Matrix Installation and Operation Instructions IMPORTANT When using the Simplified System method, exhaust connection to the return must be 4’ from where the return connects to the Matrix. IMPORTANT All main HRV ductwork to be 6” round. Exterior connections are to be insulated and include a vapor barrier. 11.3 Damper Box Included in the installation kit is a damper box. This damper box eliminates the infiltration of cold outside air when the HRV is off or in defrost mode. It is to be installed with the actuator on the top side and screw to the Matrix using the four screws provided. Damper Box with Collar Installed 11.4 Condensate Drain Condensation from defrost will collect in the ventilator and drain from the sloped drain pan. This condensation must be evacuated from the unit. The condensate tubing provided must be routed through the hole in the side of the appliance and attached to the 90° elbow directly underneath the ventilation module. From there the condensate tube must be emptied into a suitable floor drain or if necessary the emptying drain must have a trap to prevent the infiltration of toxic gases. This End to Appropriate Drain or Condensate Pump Attach End of Supplied Tubing to 41