Figure 5 Front View of the Container with Ramp Down Acclimatization HP 3PAR Storage systems shipped or stored at extreme temperatures may require time to adjust to operating temperatures before starting up. The maximum acceptable rate of temperature change for a non-operating system is 18° F/hr (10° C/hr). The storage system requires time to acclimatize to new environmental conditions before being powered on. During that time, it is possible to proceed with the physical installation of the storage system; however, the storage system may need at least 24 hours to acclimatize to a new environment prior to completing the full system installation. If condensation is present even after the 24 hour acclimatization period, it is necessary to wait until all condensation has evaporated before completing the power-on sequence. Shipping and Acclimatization Requirements 17