Download Worcester Greenstar Ri Technical data
Transcript
Condensfit II telescopic flue and plume management Greenstar Ri regular boilers are able to use the maximum system measuring 100mm dia. internal flue length of 4,600mm regardless of the amount of plume management selected. Fig A Option 1 Option 3 Plume management system Plume management system with extensions and 45º bend External plume management bends still need to be allowed for. See below. 500mm (min) (M) L (max) For Greenstar CDi Regular boilers the 100mm dia. internal flue length must be reduced by 700mm for every additional 1,000mm of plume management, refer to table and graph below. 60mm dia. plume management system To ensure that the maximum total straight flue length along the plume management route is not exceeded the following Fig B should be added to dimension (M): Greenstar Ri series • 1,500mm for each extra 90º bend • 750mm for each extra 45º bend 4,500mm (max) (M) L (max) Components required Minimum length (mm) 60mm 500 1 Greenstar CDi Regular series For plume management options with 60mm dia. extensions 60mm 500* Components required Maximum length (mm) 1 refer to pages 29 - 30. Greenstar Ri series 60mm Use the graph below to determine the permissible plume Option 2 management length that can be used with your effective Plume management system with extensions flue length ‘L’. 3,750 1 up to 4 1 up to 4 1 Greenstar CDi Regular series 60mm 3,750* 1 The effective flue length can be determined by adding Option 4 Effective straight flue lengths for telescopic flue with plume management together all the straight flue lengths and the effective Plume management system with angled termination Model and 1,000mm for each 45º bend. Fig. A Fig. B Max. straight flue Max. straight flue length (L) with min. length (L) with max. plume management plume management length 500mm (M) length 4,500mm (M) Ri series 4,600mm 4,600mm 30CDi Regular 5,900mm 3,100m 40CDi Regular 4,000mm 1,200mm lengths of the bends used, 2,000mm for each 90º bend 8,000 Greenstar Ri series 60mm Effective internal flue length ‘L’ (mm) Components required Maximum length (mm) Flue length ‘L’ versus plume management kit – Greenstar CDi Regular 7000 4,500 1 up to 4 Greenstar CDi Regular series 60mm 4,500* 1 up to 4 Greenstar Ri series 60mm 6000 Components required Maximum length (mm) 4,500 1 up to 4 Greenstar CDi Regular series 5000 60mm 4,500* 1 up to 4 4000 3000 2000 *NOTE: You must refer to the table and graph on page 28 1000 500 700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500 3700 3900 4100 4300 4500 Plume management length ‘M’ (mm) 28 ■ 30CDi Regular ■ 40CDi Regular to calculate your horizontal flue lengths and plume management length. 29