62
Chapter
Zone Parameters
Data type
Adjustment range interfaces/ multiplier
Adjustment range BA
Unit
Unsigned Char
-100…[0]…100 / 1
-99…[0]…100
%
A detailed description of the function see chapter Process Monitoring.
[P102] FCON – Forced Cooling ON (Impulse Duration)
Data type
Adjustment range interfaces/ multiplier
Unit
Word
[0]…999 / 1
s
Is the parameter not equal 0 a forced cooling is executed. There is no limitation of output value at forced cooling.
See parameter [P103] FCCD – Forced Cooling Cycle Duration.
From HEX file version xx4310
[P103] FCCD – Forced Cooling Cycle Duration
Data type
Adjustment range interfaces/ multiplier
Unit
Word
[0]…99.9 / 10
h
Is the parameter not equal 0 a forced cooling is executed. There is no limitation of output value at forced cooling.
See parameter [P102] FCON – Forced Cooling ON (Impulse Duration).
From HEX file version xx4310
[P104] Cur% - Scaling of Heating Current
Data type
Adjustment range interfaces/ multiplier
Unit
Byte
0...[100]…255 / 1
%
All measured currents (e.g. by IO-component DIO16CI, BACI, CANCT, etc.) are scaled in the master component
(MCU, PCU).
Scaled current = Current IO-Component * [Cur%] / 100.0
On the status page of the master component the currents are scaled, on the other hand the currents on the status
page of the single IO-components are not scaled.