Download Code Alarm F65 Specifications

Transcript
www.pulsar.pl
PowerSecurity
APPENDIX A – FAILURE CODES OF THE PSBEN 13,8V POWER SUPPLY
Failure
code
Information
Technical
output
activation
F01
No AC power!
EPS FLT
F02
AUX Fuse!
PSU FLT
F03
BAT fuse!
APS FLT
F04
Output overload!!
F05
Faulty battery!
F06
High AUX voltage!
F07
High battery voltage!
PSU FLT
F08
Battery charging
circuit failure!
PSU FLT
F09
Low AUX voltage!
PSU FLT
F10
F11
F12
F13
F50-F54
F60
F61-F64
F65
Event
code
I00
I01
I02
I03
I04
I05
I06
PSU FLT
APS FLT
PSU FLT
APS FLT
Low battery voltage!
Low battery voltage –
off!
EXT external input!
PSU enclosure
opening!
Internal damage of the
PSU.
No communication
APS FLT
ALARM
Causes, comments
- No AC mains supply
- FMAIN fuse failure
- Blown FAUX fuse
- AUX output overload
- Blown FBAT fuse
- Short circuit in the battery circuit
- Short circuit in the AUX output circuit
- PSU overload
- Worn out batteries
- Undercharged batteries
- Battery not connected
- The output voltage of the PSU over 14.7V
- Battery voltage >14V
- The output voltage of the PSU set too low , below
13V
- Battery charging circuit failure
- The output voltage below 11.8V (during buffer
operation)
- The battery voltage has dropped below 11.5V
(during battery-assisted operation)
- the battery voltage has dropped below 10V (during
battery-assisted operation)
- Activation of the input of collective failure: EXT IN
PSU FLT
LCD damage
Access unlocked
PSU FLT
- service codes
PSU FLT
- no communication with LCD panel
PSU FLT
- service codes
- passwords unlocked
Description
PSU start-up
AC power restored
AUX fuse replaced
BAT fuse replaced
Battery status: OK
Battery test – START
Enclosure closed
21