Download Operating instructions
Transcript
Ethernet gateways Tab. 13: Auto update mode configuration command Note Parameter Command Request data set 1 Request data set 2 Request data set 3 Request data set 4 Heartbeat mode update rate Length WORD WORD WORD WORD WORD WORD Value 00E1hex = Auto update control 0 = Do not send data set 1 1 = Send data set 1 0 = Do not send data set 2 1 = Send data set 2 0 = Do not send data set 3 1 = Send data set 3 0 = Do not send data set 4 1 = Send data set 4 0 = Disable heartbeat messages Non-zero = Enable heartbeat message at specified rate in ms. Minimum = 40 ms Auto update is disabled if all Request Input Data Set flags are set to zero. The response message returned to the application by the gateway: Tab. 14: Auto update mode configuration response Parameter Command Length WORD Value 001Ehex = Response to the auto update control message Configuration via samos®PLAN tool In order to configure the Gateway writes to Address/Port (Auto update) mode of the gateway via the samos®PLAN tool, perform the following steps: Open the samos®PLAN and load the hardware configuration including the gateway. Click on the Gateway button above the main window and select the respective gateway to open the gateway configuration dialog. Click on TCP/IP configuration on the left hand menu. The following dialog appears: Fig. 17: TCP/IP configuration for auto update Check the Connect to checkbox. Enter the IP Address and the Port number the gateway shall write to. Select the update mode: Enable COS update or Enable auto update and COS. 34 Wieland | BA000587 | 09/2009 (Rev. A)