Download Mounting and Operating Instructions EB 8384-5

Transcript
Start-up and settings
NOTICE
Perform a reset before re-initializing
the positioner if the substitute positioner has already been initialized.
Refer to section 7.8.
Enable configuration:

Note:
If no settings are entered within 120
seconds, the enabled configuration
function becomes invalid.
Enable configuration
Default: No
Turn
g Code 3, display: No
Press
, Code 3 blinks.
Turn
 YES
Press
, display:
 Pin position on lever (see relevant
Turn
section on attachment)
Press
.
Turn
 Code 5
Press
, Code 5 blinks.
Turn
 Nominal travel of the valve
Press
.
Select the initialization mode:
Init mode
Default MAX
Turn
 Code 6
Press
.
Turn
 SUb
to confirm the SUb as the initializaPress
tion mode.
Enter the direction of action:
Enter the pin position and nominal range:
mm
mm
Pin position
Default: No
Nominal range
(locked when Code 4 = No)
Turn
 Code 4
Press
, Code 4 blinks.
EB 8384-5 EN
Direction of action
Default ÖÖ
Turn
 Code 7
Press
, Code 7 blinks.
Turn
 Direction of action (ää/äæ)
Press
.
69