Ethernet gateways
Tab. 13: Auto update
mode configuration
command
Note
Parameter
Command
Request data set 1
Request data set 2
Request data set 3
Request data set 4
Heartbeat
mode update
rate
Length
WORD
WORD
WORD
WORD
WORD
WORD
Value
00E1hex = Auto update control
0 = Do not send data set 1
1 = Send data set 1
0 = Do not send data set 2
1 = Send data set 2
0 = Do not send data set 3
1 = Send data set 3
0 = Do not send data set 4
1 = Send data set 4
0 = Disable heartbeat messages
Non-zero = Enable heartbeat message at specified rate in ms.
Minimum = 40 ms
Auto update is disabled if all Request Input Data Set flags are set to zero.
The response message returned to the application by the gateway:
Tab. 14: Auto update
mode configuration
response
Parameter
Command
Length
WORD
Value
001Ehex = Response to the auto update control message
Configuration via samos®PLAN tool
In order to configure the Gateway writes to Address/Port (Auto update) mode of the
gateway via the samos®PLAN tool, perform the following steps:
 Open the samos®PLAN and load the hardware configuration including the gateway.
 Click on the Gateway button above the main window and select the respective gateway
to open the gateway configuration dialog.
 Click on TCP/IP configuration on the left hand menu. The following dialog appears:
Fig. 17: TCP/IP
configuration for auto
update
 Check the Connect to checkbox.
 Enter the IP Address and the Port number the gateway shall write to.
 Select the update mode: Enable COS update or Enable auto update and COS.