VECTOR DRIVE
page 14
Installation Manual
ELECTROMAGNETIC COMPATlBlLlTY PRECAUTIONS ( W 3 )
At not time should the screening cable replace the yellow-green earthing cable.
ADVICE : In order to ensure the electromagnetic compatibility, it may be necessary to use to connect to the
rnotor, a rnetal stuffing box with a screening contact allowing an efficient electrical link between
the flat screening cable and the metal housing (see figure below).
If the motor terminal box is isolated, then a metal stuff box is of course useless. The screening
cable should be linked in the shortest way to the rnotor earth terminal block.
Conventional connection :
Yelloy/Green
earthing cable
USlNO A SCREWDRNER
LOWRTHE MOBILE r u r E
10 INSERlTHE SCREENINO CIBLE
lin
Note Keep the motor cable as far apart from the power cable as
Note: The c a b z should only be separated from the
possible, inside as well as outside the controller.
once inside the terminal box.
screening
Connection using stuff-box :
CURVED SEAL
SCREENING
FLAT CABLE
TERMINAL
BOX WALL
3. The other links between the VECTOR DRIVE and the motor, i.e. the brake (+BR and
-BR), the motor thermistor (OV, STH) can run together but kept at least 10 cm from the
power cables.
-
EXAMPLE :
MOTOR SCREENED CABLE
11,12,13 AND EARTH + SCREENING
L i , L2, L3, + EARTH
TRUNKING
ONLY
ARRIVAL BOX
1-L
L I , NEUTRAL
MOTOREISTOR
THERMISTOR,
SHAFT WlRlNG
Check that the power supply arriva1 does not flow close
to the VECTOR DRIVE and motor link.