VECTOR DRIVE
Installation Manual
page 25
EXPLANATION OF PARAMETERS (117).
Address 000 : VO, VO.
At this address is programmed VO which can also be used as a relevelling speed.
Units :
Mini :
mettes per second (mls)
0,001 mls
,-
1/10 of V2
Factory value :
L
Address 001 : [Su,Relevelling speed.
At this address is programmed the relevelling speed.
Address 002 : INS, Inspection speed.
.
At this address is programmed the Inspection speed which can also be used as an
intermediate speed if V I is not used.
This speed is taken into account when the inspection input (INSI on K30) is activated
(VINS Led lit).
Unit :
Mini :
mettes pet- second (mfs)
0,20 mls
Factory value :
M
i:
0,60 m[s
0,50 mls
Address 003 : V I , Intermediate speed V I .
At this address is programmed the Intermediate speed V I .
Unit :
Mini :
Factory value :
metres per second (mls)
0,61 mls
Maxi :
0,61 mls
< V2