3. Remove the interconnect cable from the failed interconnect card only.
Mark the connector with either 1 or 2.
4. Unlock the failed interconnect card by pushing in on the latch handle.
Latch handle
FIGURE 5-7
Removing the Interconnect Card
5. Pull the interconnect card out using the latch handle.
Caution – The interconnect card that is removed must be replaced within 30
minutes or the array and all attached arrays will automatically shut down and
power off.
6. Insert the new interconnect card, making sure that the card sits on the frame.
7. Lock the new interconnect card in place by pushing in on the latch handle.
8. Reconnect the interconnect cable to the interconnect card.
9. Verify that the LEDs on the interconnect card show that the interconnect card has
initialized properly.
You can verify the status of the interconnect card using either the CLI or Sun
StorEdge Component Manager. Refer to the Sun StorEdge T3 and T3+ Array
Administrator’s Guide or the Sun StorEdge Component Manager User’s Guide for
instructions.
Chapter 5
Service