DUCT SMOKE DETECTOR
DH100ACDCLP
Purpose/Application
National and local safety standards and codes recognize
the ability of air duct systems to transfer smoke, toxic
gases, and flame from area to area. Sometimes smoke can
be of such quantity as to be a serious hazard to life safety
unless blowers are shut down and dampers are actuated.
The primary purpose of duct smoke detection is to prevent
injury, panic, and property damage by reducing the spread
(recirculation) of smoke. The detector samples air currents
passing through a duct and gives dependable performance
for management of smoke and combination fire smoke
dampers. Duct smoke detection can also serve to protect the
air conditioning system itself from fire and smoke damage.
There are several important documents that provide guidance
concerning the performance, application and installation of
duct detectors:
1) NFPA Standard 90A, Installation of Air Conditioning
and Ventilating Systems
2) NFPA Standard 92A, Recommended Practice for
Smoke Control Systems
3) NFPA Standard 72, National Fire Alarm Code
4) NFPA Standard 101, Life Safety Code
5) UL Standard 268A, Standard for Smoke Detectors for
Duct Applications
6) ASHRAE Handbook and Product Directory, “Fire and
Smoke Control”
7) System Sensor, Guide for Proper Use of Smoke
Detectors in Duct Applications.
Duct detectors are:
NOT a substitute for an open area smoke detector.
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection
system.
Specifications
Type: Photoelectric
Air duct velocity: 100 to 4000 fpm (.5 m/s to
20.3 m/s)
Operating temperature range: 32°F to 131°F (0°C to 55°C)
Operating humidity range: 10% to 93% R.H.
Operation Voltage: 24 VAC/DC or
120/240 VAC
Features
• Textured cover for convenient visual inspection.
• The detector provides a trouble signal in the event that the
front cover is removed.
• Integral filter system included to reduce dust and residue
effects on detector and housing, thereby reducing
maintenance and servicing.
• Terminal connections are of the strip and clamp method
suitable for 12-18 AWG wiring.
• Outside mounting tabs for easy connection to sleeve or
ductwork (when detector ships loose).
Configuration
Maximum wall thickness:6 in. (152mm) on FSD & SSFSD
applications
(Consult factory for walls greater
than 6 in. [152mm])
Actuator Location:
Must be right hand drive
Must be externally mounted
Detector Location:
Mounts opposite actuator side
Must be external
Sampling tubes longer than three feet must be supported
on each end. Holes in duct smoke detector sampling tubes
must face into the airflow.
Availability
For use with all FSD, SSFSD, SMD, SSSMD, and CFSD
models. Not available on SMDR models.
Listings
UL 268A
Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement
Sleeve Length
Ordering Options
Sleeve Length
Height less than 25 in. (635mm):
24 in. (610mm) sleeve (15 in. [381mm]‘A’ dimension)
(detector mounted parallel to sleeve)
Height greater than or equal to 25 in. (635mm):21 in. (533mm) sleeve (11 in. [279mm] ‘A’ dimension)
(detector mounted perpendicular to sleeve)
cJO
cJOY
HBNJOJNVN
SFUBJOJOHBOHMF
Figure 1: Label applied to
dampers with
factory mounted
duct smoke
detectors.
cJOYcJO
HBNJOJNVN
SFUBJOJOHBOHMF
4NPLFEFUFDUPSSFRVJSFTGQNNJOJNVN
BJSWFMPDJUZJOEVDU'PSEBNQFSBDUJWBUJPO
SFRVJSFNFOUTXIFOTZTUFNWFMPDJUZJTMFTT
UIBOGQNUIFMPDBMBVUIPSJUZIBWJOH
KVSJTEJDUJPOTIPVMECFDPOTVMUFE
"DDFTTPSZ0$*33-503
NPVOUFEFYUFSOBMMZPOSJHIU
IBOETJEFPGEBNQFS
3FGFSUPTNPLFEFUFDUPSJOTUBMMBUJPO
JOTUSVDUJPOTBOE(SFFOIFDL*0.4NPLF
%FUFDUPS4VQQMFNFOU'4GPSEBNQFSTXJUI
GBDUPSZNPVOUFEEVDUTNPLFEFUFDUPST
cJOYcJO
HBNJOJNVN
SFUBJOJOHBOHMF
%VDU#SFBLBXBZ$POOFDUJPO
CZPUIFST
)FJHIU
FRVBMUP
PSHSFBUFS
UIBO
JODIFT
cJOYcJO
HBNJOJNVN
SFUBJOJOHBOHMF
4NPLFEFUFDUPS
NPVOUFEFYUFSOBMMZ
POMFGUIBOETJEFPG
EBNQFS
4NPLFEFUFDUPS
NPVOUFE
FYUFSOBMMZPO
MFGUIBOETJEFPG
EBNQFS
/PUF "MMBDUVBUPSTXJMMCF
FYUFSOBMMZNPVOUFEPOUIF
SJHIUIBOETJEFPGEBNQFS
)FJHIUMFTTUIBO
JODIFT
%VDU#SFBLBXBZ
$POOFDUJPOCZPUIFST
"DDFTTPSZ0$*33-503
NPVOUFEFYUFSOBMMZPOSJHIU
IBOETJEFPGEBNQFS
/PUF "MMBDUVBUPSTXJMMCF
FYUFS OBMMZNPVOUFEPOUIF
SJHIUIBOETJEFPGEBNQFS
JOA"EJNFOTJPO
JOTMFFWFMFOHUI
JOXBMM
NBYJNVN
JONJOJNVNUP
BMMPXGPSSFUBJOJOH
BOHMFBOEEVDU
CSFBLBXBZ
DPOOFDUJPO
JOA"EJNFOTJPO
JOTMFFWFMFOHUI
Figure 2: Smoke detector mounting orientation for dampers
less than 25 inches (635mm) in height.
Smoke detector will be wired to a 4 in. x 4 in.
(102mm x 102mm) handi-box. The closure device
(if RRL or TOR) will also be wired to the handi-box.
Dampers provided with the smoke detector option
will include single point wiring as standard (includes
RRL, OCI, TOR, detectors, and multiple actuators).
Shipped Loose
Shipped loose smoke detector will only include the
detector itself (no mounting hardware or bracket
seals). The duct size will have to be specified in
order to allocate the appropriate length sampling
tube. Adhere to all national and local codes.
JONJOJNVNUP
BMMPXGPSSFUBJOJOH
BOHMFBOEEVDU
CSFBLBXBZ
DPOOFDUJPO
Figure 3: Smoke detector mounting orientation for dampers
equal to or greater than 25 inches (635mm) in
height.
Ordering Options
Factory Mounted
JOXBMM
NBYJNVN
IMPORTANT!
Dampers ordered with shipped loose smoke detectors
will have the standard sleeve length, not a longer sleeve
to accommodate the smoke detector installation. If
smoke detectors are intended to be field mounted on
the damper sleeve, the damper sleeve length and ‘A’
dimension will need to be manually changed to the
requirements indicated under ‘Sleeve Length’.
Space Envelopes
Electrical Ratings
Dampers Less Than 25 Inches (635mm) In Height
3 in.
Typical Actuator
(ML series shown; other
actuators available)
6 3⁄ 4 in.
Single Point W iring (Standard)
Smoke detector, actuator, and all
cont rol options are prewir ed to
junction box at the factor y.
Dampers Equal To Or Greater Than 25 Inches (635mm) In Height
2 3/4 in.
(70mm)
Typical Actuator
(other actuators available)
15 in.
(381mm)
Single Point Wiring
(Standard): Smoke
detector, actuator, and
all control optiong are
prewired to junction box
at the factory.
Electrical Ratings
Power Supply Voltage:
Input Capacitance:
Reset Voltage:
Reset Time:
Power Up Time:
Alarm Response Time:
Sensitivity Test:
Current Requirements
Max. Standby Current:
Max. Alarm Current:
20-29 VDC
24 VAC 50-60 Hz
120 VAC 50-60 Hz
220/240 VAC 50-60 Hz
270 µF max.
3.0 VDC min.
0.6 sec. max.
34 sec. max.
2-17 sec.
See detector label
270 µF max.
2.0 VAC min.
0.6 sec. max.
34 sec. max.
2-17 sec.
See detector label
N/A
10 VAC min.
0.6 sec. max.
34 sec. max.
2-17 sec.
See detector label
N/A
20 VAC min.
0.6 sec. max.
34 sec. max.
2-17 sec.
See detector label
15 mA
70 mA
35 mA RMS
125 mA RMS
25 mA RMS*
35 mA RMS*
15 mA RMS*
25 mA RMS*
Contact Ratings
Alarm Initiation Contacts (SPST):
2.0A @ 30 VAC/DC (0.6 power factor)
Alarm Auxiliary Contacts (DPDT):
10A @ 30 VDC
10A @ 250 VDC
Note:
Alarm auxiliary contacts must switch 100 mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected
to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
Trouble Contacts (SPDT):
2.0A @ 30 VDC (resistive)
Wiring Diagrams
Duct smoke detector
Fusible Link
RED
DH100ACDCLP DUCT DETECTOR
1 2 3 4 5 6 7 8 9 10
24 VAC/VDC
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
DH100ACDCLP DUCT DETECTOR
L1
115 VAC
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
MOTOR
RED
BLUE
WHITE
WHITE
L2
OPTIONAL
SECOND MOTOR
DH100ACDCLP DUCT DETECTOR
220/240 VAC
BLACK
WHITE
1 2 3 4 5 6 7 8 9 10
MOTOR
OPTIONAL
THIRD MOTOR
WHITE
BLUE
BLACK
WHITE
A B C
11 12 13 14 15 16 17 18 19 20
MOTOR
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
OCI
RED
DH100ACDCLP DUCT DETECTOR
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
OCI
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLUE
WHITE
SWITCH #2
SWITCH #1
YELLOW
YELLOW
YELLOW
YELLOW
24 VAC/VDC
RED
DH100ACDCLP DUCT DETECTOR
L1
115 VAC
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
MOTOR
RED
BLUE
OPTIONAL
SECOND MOTOR
WHITE
WHITE
L2
DH100ACDCLP DUCT DETECTOR
220/240 VAC
1 2 3 4 5 6 7 8 9 10
A B C
BLACK
WHITE
11 12 13 14 15 16 17 18 19 20
BLUE
MOTOR
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
WHITE
OPTIONAL
THIRD MOTOR
BLACK
WHITE
MOTOR
Wiring Diagrams
Duct smoke detector
RRL
RED
DH100ACDCLP DUCT DETECTOR
RRL
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
BLACK
ORANGE
24 VAC/VDC
DH100ACDCLP DUCT DETECTOR
115 VAC
L1
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
MOTOR
RED
BLUE
WHITE
WHITE
L2
OPTIONAL
SECOND MOTOR
DH100ACDCLP DUCT DETECTOR
220/240 VAC
BLACK
WHITE
1 2 3 4 5 6 7 8 9 10
MOTOR
OPTIONAL
THIRD MOTOR
WHITE
BLUE
BLACK
WHITE
A B C
11 12 13 14 15 16 17 18 19 20
MOTOR
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
RRL/OCI
RED
DH100ACDCLP DUCT DETECTOR
RRL
24 VAC/VDC
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
BLACK
ORANGE
SWITCH #2
SWITCH #1
YELLOW
YELLOW
YELLOW
YELLOW
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
DH100ACDCLP DUCT DETECTOR
115 VAC
L1
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
MOTOR
RED
BLUE
OPTIONAL
SECOND MOTOR
WHITE
WHITE
L2
DH100ACDCLP DUCT DETECTOR
220/240 VAC
1 2 3 4 5 6 7 8 9 10
A B C
BLACK
WHITE
11 12 13 14 15 16 17 18 19 20
BLUE
MOTOR
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
WHITE
OPTIONAL
THIRD MOTOR
BLACK
WHITE
MOTOR
Wiring Diagrams
Duct smoke detector
TOR
RED
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
DH100ACDCLP DUCT DETECTOR
TOR
1 2 3 4 5 6 7 8 9 10
L1
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
BLACK
SWITCH #2
SWITCH #1
SWITCHING DEVICE
(BY OTHERS)
YELLOW
YELLOW
YELLOW
YELLOW
BROWN
ORANGE
24 VAC/VDC
DH100ACDCLP DUCT DETECTOR
(OVERRIDE)
115 VAC
(PRIMARY)
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
MOTOR
RED
BLUE
WHITE
WHITE
L2
OPTIONAL
SECOND MOTOR
DH100ACDCLP DUCT DETECTOR
220/240 VAC
1 2 3 4 5 6 7 8 9 10
A B C
BLACK
WHITE
11 12 13 14 15 16 17 18 19 20
MOTOR
OPTIONAL
THIRD MOTOR
BLACK
WHITE
WHITE
BLUE
MOTOR
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
OCI w/ EP Switch
RED
DH100ACDCLP DUCT DETECTOR
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
OCI
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
BLUE
WHITE
SWITCH #2
SWITCH #1
YELLOW
YELLOW
YELLOW
YELLOW
24 VAC/VDC
RED
DH100ACDCLP DUCT DETECTOR
L1
115 VAC
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
RED
RED
BLUE
WHITE
RED
BLACK
WHITE
L2
OPTIONAL
SECOND E/P SWITCH
DH100ACDCLP DUCT DETECTOR
220/240 VAC
RED
E/P SWITCH
RED
BLUE
BLACK
WHITE
OPTIONAL
THIRD E/P SWITCH
RED
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
WHITE
RED
A B C
BLACK
WHITE
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
Wiring Diagrams
Duct smoke detector
RRL W/ EP Switch
RED
DH100ACDCLP DUCT DETECTOR
RRL
1 2 3 4 5 6 7 8 9 10
ORANGE
24 VAC/VDC
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
BLACK
RED
DH100ACDCLP DUCT DETECTOR
115 VAC
L1
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
RED
RED
BLUE
WHITE
RED
BLACK
WHITE
L2
OPTIONAL
SECOND E/P SWITCH
DH100ACDCLP DUCT DETECTOR
220/240 VAC
RED
RED
BLUE
BLACK
E/P SWITCH
RED
WHITE
OPTIONAL
THIRD E/P SWITCH
WHITE
A B C
BLACK
WHITE
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
RED
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
RRL/OCI W/ EP Switch
RED
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
DH100ACDCLP DUCT DETECTOR
RRL
1 2 3 4 5 6 7 8 9 10
ORANGE
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
BLACK
SWITCH #2
SWITCH #1
YELLOW
YELLOW
YELLOW
YELLOW
24 VAC/VDC
DH100ACDCLP DUCT DETECTOR
115 VAC
L1
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
RED
RED
BLUE
WHITE
RED
BLACK
WHITE
L2
OPTIONAL
SECOND E/P SWITCH
DH100ACDCLP DUCT DETECTOR
220/240 VAC
1 2 3 4 5 6 7 8 9 10
A B C
RED
E/P SWITCH
RED
BLUE
BLACK
WHITE
OPTIONAL
THIRD E/P SWITCH
RED
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
WHITE
RED
BLACK
WHITE
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
Wiring Diagrams
Duct smoke detector
TOR w/ EP Switch
RED
DH100ACDCLP DUCT DETECTOR
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).
TOR
L1
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
WHITE
BLUE
RED
BLACK
SWITCH #2
SWITCH #1
SWITCHING DEVICE
(BY OTHERS)
YELLOW
YELLOW
YELLOW
YELLOW
BROWN
ORANGE
24 VAC/VDC
DH100ACDCLP DUCT DETECTOR
(OVERRIDE)
115 VAC
(PRIMARY)
1 2 3 4 5 6 7 8 9 10
A B C
11 12 13 14 15 16 17 18 19 20
E/P SWITCH
RED
RED
BLUE
WHITE
RED
BLACK
WHITE
L2
OPTIONAL
SECOND E/P SWITCH
DH100ACDCLP DUCT DETECTOR
220/240 VAC
RED
E/P SWITCH
RED
BLUE
BLACK
WHITE
OPTIONAL
THIRD E/P SWITCH
WHITE
RED
A B C
11 12 13 14 15 16 17 18 19 20
BLACK
WHITE
1 2 3 4 5 6 7 8 9 10
E/P SWITCH
RED
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.
Copyright © 2008 Greenheck Fan Corporation
DH100 Smoke Detector Rev. 6 May 2008