1B and 1C
SYSTEM 236 Installation Manual
Command Location 1B: Panel timing
Default Values
1
3
2
(1)
(2)
2
1
0
0
(5)
(6)
5
6
(5)
(6)
B
(3) (4)
Digit Position (1): Entry Delay
1=10 seconds
2=30 seconds
3=60 seconds
4=90 seconds
5=120 seconds
6=150 seconds
Digit Position (2): Exit Dalay
1=10 seconds
2=30 seconds
3=60 seconds
4=90 seconds
5=120 seconds
6=150 seconds
Digit Position (3): Audible Time
1=2 seconds
2=5 seconds
3=10 seconds
4=15 seconds
5=30 seconds
Digit Position (4): Delay before Dial time
1=10 seconds
2=20 seconds
3=30 seconds
4=40 seconds
5=50 seconds
6=60 seconds
Digit Position (5): Disab le Instant/Home Exit Delay
0=No
1=Yes: no exit delay when system is Instant, Home, or Instant/Home armed
Digit Position (6): Autohome Enable
0= No
1=Yes:interior zones automatically shunted when the system is armed and the exit door is not used
Command Location 1C: Loop Alarm reporting Codes
Default Values
1
1
2
(1)
(2)
3
4
C
(3) (4)
Digit Position (1): Loop 1 Alarm report code
valid entries are 1-F.
Zone number is automatically added as the second digit.
Program a 0 to disable Alarm Reports for this loop.
Digit Position (2): digit Position (2):
See Digit Position (1) for programming information.
Digit Position (3): Loop 3 Alarm Report Code
See Digit Position (1) for programming information.
Digit Position (4): Loop 4 Alarm report code
See Digit Position (1) for programming information.
Digit Position (5): Loop 5 Alarm Report code
See Digit Position (1) for programming information.
PROGRAMMING CONVERSIONS
Hexadecimal Value
Digit Position (6): Loop 6 Alarm Report code
See Digit Position (1) for programming information.
A
B
C
D
E
F
18
Key Strokes
*0
*1
*2
*3
*4
*5
CL 1D and 23
SYSTEM 236 Installation Manual
Command Location 1D-22: Loop Control
Default Values
1D=Loop 1
1E=Loop 2
1F=Loop 3
20=Loop 4
21=Loop 5
22=Loop 6
1
1
1
(1)
(2)
1
2
2
0
(5)
(6)
D
(3) (4)
Digit Position (1): Loop Response time
0=10 milliseconds
1=500 milliseconds
Digit Position (2): Loop Receiver Select
0=Receiver 1 with Receiver 2 as back-up
1=receiver 1 only
2=Receiver 2 only
3=Receiver 1 and Receiver 2(Dual Reporting)
Digit Position (3): Loop Restore Type
0=No restoral
1=return to normal
2=return to normal, bell silences
3=Return to normal, system disarmed
Digit Position (4): Loop Arming Type
0=Instant
1=Interior
2=Delay
3=Long Delay
4=24 hours (always armed)
Digit Position (5): Loop Audible type
1=Pulsing
2=steady
3=Chirp
4=silent with no LED
5=Silent with LED
Digit Position (6): Loop circuit Type
NOTE: A Loop programmed as type 1 or 2 will report
0=EOL: alarm on open or short
any open as a trouble condition, regardless of
1=Supervised: trouble on open; alarm on short; follows bell time
panel armed status.
2=supervised, bell latched: trouble on open; alarm on short; bell latched
Command Location 23: Door chime enable
Default Values
2
Digit Position (1): Loop 1 door chime enable
0=No
1=Yes: keypads beep two seconds when loop is faulted
Digit Position (2): Loop 2 door chime enable
Refer to digit Position (1) for programming options.
Digit Position (3): Loop 3 door chime enable
Refer to digit Position (1) for programming options.
Digit Position (4): Loop 4 door chime enable
Refer to digit Position (1) for programming options.
Digit Position (5): Loop 5 door chime enable
Refer to digit Position (1) for programming options.
Digit Position (6): Loop 6 door chime enable
Refer to digit Position (1) for programming options.
19
0
0
0
0
(1)
(2)
(3)
(4)
0
0
(5)
(6)
3
CL 24-25 and A0
SYSTEM 236 Installation Manual
Command Location 24: Shunting enable
Default Values
1
1
1
1
(1)
(2)
(3)
(4)
0
0
0
0
(1)
(2)
(3)
(4)
1
1
(5)
(6)
0
0
(5)
(6)
4
2
Digit Position (1): Loop 1 Shunting Enable
0=No:makes this zone a priority zone (not shunt able)
1=Yes: keypads beep two seconds when loop is faulted
Digit Position (2): Loop 2 Shunting Enable
Refer to digit Position (1) for programming options.
Digit Position (3): Loop 3 Shunting Enable
Refer to digit Position (1) for programming options.
Digit Position (4): Loop 4 Shunting Enable
Refer to digit Position (1) for programming options.
Digit Position (5): Loop 5 Shunting Enable
Refer to digit Position (1) for programming options.
Digit Position (6): Loop 6 Shunting Enable
Refer to digit Position (1) for programming options.
Command Location 25: Delay Before dial enable
Default Values
5
2
Digit Position (1): Loop 1 Delay Before Dial Enable
0=No
1=Yes: this loop will delay dialing on alarm for time programmed in CL 1B (4)
Digit Position (2): Loop 2 Delay Before Dial Enable
Refer to digit Position (1) for programming options.
Digit Position (3): Loop 3 Delay Before Dial Enable
Refer to digit Position (1) for programming options.
Digit Position (4): Loop 4 Delay Before Dial Enable
Refer to digit Position (1) for programming options.
Digit Position (5): Loop 5 Delay Before Dial Enable
Refer to digit Position (1) for programming options.
Digit Position (6): Loop 6 Delay Before Dial Enable
Refer to digit Position (1) for programming options.
Command Location A0: Set Test Report Countdown Timer
A
Digit Position (1): Set Countdown Timer
This command will sets the time when the first test Report is transmitted to the central station.
The SYSTEM 236 will use this transmission time whenever it is powered up or the CPU is reset
(unless CL A0 is reprogrammed).
0
1
2
3
4
=
=
=
=
=
1/4 hour
1/2 hour
1 hour
2 hours
3 hours
5 = 4 hours
6 = 6 hours
7 = 8 hours
8 = 10 hours
9 = 12 hours
Example:
*0 = 14 hours
*1 = 16 hours
*2 = 18 hours
*3 = 20 hours
*4 = 22 hours
*5 = 24 hours
The time is 1500 hours (3:00 pm). You want the
first Test Report to transmit at 0100 hours (1:00
am). 3:00pm+ 10 hours = 1:00 am. Program the
value 8 in Position (1) of CL A0.
20
SYSTEM 236 Installation Manual
TESTING
FCC NOTICE
Once the installation is complete, connect AC and DC power.
Complete programming, if required. Test all panel operations.
WARING: This device is intended to be installed by a
professional alarm installer.
The user shall be cautioned that changes or modifications
not expressly approved by Intelligence could void the
user s authority to operate the equipment.
TO THE INSTALLER
Regular main tenanc e and inspection (at least monthly) by the installer
and frequent testing by the user are vital to the continuous and
satisfying operation of any alarm system.
The installer should assume the responsibility for developing and
offering a regular maintenance program to the user, as well as
acquainting the user with the proper operation and limitations of
the alarm system and its component parts.
Recommendations must include a specific program of regular
testing (at least weekly) to insure that the system is operating
properly at all times.
This equipment complies with FCC Rules, Part 68.
On the outside of this equipment is a label that contains, among other
information, the FCC Registration Number and Ringer Equivalence
Number (|REN) for this equipment. If requested, provide this
information to your telephone company.
The REN is useful to determine the quantity of devices you may
connect to your telephone line and still have all of those devices ring
when your number is called. In most, but not all areas, the sum of the
REN'S devices should not exceed five (5.0). To be certain of the
number of devices you may connect to your line, as determined by
the REN, you should call your local telephone company to determine
the minimum REN for your calling area.
TELEPHONE LINE PROBLEMS
In the event of telephone line problems, disconne ct the SYS TEM
FC-236 by removing the modu lar connector plug from the Telco interface jack. Do not disconnect the connection inside the SYSTEM
FC-236 cabinet. Doing so will prevent the premise phones from
operating. If your phone works correctly after the control panel
has been disconnected from the phone line, the control panel has
a problem and should be returned for repair
Should you experience trouble with the telephone lines, disconnect
the equipment from the line to determine the source of the trouble.
If it is determined that the equipment is malfunctioning, discontinue
its use until the malfunction has been corrected. Any repairs or
alterations made by the user to this equipment, or equipment
malfunctions, may give the telephone company cause to request
the user to disconnect the equipment. Repairs to this equipment
should be made by an authorized agent of IntelliSense. Contact
your local alarm installation company for service.
If the phone does not work correctly after the control panel has been
disconnecte d from the phone line, notify the telephone compa ny
and request prompt repair. The user may not under any circumstance (in or out lf warranty) attempt any service or repairs on
the SYSTEM FC-236. The control panel must be returned to our
factory an authorized service agency for repairs.
Should this equipment cause harm to the telephone network, the
telephone company may temporarily discontinue your service. If
possible, they will provide you with advance notice. Otherwise th
ey will notify you as soon as possible. The telephone company will
also advise you of changes in its facilities, equipment, operations
or procedures which could affect the operation of your equipment,
allowing you the opportunity to maintain uninterrupted service. You
will also be advised of your right to file a complaint with the FCC.
This equipment must not be used on party lines or coin operated
phone lines.
Watchdog Indicator
DS1
WATCH
DOG
FCC Part 15 Notice
This equipment has been tested and found to comply with the limits
for Class B digital devices, pursuant to part 15 of the FCC Rules.
These limits are designed to Provide reasonable protection against
harmful interference in a residential installation.
The SYSTEM 236 is protected by an advanced circuit that
constantly monitors the microprocessor.
As long as the panel is power and operating normally, theDS1 LED
on the circuit board will flash. If the Watchdog circuit detects a
failure, it will attempt to reset the panel and make the Ds1 LED
light steadily.
This equipment generates, uses, and can radiate radio frequency
energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
If the panel resumes normal operations after a Watchdog reset, clear
.
the Ds1 LED by resetting the panel or pressing [*][1][#],then test
the system, No further action is required.
If the panel does not operate properly after a Watchdog reset, call the
Technical Support Hotline.
Reorient the radio/television antenna.
Connect the AC transformer to a different outlet so that
the control panel and radio/television are on different
branch circuits.
Relocate the equipment with respect to the radio/
television.
Consult the dealer or an experienced radio/television
technician for help.
FCC Registration Number: C2DCHN-75290-AL-E
Ringer Equivalence:0.3B
CANADIAN EMISSION REQUIREMENTS
This digital apparatus does not exceed that Class B limits
for radio noise emissions from digital apparatus set out in
the Radio interference Regulations of the Canadian
Department of Communications.
21
SYSTEM 236 Installation Manual
Keypad Operation Command Summary
The majority of the keypad commands apply equally to the LED and Alpha II keypads. Some keypad commands, however,
apply to the LCD keypad only.
The following Keypad Commands apply to both the LED and Alpha II keypads:
Function
Arm/Disarm
Bypass Zone (n)
Chime On/Off
Change Combo
Clear Alarm Memory
Entry/exit Pre-Alarm
Error Tones
Exit Programming
Home Arm
Instant Arm
Instant Home Arm
Keypad Activated RPS
Keypad Tone disable
Panic Alarm
Reset Aux Power
Reset Panel
Test-Battery
Test-Bells
Test-Central Station
Test-Local Walk Test
Comments
Delays active
[n] is zone # 1-6; Combo may be required
Must be done from Master
Combination( User #1)
Toggle Pre-Alarm tones on and off
Toggle Error Tones on and off
Keystroke Sequence
[Combination] [#]
[Combination]*][2][n] [#]
[*][5][#]
[Master Combo][*][0][#][User No.][#]
[New Combo][#][New Combo][#]
[*][1][#]
[*][5] [2][#]
[*][5] [4][#]
[*] [#]
[Combination][*] [4][#]
All interior zones are shunted simultaneously;
Exterior zones armed; Combo may be required
Converts all delayed zones to instant; Combo
[Combination][*] [7][#]
may be required
Arms exterior zones, shunts interior zones,
[Combination][*] [4][7][#] or
Entry delays converted to Instant; Com bo
[Combination][*] [7][4][#]
may be required
If enabled, CL 09 (4); Combo may be required
[Combination] [*][0][2][#]
Toggle Entry/Exit Pre-Alarm and confirmation/ [*][5] [1][#]
Error tones on and off
Keypad activated
[9] (Hold for 3 seconds)
If resettable devices are connected to
[*][6] [2][#]
Terminals labelled AUX (+) and C
Panel must be disarmed
[Master Combo][*][6][8][#]
Use after correcting Low Battery problem
[*][6][4][#]
Combo may be required
[Combination] [*][6][3][#]
Combo may be required
[Combination] [*[][6][1][#]
Combo may be required
[*][6][0][#]
NOTE: For additional information about combination command requirements, see page 26 and CL 08 (5)
.
The following Keypad commands apply to the Alpha II keypad only:
Function
Comments
Keystroke Sequence
Arm Tones Toggle On/Off
[*][5][4][#]
Audible Feedback Toggle
[*][5][1][#]
Backlight Toggle On/Off
[*][8][#]
Display Keypad Model
[*][9][#]
&Revision Number
Chime Toggle
[*][5][3][#]
Pre-warn Toggle On/off
[*][5][2][#]
The following Keypad commands are Installer Only Commands:
Function
Alpha Keypad Programming
Alpha Keypad Test
Kill/Revive Panel
Panel Programming
Comments
Start Programming the Keypad
Keypad must be disconnected from panel
Panel must be disarmed
Start Programming the Panel
22
Keystroke Sequence
[Installer Combination] [*][0][1][#]
[*][6][7][#]
[Installer Combination] [*][6][9][#]
[Installer Combination] [*][0][#]
SYSTEM 236 Installation Manual
Survey of Most common Questions
The following is a summary of the questions most frequently asked of our Technical Support Department.
Question: How do I program the panel with the LED keypad?
Answer: To program with the LED keypad, enter the command Location to be programmed, the Data to be programmed
and press the [#] key, (See also pages 6.)
For Example:
CL
[0][2]
To program User #2 with a PIN of 4-5-3-5, enter the following keystrokes:
Data to Store
[4] [5] [3] [5]
Write data
[#]
Question: How do I access Alpha Keypad Programming to enter Zone Labels?
Answer: To begin Alpha Keypad Programming (you cannot program the LED keypad), enter [Installer Combination]
[*][0][1][#] . Then scroll to the desired message location. (See also pages 7.)
Question: How do I interpret a Trouble on the LED keypad? How do I clear a Trouble on the LED keypad?
Answer: A number of conditions may cause the Service LED to light. See the chart below for additional information.
Trouble LED
Flash Slow
On
On
On
Flash Fast
On
Question:
Answer:
Power LED
On
On
Off
Flash Slow
On
On
Zone LED's
Off
Flash Slow
Off
Off
Off
Off
Cause
Watchdog
Zone Trouble
AC Failure
Low Battery
System Trouble (Comm Fail)
System Trouble (Bell Fuse Fail.)
How do I enter hexadecimal numbers when using keypad programming?
Hexadecimal values are entered through the use of the [*] key and one of the digits [0]-[5]. For additional
help with entering hexadecimal numbers, refer to page 6-7. The hexadecimal conversion chart is also
found at various locations throughout the programming section of the manual.
Question: What is an Interface error 1 and how do I correct the error?
Answer:
This error is caused by a problem with the Data line (Green wire) between the panel and the keypad. Check
the connection to ensure that the wire is not pinched or loose. Also try disconnecting all keypads from the
panel (one at a time), resetting the panel after each keypad is removed. Remember, to reset the panel press:
[Master Combination] [*][6][8][#]
Question: How do I reset Alarm Memory?
Answer:
To Clear Alarm Memory, press [*][1][#]
Question: How do I address an Alpha Keypad for the first time?
Answer: If you have an Alpha keypad that has never been addressed, when power is initiall y applied, the display wil l
read KEYPAD ADDRESS? To enter the address, simply press a number between 0 and 7. Remove panel
power for 3seconds and then re-apply power to reset the system. For additional information about Keypad
addressing, see page 5.
NOTE: If operating at or near the limit of AUX Power and Keypad Power, you may need to remove power for up to 30
seconds in order for the system to reset properly.
Question: Why do my loops fail to respond after changing the programming?
Answer: In order for the panel to recognize the programming changes for the loops, either the loops have to be tripped
and restored or the panel must be reset ([Master Combination] [*][6][8][#]).
23
SYSTEM 236 Installation Manual
Question: How do I interpret the Unit Status Reports? Can the codes be changed?
Answer:
Status Reporting is divided between CL 17 and CL 18. Each Reporting Code of the Unit Statu s Report is a
two -digit code. The first digit is the data programmed into CL 17 Digit Position (1) and may be any value
from 0-F. The second digit is the data programmed into the respective Status Report code. Please note that
programming a 0 into cl 17 (1) will disable all Unit status Reports in CL 17 and 18. Additional information
about Unit status reporting Codes can be found on page 16 in the programming section.
Question: How do I enter Receiver and RPS Phone Numbers ? Why do I have to enter the E at the end of the number?
Answer: The System 236 is designed to handle phone numbers up to 18 digits long, but the firmware can only handle
6 digits per command Location. This means that 3 Command Locations are required to store a phone number.
With variations in number length and special characters which may need to be included, the software needs
some method of determinin g the end of the number. The E (entered by pressing [*][4]) tells the software that it
has reached the end of the phone number and to ignore any additional digits.
For Example: To program the panel for Receiver #1 with a phone number of 555-1212 and disable the call
waiting feature using *70, enter the following sequence:
Command Location 0C
C
( 1)
7
( 2)
0
( 3)
5
( 4)
Command Location 0E
Command Location 0D
5
5
( 5)
( 6)
1
2
1
2
( 1)
( 2)
( 3)
( 4)
NOTE: Entering [*][2] in CL 0C (1) will display the value
C
E
( 5)
0
0
0
0
0
( 6)
( 1)
( 2)
( 3)
( 4)
0
( 5)
0
( 6)
and entering [*][4] in CL 0D (5) will display the value
E
Question: How can I correct the problem of two Alpha keypad with the same address?
Answer: When two keypads have been given the same address, a conflict occurs on the data bus since two keypads
are trying to communicate at the same time. The only way to correct the problem is to disconnect bo th
keypads and then re-address one of them, making sure that the address is not used by any other keypad. To
re-address the keypad, enter Alpha Keypad Programming ([Installer Combination] [*][0][1][#]) and scroll
backward one step [*][BYPASS] . Then enter the new address. Don't forget to reset the panel ([Master
Combination] [*][6][8][#]) after changing the address, so the panel knows how to properly address the keypad.
For additional information about keypad addressing, see page 5.
Question: Why can't my panel communicate with the Central Station?
Answer: There are several reasons for the panel not communicating. The first place to look is CL 09 (1). This is the
Telco Control, if Digit Position (1) is programmed with a1, all communication except RPS is disabled. If 09 (1)
is programmed with a 0, check to ensure that all of the following parameters are properly set:
Account Number 1 is programmed into CL 0B
Receiver #1 Phone Number is correctly programmed into CL 0C-0E
Receiver Format and Message Format agree CL 0A
Telco Control Options (CL 09) are correctly programmed.
The RJ-31X jack is correctly wired (pins 4 & 5 are not switched with 1 & 8)
24
SYSTEM 236 Installation Manual
Recommendations for Reducing False Alarms
The recommendations contained in this section are designed to assist you in reducing false alarms. The first column
contains the Command Locations and Digit Positions in parentheses( ). The second column is the recommended program
option followed by a brief explanation.
Program Option
CL
Program Function
Comments
Arming/Com bination 08(5)
options
Combi nation
Command
This feature is enabled to prevent unauthorized users from activating
certain keypad functions. When activated, this Command will require
a valid User Combination to perform such functions as Bypassing
a Zone, Group Bypassing, Keypad Activated RPS, Central Station
and Bell Testing, and Instant Arming. For additional assistance with
commands requiring User Combinations, see page 22 (comman d
Summary).
Loop Control
1D-22 (1)
Loop response
Time
This option determines the response time of the loop itself. It acts as
a buffer on the loop to minimize the possibility of fast acting sensors,
such as swingers on window foil, producing false alarms.
Loop Control
1F-22 (3)
Loop Restore
Type
This option is used in conjunction with CL 15 Digit Positions (5),
Restore Reporting Code, and CL 15 (1), Event Report Receiver Select.
The panel can be programmed to send a Restoral Report only when
the loop is normal and the system is disarmed. With this arrangement,
any loop which is triggered multiple times while armed will only send
one alarm report until the system is disarmed. This prevents the system
from tieing up the p hone line with continuous alarm and restoral
reports.
Loop Control
1D-22 (4)
Loop Arming
There may be occasion where it is desirable to program all doors and
interior points as delayed. Or you may need to program interior zones
to be delayed only during the Entry/Exit Delay time. This Command
Location allows a variety of Arming Types to help minimize false alarms.
Type
Event Re porti ng
15 (1 & 3)
Can cel Repo rt
Code/Cancel
Report Receiver
Select
This feature should always be enabled on reporting systems, especially
if the system does not send Opening and Closing Reports. A Cancel
Report is sent to the monitoring station in the event that an Authorized
User clears the alarm while the bell is still active. The Cancel Report
Code (Digit Position 3) is actually a two-digit code with the first digit
being programmed by the installer and the second digit being the
User ID # when the report is sent. Digit Position (1) determines which
receiver gets the Cancel Report.
Loop Switches
25(1-6 )
Delay Before
Dial
This option programs the loops to have a delay after they are triggered
to allow the User time to shut down the system in the event of an
accidental triggering of the zone. The amount of time is determin ed
by the value programmed into CL 1B Digit Position (4). The time
delay may be between 10 and 60 seconds, in 10 second intervals.
25
SYSTEM 236 Installation Manual
THE LIMITATIONS OF YOUR ALARM SYSTEM
While the SYSTEM 236 is an advanced design security
system, it does not offer guaranteed protection against
burglary, fire, or other losses. Any alarm system, whether
commercial or residential, is subject to compromise or
failure-to-warn for a variety of reasons. These include:
Intruders may gain access through unprotected openi ngs
or have the technical sophistication to bypass an alarm
sensor or disconnect an alarm warning device.
Intrusion detectors, smoke detectors, and many sensing
devices will not operate without power. Devices powered
by AC will not work if their AC power supply is off for any
reason and their back-up batteries are missing, dead, or
improperly installed.
Alarm warning devices such as sirens, bells, and horns
may not alert people or wake up sleepers if they are located
on the other side of closed or partly closed doors. If warning
devices are on a different level of the residence from the
bedrooms, they are less likely to waken or alert people inside
the bedrooms.
Telephone lines needed to transmit alarm signals from a
premise to a central monito ring station may be out of
service or temporarily out of service. Telephone lines are
subject to compromise by sophisticated methods of attack.
26
SYSTEM 236 Installation Manual
SYSTEM 236 Programming
Client:
Worksheet
SYSTEM 236 Phone Number:
Address:
Installer:
Date:
VOLTS
CONTROL LOCATION:
KEYPADS
AC volts (AC terms):
Address
Location
0
AUX POWER VOLTS
(terms AUX+ and C):
1
BATTERY VOLTS
Under load-AC off:
2
BREAKER # AND LOCATION:
3
CURRENT
Keypads
4
AUX POWER
+
5
6
TOTAL
(400mA allowed):
=
7
0
0
0
0
1
0
3
0
5
0
7
0
9
1
2
3
4
5
#
1
2
3
4
0
0
1
0
0
0
1
0
0
0
1
Name:
0
Name:
#
Name:
1
0
0
0
2
0
4
0
6
0
User #3-Master
#
0
0
0
User #1-Master
#
0
Installer
Combination
0
User #5-Master
0
0
#
User Arming
Type
0
8
#
Telco control
Options
0
A
1
0
0
0
0
0
0
1
0
User #2-Master
#
Name:
#
Name:
#
Name:
0
User #4-Master
0
0
0
User #6-Master
1
#
1
27
0
1
1
1
#
Panel control
Opeions
Communications
Format
SYSTEM 236 Installation Manual
0
0
0
0
0
0
0
B
#
Account Number
Phone #1 (1st 6 digits)
E
0
0
0
0
0
(Middle 6 digits)
0
0
C
0
#
0
0
0
0
0
1
1
2
1
5
1
7
1
9
1
B
1
D
1
F
2
1
2
3
2
5
0
0
9
D
F
E
#
0
0
0
0
0
1
1
1
1
1
0
0
2
1
1
1
0
0
2
1
1
1
0
0
1
2
0
0
0
0
0
2
2
2
0
0
0
0
0
0
1
0
0
0
0
1
8
1
A
0
C
#
Loop 1
Control
1
E
#
Loop 3
Control
2
0
#
Loop 5
Control
2
2
#
Door Chime
Dial
2
4
#
Delay Before
Dial
0
0
0
0
0
B
C
0
0
0
0
0
0
1
1
1
1
2
1
1
1
1
3
0
0
5
1
1
0
1
4
1
0
4
1
0
0
0
0
0
5
2
2
1
1
Status Events
Reporting
Codes - #2
Test Report
6
#
Loop Alarm
Reporting Codes
#
Loop 2
Control
#
Loop 4
Control
#
Loop 6
Control
0
0
1
1
Shunt Enalbe
#
0
#
Opening/Closing
Reports
#
1
28
0
4
#
1
1
0
#
0
1
#
0
Timing/Keypad
Control
0
(Last 6 digits)
0
#
0
1
0
1
6
0
#
0
1
#
1
0
(Last 6 digits)
3
Event Reports
0
E
0
#
Panic/Duress
#
3
0
Status Event
Reporting Codes -#1
#
0
0
0
(Middle 6 digits)
0
#
1
(Last 6 digits)
0
0
RPS Phone (1st 6 digits)
0
0
#
0
#
0
0
(Middle 6 digits)
0
F
E
0
D
Phone #2 (1st 6 digits)
E
0