Service functions and error messages
Error message
Main
Sub
index
index
3
Meaning of the error message Measures
CAN:
exceeded, correct terminating resistors, cable
Communication error on receive shield grounded, all signals applied?).
Check the start sequence of the application.
Replace the device.
If the error could be eliminated by replacing the
device, please send the replaced device to our
sales partner.
4
CAN:
Equalize the cycle time of the remote frames with
Node Guarding
the PLC resp. failure of the PLC.
Signals interfered?
5
CAN:
Check the configuration.
RPDO too short
9
CAN:
Check the command syntax of the control
Protocol error
(record the data traffic).
Please contact the Technical Support.
13
0
Timeout CAN-Bus
Check CAN parameterisation.
14
0
Insufficient supply for
Check the power supply.
identification
Check the motor resistor.
Identification current controller:
The automatic parameter identification process
Measurement cycle insufficient
delivers a time constant beyond the
1
parameterisation value range. The parameters
must be optimized manually.
2
3
Power stage could not be
The power stage has not been enabled,
enabled
check the connection of DIN 4.
Power stage prematurely
The power stage has been disabled while the
disabled
identification process was running (for example
via DIN 4).
4
Identification does not support
The identification cannot be performed with the
selected resolver
present angle encoder settings.
Check the configuration of the angle encoder. If
necessary, contact the Technical Support.
5
No index pulse detected
The index pulse could not be found after the
maximum number of electrical rotations.
Check the index pulse signal.
Check the angle encoder settings.