Download Carrier 38YKC Instruction manual
Transcript
3/8 IN. DIA TIEDOWN "_ KNOCKOUTS IN BASEPAN (2) PLACES NOTE: Avoid contact between tubing and structure OUTDOOR WALL-k ,NDOOR WALtz ? CAULK (_ -- &- LIQUID TUBE_ 2/-% J_'_ SULATION -_" _ ......... VAPOR TUBE THROUGH THE WALL J_"-JOIST HANGER STRAP'_ (AROUND VAPOR TUBE ONLY) %= -_,' \ /_ --8 3/16" INSULATION A97548 Dimensions (In.) I1 UNIT SIZE tl _--- MINIMUM MOUNTING PAD DIMENSIONS LIQUID TUBE SUSPENSION TIEDOWN KNOCKOUT LOCATIONS Support Feet Snow Stand 018, 024 20 X 27 24 X 28 4-1/8 7-1/8 030-060 26 X 32 31 X 35 5-1/16 9-11/16 A Fig. 3_Mounting B Unit to Pad A94028 Fig. 2---Connecting ---) Step 2--Install If conditions down bolts provided in to determine Step 5---Elevate Unit Tubing Installation on a Solid, Level Mounting Pad or local codes require the unit be attached to pad, tie should be used and fastened through knockouts unit base pan. Refer to unit mounting pattern in Fig. 3 base pan size and knockout hole location. eqmpment Elevate On rooftop applications, mount on level platform or frame 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications. damage. unit per clearance above drainage of unit. installed. freezing Use local climate estimated Fig. 4 shows accessory temperatures tion Instructions and code snowfall snow stand with in areas Refer to provide and ensure unit with accessory are encountered. packaged requirements level adequate support where to separate feet prolonged Installa- accessories. Roof mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind baffle construction. NOTE: Unit must be level to within _+ 2 ° (_+ 3/8 in./ft) per compressor manufacturer specifications. Step 3_Clearance Requirements When installing, allow wiring, refrigerant piping, sufficient service end of unit and 48 in. above space and service. for Allow airflow 30-in. clearance, clearance unit. For proper airflow, to a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position directly so water, snow, or ice from root" or eaves cannot fall on unit. On rooI_Lop applications, surface. locate unit at least 6 in. above roof A98534 Step 4_Operating Ambients Fig. 4---Accessory The minimum outdoor operating ambient in cooling mode is 55°F, and the maximum outdoor operating ambient in cooling mode is 125°F. The maximum outdoor operating ambient in heating mode is 66°F. _) Step 6_Check Support Feet Indoor and Outdoor AccuRater_ Piston Check indoor coil piston to see if it matches the required piston shown on outdoor unit rating plate. If it dees not match, replace 2