Download Drivedata DR2 Specifications
Transcript
Connection method 4.3.1 PROFIBUS-DP address and termination setting CNC unit address setting The address of the CNC unit is fixed to 2 (no hardware setting). Machine control panel I/O Set the DIP switch S1 on the PC board to a value between 3 and 32 such that each unit has a unique value. I/O module Set the DP address switch (DIP switch) on the ET200M interface module to a value between 3 and 32 such that each unit has a unique value. Converter Set the DIP switch to a value between 3 and 32 such that each unit has a unique value. Termination setting Set the termination switch on each PROFIBUS-DP connector as given below. Unit INFO Setting CNC unit ON Units in between OFF End units ON • Any unit other than CNC must not have its address set to 0, 1, or 2. • Up to 32 PROFIBUS-DP addresses are available with the YS 840DI system. • For information on how to specify addresses in software, see Chapter 9, Hardware Configuration. 4-20