Ethernet gateways 5 Ethernet gateways This chapter describes the following samos®PRO gateways: • EtherNet/IP gateway (SP-EN-IP) • Modbus TCP gateway (SP-EN-MOD) • Profinet IO gateway (SP-EN-PN) 5.1 Common features of the Ethernet gateways 5.1.1 TCP/IP configuration interface The samos®PRO Ethernet gateways offer a TCP/IP configuration interface which allows the configuration of the samos®PRO System over Ethernet TCP/IP. This runs parallel to the Ethernet TCP/IP or other Ethernet protocols. Do not connect to the samos®PRO system via the RS-232 and the Ethernet interface at the same time! The samos®PRO system can only communicate with one instance of the samos®PLAN at one time. Connecting to the samos®PRO system using multiple instances of the Designer, either on a single PC or multiple PCs, may result in inconsistencies of the configuration and the diagnostics as well as in operational errors. This applies to both RS-232 and Ethernet connections equally. WA RNING In order to configure a gateway for TCP/IP configuration for the first time, perform the following steps: Step 1: Assign an IP address Connect a PC or notebook to the RS-232 interface of the SP-SCON. Power on the samos®PRO System. Open the samos®PLAN configuration tool installed on the PC and load the hardware configuration including the gateway. If your project is online, click on the Disconnect button to go offline. Click on the Gateway button above the main window and select the desired gateway. Click on Gateway configuration on the left hand menu. The following dialog appears: Wieland Electric | BA000587 | 09/2009 (Rev. A) 25