Pigeon Point Shel f Manager Us er Guide NAME TYPE DEFAULT TURBO_MODE_MIN _MISSING_FAN_T RAYS Number 1 UNCONDITIONAL_ SDR_REREAD_ON_ VERSION_CHANGE Boolean FALSE USE_DHCP Boolean FALSE Release 3.2.0 DESCRIPTION CAN BE OBTAINED FROM SHELF FRU INFO This parameter specifies the minimum Yes number of missing/inactive fan trays that triggers the remaining fan trays to go to TURBO mode (that is, run at full speed) in the default HPDL cooling management algorithm. If this parameter is set to 0, this feature of setting fans to their maximum speed (due to missing/inactive fan trays) is disabled, entirely. If the shelf implements zoned cooling, the specified number of missing/inactive fan trays is counted relative to each zone and setting TURBO mode affects only the fan trays that participate in cooling of the corresponding zone If the value of this parameter is TRUE Yes the Shelf Manager unconditionally rereads SDRs from an IPM controller when it receives a Version Change event from that controller, even if the Sensor Population Change Indicator in the “Get Device SDR Info” response does not change. This is done for the benefit of ATCA boards that are not fully IPMI-compliant in this respect. Requests assignment of RMCPYes accessible and private IP addresses for the Shelf Manager from a DHCP server; the configuration parameter DHCP_SERVER_ADDRESS can be used to specify the IP address of the DHCP server. 69 July 31, 2013