Download Emerson CP200 Data Sheet

Transcript
Bulletin 71.1:CP200
TYPE 67CP PRESSURE
LOAdINg REgULATOR
CLOSINg
SPRINg
dIAPHRAgM
HEAd
dIAPHRAgM
LEVER
LOWER
CASINg
EXTERNAL
CONTROL LINE
PLUg (dO NOT
REMOVE IF UNIT IS
PRESSURIZEd)
VALVE STEM
ORIFICE
VALVE dISK
Figure 2. Typical CP200 Series Cut-away View
Introduction
The CP200 Series pressure loaded regulators have
been engineered to fit a multitude of pressure reducing
applications including commercial and industrial
installations. The CP200 Series provides accurate
control for use in pressure factor measurement (fixed
factor billing) applications. This flexibility is provided
by the various body end connection sizes, outlet
pressure settings, and orifice sizes.
2
Overpressure Protection Options
Available:
• Token Relief—Provides a small capacity or token
relief located in the Type 67CPR pressure loading
regulator that relieves minor overpressure caused by
thermal expansion or minor nicks in the orifice or disk.
• Secondary Seat™ Protection—Provides lockup
via a secondary seating and disk surface in the
event that damage to the primary disk or orifice
seating surface, or debris in the flow path, inhibit
primary lockup. Secondary Seat protection does
not provide additional overpressure protection in
the event the secondary seat or disk is damaged
by debris or contamination in the pipeline or from
conditions that would cause the regulator to go
wide open. See page 6 for additional information.