Download Chapter 4 Explanation of function

Transcript
N300-P INSTRUCTION MANUAL
Chapter 4 Explanation of function
Relation code
Acceleration and deceleration pattern
A097 : Acceleration pattern selection
A098 : Deceleration pattern selection
A131 : Acceleration curve constant
A132 : Deceleration curve constant
(1) Selection of pattern
Pattern of acceleration and deceleration speed is
possible to set up corresponding to each system.
Select the pattern of acceleration and deceleration
with A097 and A098.
set value
00
curve
Line
02
Sigmoid
U-shape
Output frequency
Output frequency
Contents
time
time
Output frequency
Output frequency
time
Accelerate and
decelerate in line
frequency set value
Reverse U-shape
Output frequency
time
time
A098
(Deceleration)
03
Output frequency
Output frequency
Output frequency
A097
(Acceleration)
01
time
time
time
Collapsing the cargo such
as the going up and
down machine, conveyor
it uses it for prevention
Cutting the tension control, rolled book such as
the volume collector machine it uses it for
prevention
It is possible to set the pattern of both acceleration, deceleration
(2) The curve constant (the swelling degree)
It makes the rough sketch reference and please decide the swelling degree.
(100%)
(100%)
96.9
82.4
99.6
93.8
87.5
68.4
64.6
10
Output frequency(Hz)
Goal frequency
Output frequency(Hz)
Goal frequency
Output frequency(Hz)
Goal frequency
02
(100%)
10
65
02
35
17.6
3.1
50
02
10
12.5
6.25
02
10
25
35.4
31.6
75
Acceleration time to
output frequency
set value(100%)
0.39
10
time
25
50
75
Acceleration time to
output frequency
set value(100%)
25
50
75
Acceleration time to
output frequency
set value(100%)
There is the range which the midway adjustable-speed time becomse fast in the S character parrtern.
When An intelligent input terminal is allocated to LAD cancel (LAC) and the terminal is ON, output frequency
is immediately controlled by Setup frequency.