Download Automation System TROVIS 5100 Ventilation
Transcript
Configuring the LON interface 6 LON communication (Co7, PA7, Co5 Fb03) LON communication (Co7, PA7, Co5 Fb03) The TROVIS 5177 Ventilation Controller can be linked together with other controllers from the TROVIS 5100 series in a specific SAMSON LON network. In this way, two outdoor temperatures, the flow temperature for externally required signal and the time can be exchanged among the connected controllers. A special communication tool is not necessary. Just the LON communication must be activated, an address allocated to each controller in the LON network as well as a definition about which controller sends which 6.1 value to the LON bus. It is possible to define that a controller send all values or each different value is sent from a separate controller. Data are transmitted every 4 minutes over the LON bus, except when the temperature values changes significantly (∆tA > 0.5 K; ∆tVL > 2 K) which are sent immediately. The values from the LON bus remain valid in the controllers for a maximum of 10 minutes before error routines become active. If the controller issuing the time fails, the time runs on locally in all the other controllers. Configuring the LON interface 1. Activate the function block Fb00 in Co7 to switch on LON communication. 2. Allocate a node address in PA7. A subnet is automatically assigned to each type of controller (e.g. 5174), see table below. Assign each controller a node address (1 to 20) in the parameter level PA7, making sure a node address is only assigned once within a subnet. But, for example, it would be permissible to assign the node address 9 for a TROVIS 5174 Controller as well as for a TROVIS 5179 Controller since they belong to different subnets. Controller type Subnet Node address 5174 4 1 to 20 5177 7 1 to 20 5179 9 1 to 20 Primary controller 1 1 You can optionally determine the following functions in Co7: You can define a controller to function as the primary controller in a control system, this is, however, not absolutely necessary. The primary controller receives the request for the externally required signal from all the other controllers and controls the primary flow temperature correspondingly. Activate Co7 Fb01 in a controller to turn it into the primary controller. Activate Co7 Fb02 to send the time. This function block, however, may only be set in one controller to ensure all the controllers function with the same time. If the time is sent over LON, all the other devices in a system automatically function with this time. Activate Co7 Fb03 to send the outdoor temperature Lon1 and activate Co7 Fb04 for outdoor temperature Lon2. After activating these function blocks, the number of the terminal to which the outdoor sen- 4 4 4 EB 5177 EN 79