Download Viessmann Vitodens 200-W Combi Operating instructions
Transcript
Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Boiler control unit LON Subscriber no. 1 Code "77:1" Control unit is fault manager Code "79:1" Control unit transmits the time Code "7b:1" Control unit transmits outside temperature Set code "97:2" LON subscriber fault monitoring Code "9C:20" Vitotronic 200-H Vitotronic 200-H LON LON Subscriber no. 10 Code "77:10" Control unit is not fault manager Code "79:0" The control unit receives the time Set code "81:3" The control unit receives the outside temperature Set code "97:1" LON subscriber fault monitoring Code "9C:20" Subscriber no. 11 Set code "77:11" Control unit is not fault manager Code "79:0" The control unit receives the time Set code "81:3" The control unit receives the outside temperature Set code "97:1" LON subscriber fault monitoring Code "9C:20" Vitocom Subscriber no. 99 Device is fault manager Device receives the time — — Carrying out a LON subscriber check Communication with the system devices connected to the fault manager is tested with a subscriber check. Preconditions: ■ The control unit must be programmed as fault manager (code "79:1") ■ The LON subscriber number must be programmed in all control units (see page 36) ■ The LON subscriber list in the fault manager must be up to date (see page 36) 2. "Service functions" 3. "Subscriber check" 1. Press OK and å simultaneously for approx. 4 s. 36 5692 857 GB Carrying out a subscriber check: