Download Tempest Cyclone 8000
Transcript
Cyclone HUSH Enclosures Cyclone HUSH enclosures must be provided with an exhaust duct for exhaust air, from the top of the enclosure to a location where the noise of the Cyclone fans will not be heard. This is usually an insulated ceiling void, drop ceiling, an adjoining room, or an outside wall. The exhaust duct is normally installed by an air conditioning installer, and rated for airflow as follows: Cyclone 8000, 8100 HUSH 500cfm 0.25m3/s Cyclone 8200 and up 1,000cfm 0.50m3/s The Cyclone HUSH enclosure is supplied with a fan plate to be mounted at the far end of the duct. Installer must provide a 3-conductor flexible cable rated at 250VAC, 10 Amps, conforming to local electrical standards, to connect the fan plate to the Cyclone DEC controller, and pulled either through the duct or in a separate electrical conduit. Power and Signal Conduit Entries Cyclone Enclosure User Manual page 13