CHAPTER 6 INPUT SIGNAL SETTINGS 6.1 INPUT TYPE AND SCALING SETTING. This section explains input signal type and range. Procedure Press [Page] and [En] at the same time, enter the configuration menu. Use arrow keys and [En] to input the password, enter the [Analog Input] screen. Input 2010-06-21 15:04:23 Chnl01 Tag: Chnl: 1 Type: 4-20mA Scale: 0.0 Vacu: No 100.0 Unit: % Sqrt: No Filter: 0.0Sec Cut: 0.0% BurnOut: Accu: No Magnify: Freq K: Min 1 1 Adjust K: 1.00 0.00 Adjust B: LL L H HH Zone 0.00 Value: 0.0 0.0 100.0 100.0 Relay: 0 0 0 0 ClrAccu Copy Paste Edit Exit 1. Input channel Select the channel to set the parameter, which is limited by the input board channel’s number. 2. Channel type Set the current channel’s input signal type. 3. Channel range Set the current channel's input signal measuring range. 4. Adjusted value Set the adjusted value of the current channel, display data measurement data * k + B. Note ●The high and low value should not be the same. ●The low value is -9999 and high range is 19999. IM01B82R01-01E 65