Condensfit II telescopic flue and plume management
Greenstar Ri regular boilers are able to use the maximum
system measuring
100mm dia. internal flue length of 4,600mm regardless of
the amount of plume management selected.
Fig A
Option 1
Option 3
Plume management system
Plume management system with extensions and 45º bend
External plume management bends still need to be allowed
for. See below.
500mm
(min) (M)
L (max)
For Greenstar CDi Regular boilers the 100mm dia. internal
flue length must be reduced by 700mm for every additional
1,000mm of plume management, refer to table and
graph below.
60mm dia. plume management system
To ensure that the maximum total straight flue length along
the plume management route is not exceeded the following
Fig B
should be added to dimension (M):
Greenstar Ri series
• 1,500mm for each extra 90º bend
• 750mm for each extra 45º bend
4,500mm
(max) (M)
L (max)
Components required
Minimum
length (mm)
60mm
500
1
Greenstar CDi Regular series
For plume management options with 60mm dia. extensions
60mm
500*
Components required
Maximum
length (mm)
1
refer to pages 29 - 30.
Greenstar Ri series
60mm
Use the graph below to determine the permissible plume
Option 2
management length that can be used with your effective
Plume management system with extensions
flue length ‘L’.
3,750
1
up to 4
1
up to 4
1
Greenstar CDi Regular series
60mm
3,750*
1
The effective flue length can be determined by adding
Option 4
Effective straight flue lengths for telescopic flue with
plume management
together all the straight flue lengths and the effective
Plume management system with angled termination
Model
and 1,000mm for each 45º bend.
Fig. A
Fig. B
Max. straight flue
Max. straight flue
length (L) with min.
length (L) with max.
plume management
plume management
length 500mm (M)
length 4,500mm (M)
Ri series
4,600mm
4,600mm
30CDi Regular
5,900mm
3,100m
40CDi Regular
4,000mm
1,200mm
lengths of the bends used, 2,000mm for each 90º bend
8,000
Greenstar Ri series
60mm
Effective internal flue length ‘L’ (mm)
Components required
Maximum
length (mm)
Flue length ‘L’ versus plume management kit – Greenstar CDi Regular
7000
4,500
1
up to 4
Greenstar CDi Regular series
60mm
4,500*
1
up to 4
Greenstar Ri series
60mm
6000
Components required
Maximum
length (mm)
4,500
1
up to 4
Greenstar CDi Regular series
5000
60mm
4,500*
1
up to 4
4000
3000
2000
*NOTE: You must refer to the table and graph on page 28
1000
500
700
900
1100 1300 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500 3700 3900 4100 4300 4500
Plume management length ‘M’ (mm)
28
■ 30CDi Regular
■ 40CDi Regular
to calculate your horizontal flue lengths and plume
management length.
29