Download SPLIT SYSTEM AIR CONDITIONER
Transcript
10-2-3. Only outdoor unit does not run. A. Check setting temperature. COOL HEAT Is room temperature too low ? Is room temperature too high ? NO NO Try to lower setting temperature by temperature setting button ( button). Try to raise setting temperature by temperature setting button ( button). Outdoor unit still does not run. Outdoor unit still does not run. • Try to run using another remote control unit. • Try to run using another remote control unit. OK OK Remote control unit is defective. Remote control unit is defective. B. Check PCB Ass'y in either indoor or outdoor unit. • Check voltage between terminals No. 1(+) and No. 2 at the terminal plate. (DC 24V) OK • Outdoor PCB Ass'y is defective. No voltage appears. • Indoor PCB Ass'y is defective. 10-2-4. Only Indoor unit does not run. • Indoor PCB Ass'y is defective. 65