Download Emerson DLC3020f Quick Start Guide
Transcript
Quick Start Guide DLC3020f Digital Level Controller D103470X012 July 2012 IECEx Conditions of Certification Intrinsically Safe & Dust This apparatus shall only be connected to an intrinsically safe certified equipment and this combination must be compatible regarding the intrinsic safety rules (see electrical parameters in table 4). Flameproof & Dust, Type n & Dust No conditions of certification. Refer to table 4 for additional approval information, and figure 26 for a typical ATEX/IECEx nameplate. Table 4. Hazardous Area Classifications—IECEx Certification Certification Obtained Entity Rating Temperature Code Enclosure Rating Fieldbus Intrinsically Safe Ex ia IIC T5/T6 Ga Dust Ex iaD 20 IP66 T87_C (Tamb ≤ 80_C) Da Ex iaD 20 IP66 T80_C (Tamb ≤ 73_C) Da IECEx Flameproof Ex d IIC T5/T6 Dust Ex tD A21 IP66 T87_C (Tamb ≤ 80_C) Ex tD A21 IP66 T80_C (Tamb ≤ 73_C) Type n Ex nA IIC T5/T6 Dust Ex tD A22 IP66 T87_C (Tamb ≤ 80_C) Ex tD A22 IP66 T80_C (Tamb ≤ 73_C) Ui ≤ 24 V Ii ≤ 380 mA Pi ≤ 1.4 W Ci + 5 nF Li + 0 mH FISCO T5(Tamb ≤ 80_C) T6(Tamb ≤ 73_C) IP66 T5(Tamb ≤ 80_C) T6(Tamb ≤ 73_C) IP66 T5(Tamb ≤ 80_C) T6(Tamb ≤ 73_C) IP66 Ui ≤ 17.5 V Ii ≤ 380 mA Pi ≤ 5.32 W Ci + 5 nF Li + 0 mH --- 9