Download Operating Instructions
Transcript
62 Chapter Zone Parameters Data type Adjustment range interfaces/ multiplier Adjustment range BA Unit Unsigned Char -100…[0]…100 / 1 -99…[0]…100 % A detailed description of the function see chapter Process Monitoring. [P102] FCON – Forced Cooling ON (Impulse Duration) Data type Adjustment range interfaces/ multiplier Unit Word [0]…999 / 1 s Is the parameter not equal 0 a forced cooling is executed. There is no limitation of output value at forced cooling. See parameter [P103] FCCD – Forced Cooling Cycle Duration. From HEX file version xx4310 [P103] FCCD – Forced Cooling Cycle Duration Data type Adjustment range interfaces/ multiplier Unit Word [0]…99.9 / 10 h Is the parameter not equal 0 a forced cooling is executed. There is no limitation of output value at forced cooling. See parameter [P102] FCON – Forced Cooling ON (Impulse Duration). From HEX file version xx4310 [P104] Cur% - Scaling of Heating Current Data type Adjustment range interfaces/ multiplier Unit Byte 0...[100]…255 / 1 % All measured currents (e.g. by IO-component DIO16CI, BACI, CANCT, etc.) are scaled in the master component (MCU, PCU). Scaled current = Current IO-Component * [Cur%] / 100.0 On the status page of the master component the currents are scaled, on the other hand the currents on the status page of the single IO-components are not scaled. Rev. 1.02.16 Technical changes reserved